8.1 Approved Piping Materials by Service & Lead-Free Rules

Key Takeaways

  • Lead-free means no more than 0.2 percent lead in solder and flux and no more than a 0.25 percent weighted average on wetted surfaces (SPS 381.01 (141)); leaded joints are allowed only to repair cast iron pipe.

  • Water service and private main pipe must be rated at least 150 psig at 73.4 degrees F; water distribution pipe at least 100 psig at 180 degrees F.

  • Type M copper tubing may not be installed underground, and copper may not be used where the water's pH is 6.5 or less.

  • Plastic or copper pipe within 1 inch of a framing edge needs a steel plate of at least No. 18 gauge extending 1-1/2 inches beyond the pipe.

  • Kinked pipe, pipe with gouges or deep scratches, bent rigid pipe and piping previously used for anything but potable water may not be installed in water supply systems.

Last updated: October 2026

General rules (SPS 384.30 (1))

Design must consider sizing, working pressure, temperature, material compatibility with the water or wastewater, and the installation environment. CR 26-019, effective September 1, 2026, added these handling rules:

RuleRequirement
Flexible or annealed pipeBend or offset only per the material standard or manufacturer
Rigid pipeBending or offsetting is prohibited
Damaged pipeNo gouges, cuts or deep scratches; kinked pipe may not be installed
Framing protectionPlastic or copper pipe through framing within 1 inch of the edge gets a steel plate of at least No. 18 gauge extending 1-1/2 inches beyond the pipe
Low-flow treatment pipingPiping downstream of treatment devices serving outlets under 1 gpm is sleeved through walls, floors and structural members

Lead-free (SPS 384.30 (1m) and SPS 381.01 (141))

Lead-free means:

  • No more than 0.2 percent lead in solder and flux.
  • No more than a weighted average of 0.25 percent lead on the wetted surfaces of pipes, fittings and fixtures.

Weighted average = the sum, over every wetted component, of (percent lead of the component x its share of total wetted area). Use the maximum value of any range. Count coatings and liners, but exclude filter media.

Non-lead-free material may not be used to install or repair any public water system or any plumbing that provides water for human consumption. The only exception is leaded joints needed to repair cast iron pipe. Drinking water coolers have extra limits: no more than 0.2 percent lead in solder, flux or tank surfaces, and no more than 8 percent in any single wetted part.

Drain, waste and vent materials (SPS 384.30 (2) and (3))

ServiceTableNotes
Aboveground drain and vent384.30-1ABS, brass, cast iron, CPVC, copper, ductile iron, galvanized steel, PE, PP, PVC (Schedule 40 for F891 cellular core), PVDF, 304 and 316L stainless; synthetic rubber hose only for dishwasher indirect or local waste
Underground drain and vent384.30-2ABS, brass, cast iron, CPVC, copper (no Type M), ductile iron, PVC (D3034 limited to SDR 26 or less; F891 to Schedule 40), 316L stainless; no galvanized steel underground
Sanitary building sewer384.30-3Adds concrete, PE, PP, vitrified clay (extra strength) and PVC sewer profiles; thermoplastic sewer pipe installed per ASTM D2321
POWTS non-perforated, non-pressurized384.30-3Same as building sewer
POWTS perforated gravity distribution384.30-4PE and PVC must have exactly 2 rows of holes, 120 degrees plus or minus 5 apart, at the 4 and 8 o'clock positions
Pressurized drain, POWTS pressure laterals, service suction lines384.30-5Rated for working pressure and temperature
Storm building sewer384.30-6Includes elliptical concrete; thermoplastic per ASTM D2774
Storm conductors inside buildings384.30-1Black steel (ASTM A53) also allowed but may not be embedded in concrete or masonry
Chemical drain and vent-Corrosion-resistant material the manufacturer verifies for the chemicals

Catch basins, interceptors and sumps must be watertight and built of precast or monolithic reinforced concrete, cast iron, coated 12-gauge steel, vitrified clay, fiberglass, plastic or other approved material. Fiberglass manholes are allowed in traffic areas only if the top section is not fiberglass. Roof drains need removable strainers and an outlet of at least 2 inches.

Water supply materials (SPS 384.30 (4))

UseMinimum ratingTable
Water services and private water mains150 psig at 73.4 degrees F384.30-7
Water distribution100 psig at 180 degrees F384.30-8
Underground cold water distribution150 psig at 73.4 degrees F384.30-7 or 384.30-8
Cold distribution downstream of under-1-gpm treatment devices100 psig at 73.4 degrees F384.30-8 or 384.30-11, marked every 4 ft

All water supply pipe and fittings must be lead-free (no more than 0.25 percent weighted average). Plastic water pipe must be certified for potable water by an acceptable listing agency. Key footnotes:

  • Type M copper may not be installed underground.
  • Copper may not be used where the water's pH is 6.5 or less.
  • 304 stainless may not be installed underground.
  • Plastic services are installed per ASTM D2774.
  • Combination fire and domestic services and mains must also meet NFPA 24.
  • A local government may restrict water service materials in rights-of-way by ordinance, but only after department review.

Water piping is prohibited in contaminated soil or groundwater (solvents, fuels, organics) unless the contamination is eliminated, the pipe and joints are proven resistant, or the route avoids it. A chemical analysis may be required where contamination is suspected. Used piping that has carried anything other than potable water may never be reused for water supply.

Fittings, valves and special materials (SPS 384.30 (5) and (6))

  • Fittings meet the pipe standard or Table 384.30-9. Threaded drain fittings must be the recessed drainage type. Steel and malleable iron fittings in water systems must be galvanized.
  • Water service valves are rated at least 125 psig at 73.4 degrees F; distribution valves at least 100 psig at 180 degrees F.
  • A valve serving 2 or more fixtures may not be a globe valve, and its open passage must be no more than one nominal size smaller than the pipe.
  • Special devices: water hammer arrestors ASSE 1010; pressure-reducing valves ASSE 1003; backwater valves ASME A112.14.1 or CSA B1800; stack AAVs ASSE 1050 and branch AAVs ASSE 1051; trap primers ASSE 1018 (water-fed) and 1044 (drainage and electric); freeze-resistant wall hydrants ASSE 1019; sanitary yard hydrants ASSE 1057; push-fit fittings ASSE 1061 (only 2 inches and under, and not in T&P drain lines unless rated for 210 degrees F and 150 psig).
  • Sheet lead flashing: 3 lb/sq ft site-fabricated, 2-1/2 lb/sq ft prefabricated. Sheet copper: 8 oz/sq ft for vent flashing and 10 oz/sq ft for flush tank linings.
  • Copper or tubular brass traps are at least 20 gauge. Brass cleanout plugs go only in metallic piping.
  • Safing must stay waterproof under 2 feet of hydrostatic head (ASTM C1306 or D4068).
  • POWTS aggregate is washed stone 1/2 to 2-1/2 inches with a Mohs hardness of at least 3.
Loading diagram...
Choosing a pipe material
Test Your Knowledge

What maximum lead content defines lead-free solder and flux under SPS 381.01 (141)?

A

0.25 percent

B

0.2 percent

C

2 percent

D

8 percent

Test Your Knowledge

Which material is NOT allowed for an underground water service under Table 384.30-7 and its footnotes?

A

Type K copper

B

PEX installed per ASTM D2774

C

Type M copper

D

Ductile iron

Test Your Knowledge

What minimum working pressure rating applies to water distribution pipe under SPS 384.30 (4) (e) 1.?

A

150 psig at 73.4 degrees F

B

125 psig at 73.4 degrees F

C

80 psig at 140 degrees F

D

100 psig at 180 degrees F