3.1 Vent Stacks, Relief Vents & Vent Sizing Tables

Key Takeaways

  • Vents must limit the pneumatic pressure differential on any trap seal to 1 inch of water column (SPS 382.31 (3) (a)).

  • A vent stack and a stack vent are required for any drain stack of 5 or more branch intervals; stacks of more than 10 branch intervals need a relief vent at each tenth interval.

  • A building drain that drops 12 feet or more at an angle of 45 degrees or more needs a relief vent connected within 2 feet upstream of the drop.

  • Vents connecting to other vents must do so at least 38 inches above the floor and at least 2 inches above the flood level rim of the highest fixture served.

  • Table 382.31-3 sizes branch, individual, common and circuit vents by dfu and developed length; a 1-1/4 inch vent may serve no water closets.

Last updated: October 2026

The performance rule behind every vent table

SPS 382.31 (3) (a) states the goal: every trap and trapped fixture gets an individual vent unless the chapter allows another method. Vent systems must be designed so that a trap seal "shall be subject to a maximum pneumatic pressure differential equal to one inch of water column." Every table in this chapter exists to meet that 1-inch limit.

Stacks that must be vented

SituationRequirement
Every gravity sanitary building sewerAt least one stack, minimum 3 inches, from building drain to vent terminal or vent header (3) (b)
Drain stack of 5 or more branch intervalsVent stack plus stack vent (4) (a)
Drain stack of more than 10 branch intervalsRelief vent at each tenth interval (6)
Offset of 30 to 45 degrees with a branch within 2 ft, 5 or more intervals aboveOffset venting per (5) (a), unless stack and offset are sized as building drain
Offset over 45 degrees with 5 or more intervals aboveVent upper section as its own stack, plus a yoke vent on the lower section (5) (b)
Building drain dropping 12 ft or more at 45 degrees or moreRelief vent (7)

Vent stack connections. The vent stack connects to the drain stack at or below the lowest branch drain connection, using a wye-pattern fitting in a vertical part of the stack. The vent stack and stack vent then either run to a vent terminal, join a vent stack that does, or connect to a stack vent at least 6 inches above the flood level rim of the highest fixture on the drain stack. Where a vent stack joins another vent, the joint must be at least 38 inches above the next higher floor where vented fixtures are located, and never less than 2 inches above the highest flood level rim served.

Relief vents for tall stacks. On stacks over 10 intervals, the relief vent's lower end connects with a wye below the horizontal branch on that floor, and its upper end ties to the vent stack at least 38 inches above the next higher floor with fixtures on the stack.

Building drain relief vents. The relief vent connects with a wye within 2 feet upstream of the top of the change in elevation. Its connection to another vent is at least 38 inches above the next higher floor. It must be at least half the diameter of the building drain.

Vent grade and connection heights (SPS 382.31 (15))

  1. All vents must be graded to drain back to a drain pipe by gravity.
  2. Except for wet vents, a vent connects to horizontal drain piping above the horizontal centerline of the drain.
  3. A vent serving a wall-outlet fixture may not run horizontally lower than 36 inches above the floor, and never below the highest flood level rim it serves (return vents and combination systems excepted).
  4. Vent piping may not connect to a branch vent lower than 38 inches above the floor, and never less than 2 inches above the highest flood level rim served.

Sizing stack vents and vent stacks (Table 382.31-2)

Stack vents and vent stacks are sized from the diameter of the drain stack at its base and the developed length of the vent. The developed length of a stack vent is measured from the highest drain branch connection to the vent terminal or header. For a vent stack, it is measured from its base connection to the terminal or header.

Drain stack at base (in.)1-1/2 vent2 vent3 vent4 vent5 vent
250 ft150 ftno limit--
3NP50 ft400 ftno limit-
4NP20 ft180 ft700 ftno limit
5-NP50 ft200 ft700 ft
6-NP20 ft70 ft200 ft

A 1-1/2 inch stack vent may serve no more than 2 water closets or similar flush-action fixtures of 4 or more dfu. Yoke vents are sized as vent stacks.

Sizing individual, common, branch and circuit vents and vent headers (Table 382.31-3)

These vents are sized by the dfu they serve and the developed length from the farthest fixture drain served to the point where the vent joins a larger vent or the terminal.

dfu served1-1/4 in.1-1/2 in.2 in.3 in.4 in.
250 ftno limit---
440 ft200 ftno limit--
8NP150 ft250 ftno limit-
10NP100 ft200 ftno limit-
24NP50 ft150 ftno limit-
42NP30 ft100 ft500 ftno limit
72-NP50 ft400 ftno limit
240-NP40 ft250 ftno limit
500-NP20 ft180 ft700 ft

Footnotes: a 1-1/4 inch vent may serve no water closets, and a 1-1/2 inch vent may serve no more than 2 water closets or similar fixtures of 4 or more dfu. A vent header uses the sum of the dfu of all stacks it vents and may not be smaller than any vent connecting to it.

Worked example 1. A branch vent serves 20 dfu with a developed length of 120 feet. Use the 24-dfu row: 1-1/2 inch allows only 50 feet, 2-inch allows 150 feet, so the vent is 2 inches.

Worked example 2. A 4-inch drain stack needs a stack vent with a 100-foot developed length. In Table 382.31-2 a 2-inch vent is limited to 20 feet and a 3-inch vent to 180 feet, so use 3 inches.

Relief vent sizing. A relief vent for a circuit-vented branch must be at least half the branch diameter. A relief vent for a horizontal wet vent must be at least 1-1/2 inches. Lengths for both come from Table 382.31-3.

Loading diagram...
Choosing the vent table
Test Your Knowledge

When must a drain stack be provided with both a vent stack and a stack vent under SPS 382.31 (4)?

A

When it serves any water closet

B

When it serves 5 or more branch intervals

C

When it is larger than 3 inches

D

When it has 3 or more branch intervals

Test Your Knowledge

A branch vent serves 20 dfu and has a developed length of 120 feet. What is the minimum vent diameter under Table 382.31-3?

A

1-1/4 inches

B

1-1/2 inches

C

3 inches

D

2 inches

Test Your Knowledge

A vent will connect to a branch vent in a bathroom whose highest fixture flood level rim is 36 inches above the floor. What is the lowest permitted connection height?

A

38 inches above the floor

B

42 inches above the floor

C

36 inches above the floor

D

6 inches above the floor