8.3 Hangers, Supports & Protection of Piping (SPS 382.60)

Key Takeaways

  • Drain piping is designed as if full of water, and hangers must be compatible with the pipe so they do not cause galvanic action or cut or abrade it.

  • Table 382.60 limits horizontal support spacing to 4 feet for PVC and ABS (5 feet for PVC vents), 5 feet for cast iron (10 feet with 10-foot lengths) and 2 feet 8 inches for PEX.

  • Copper tubing 1-1/4 inch and smaller is supported every 6 feet horizontally; 1-1/2 inch and larger every 10 feet; copper pipe and steel pipe every 12 feet.

  • Hubless pipe laid horizontally must be supported within 24 inches on each side of a joint unless the joint has an alignment retaining shield.

  • Hangers may not be attached with wood plugs, and shower valves and piping to the showerhead must be securely fastened to the structure.

Last updated: October 2026

Materials and strength (SPS 382.60 (1))

  • Hangers, anchors and supports must carry the piping and its contents. Drain piping is considered full of water for this purpose.
  • Underground piers for pipe support must be concrete, masonry, plastic or pressure-treated wood.
  • Hangers and straps must be of a compatible material that reduces galvanic action, and may not distort, cut or abrade the pipe. Bare steel strap on copper is the classic violation.

Installation (SPS 382.60 (2))

  1. Hangers and anchors are attached securely to the building structure at intervals no greater than Table 382.60. PVC used for venting may be supported every 5 feet horizontally.
  2. The connection of drain piping to a fixture or appliance counts as a point of support.
  3. Hubless pipe installed horizontally must be supported within 24 inches on each side of a joint, unless the joint has an alignment retaining shield.
  4. Hangers may not be attached with wood plugs.
  5. Shower valves and the piping from the valve to the showerhead outlet must be securely attached to the structure.

Table 382.60 support spacing

MaterialMax horizontal spacingMax vertical spacing
ABS4 ft10 ft
Brass10 ft10 ft
Cast iron5 ft (10 ft with 10-ft lengths)15 ft
Copper or copper-alloy pipe12 ft10 ft
Copper tubing, 1-1/4 in. and smaller6 ft10 ft
Copper tubing, 1-1/2 in. and larger10 ft10 ft
CPVC, 1 in. and smaller3 ft5 ft (mid-story guide)
CPVC, 1-1/4 in. and larger4 ft6 ft (mid-story guide)
PEX2-2/3 ft (2 ft 8 in.)4 ft
Ductile iron5 ft (10 ft with 10-ft lengths)15 ft
Galvanized steel12 ft15 ft
LeadContinuous4 ft
Polybutylene2 ft 8 in.4 ft
PE, PP, PVDF, flexible PVC2 ft4 ft
PVC4 ft (5 ft for vents)10 ft
Stainless steel12 ft15 ft

"Mid-story guide" (CPVC vertical) means a guide is also required midway between floors.

Worked examples

PVC drain. A 60-foot horizontal run of 3-inch PVC drain needs supports at no more than 4-foot intervals: 60 / 4 = 15 spaces, so about 16 supports counting both ends. Where the drain connects to a fixture, that connection counts as one support point. If the same pipe were a vent, 5-foot spacing would need about 13 supports.

Cast iron. No-hub cast iron in 10-foot lengths may be hung every 10 feet. But each horizontal no-hub joint without an alignment shield still needs a support within 24 inches on each side. In practice that means a hanger near every coupling.

PEX. A 40-foot horizontal PEX run needs supports no more than 2 feet 8 inches (32 inches) apart: 480 inches / 32 = 15 spaces, so about 16 supports. That is why PEX is often run in continuous channel or laid on joists. Continuous support satisfies the spacing limit.

Copper. In a 1-inch copper tube riser through a three-story building, Table 382.60 requires vertical support at least every 10 feet. Horizontally the same 1-inch tube needs support every 6 feet; a 2-inch tube, every 10 feet.

Related protection rules

TopicRuleSection
Framing penetrationsSteel plate of at least No. 18 gauge where plastic or copper pipe is within 1 inch of the framing edge, extending 1-1/2 inches beyond the pipeSPS 384.30 (1) (e)
FreezingAll water supply piping protected from freezing; exterior wall hose bibbs frost-proof and self-drainingSPS 382.40 (8) (a)
TrapsRigidly supported, set level, protected from freezing and evaporationSPS 382.32 (4) (a)
Fire-resistive assembliesPenetrations protected per the commercial building code, chs. SPS 361 to 366SPS 384.13
Wall-hung fixturesCarriers meet ASME A112.6.1M or A112.6.2; no load on the drain connectionSPS 384.20 (4) (b) 2.
Water distribution supportDistribution piping supported per SPS 382.60SPS 382.40 (8) (d) 1.
Vacuum drainage systemsHangers per SPS 382.60SPS 382.30 (14) (i)

Rough-in inspection checklist for supports

Before calling for a rough-in inspection, walk the job with the table in hand:

  1. Measure the longest unsupported horizontal run of each material and compare it to Table 382.60. Remember the fixture connection counts as one support.
  2. Check every horizontal no-hub coupling for a hanger within 24 inches on each side, or an alignment shield.
  3. Confirm that hangers are fastened to structure (not to other piping, ductwork or wood plugs), and that straps match the pipe material.
  4. Look at risers: vertical supports at the table spacing, and mid-story guides on CPVC.
  5. Verify that shower valves and the piping to the showerhead are rigidly fastened, and that nail plates protect pipe within 1 inch of framing edges.

Exam traps

  • Answering "10 feet" for horizontal cast iron: the base value is 5 feet, rising to 10 only with 10-foot lengths.
  • Confusing copper pipe (12 ft) with copper tubing (6 or 10 ft).
  • Forgetting that drain piping counts as full of water when sizing hangers.
Loading diagram...
Placing pipe supports
Test Your Knowledge

What is the maximum horizontal support spacing for PVC drain piping under Table 382.60?

A

4 feet

B

5 feet

C

6 feet

D

10 feet

Test Your Knowledge

How must horizontal hubless cast iron pipe be supported at a joint that has no alignment retaining shield?

A

Within 6 inches of the joint on one side

B

Within 24 inches on each side of the joint

C

At every second joint

D

Only at changes of direction

Test Your Knowledge

What is the maximum horizontal support spacing for 3/4-inch PEX tubing under Table 382.60?

A

4 feet 0 inches

B

6 feet 0 inches

C

3 feet 6 inches

D

2 feet 8 inches