6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation

Key Takeaways

  • Air gaps, reduced pressure principle assemblies (ASSE 1013) and reduced pressure detector assemblies (ASSE 1047) are allowed for every hazard, pressure and backflow condition.

  • Double check assemblies (ASSE 1015), double check detector assemblies (ASSE 1048) and dual checks (ASSE 1024) are limited to low hazard situations.

  • Atmospheric vacuum breakers are allowed only for back-siphonage with noncontinuous pressure, at least 6 inches above the flood rim or highest downstream point, with no valve downstream.

  • Pressure and spill-resistant vacuum breaker assemblies handle back-siphonage only and must be at least 12 inches above the flood rim or highest downstream outlet.

  • Testable assemblies must sit 12 inches to 7 feet above the access floor, with 18 inches below the ceiling, 4 inches at back and ends, and 24 inches in front.

Last updated: October 2026

Reading Table 382.41-1

The table has eight condition columns: backpressure or back-siphonage, each split into low or high hazard, each split into continuous or noncontinuous pressure. A device is acceptable only where the table marks an X. Footnote a limits a mark to campgrounds and marinas; footnote b limits it to a maximum of 10 feet of backpressure. The table was recreated by CR 26-019, effective September 1, 2026.

Method, device or assembly (standard)Backpressure, low hazardBackpressure, high hazardBack-siphonage, low hazardBack-siphonage, high hazard
Air gap (ASME A112.1.2), air gap fitting (A112.1.3)AllAllAllAll
Reduced pressure principle assembly (ASSE 1013 / CSA B64.4) and fire version (B64.4.1)AllAllAllAll
Reduced pressure detector assembly (ASSE 1047)AllAllAllAll
Double check assembly (ASSE 1015 / CSA B64.5) and fire version (B64.5.1)All-All-
Double check detector assembly (ASSE 1048)All-All-
Dual check (ASSE 1024 / CSA B64.6)All-All-
Intermediate atmospheric vent (ASSE 1012 / CSA B64.3)All-All-
Pressure vacuum breaker assembly (ASSE 1020 / CSA B64.1.2)--AllAll
Spill-resistant vacuum breaker assembly (ASSE 1056 / CSA B64.1.3)--AllAll
Barometric loop; vacuum breaker tee--AllAll
Atmospheric vacuum breaker (ASSE 1001 / CSA B64.1.1)--Noncontinuous onlyNoncontinuous only
Hose connection vacuum breakers (ASSE 1011, B64.2, B64.2.1, B64.2.2); hose connection backflow preventer (ASSE 1052)Noncontinuous; continuous only at campgrounds and marinas; 10 ft maxSameNoncontinuous; continuous only at campgrounds and marinasSame

"All" means every pressure condition in that hazard group.

Two quick rules: (1) for high hazard backpressure, only an air gap, RP or RPDA works; (2) for high hazard back-siphonage, add PVB, SVB, AVB (noncontinuous), barometric loop and vacuum breaker tee to that list.

Device limitations (SPS 382.41 (4))

DeviceLimitation
Atmospheric vacuum breakerBottom or critical level mark at least 6 inches above the flood rim, the highest downstream backpressure point and any injection port; 1 inch for deck-mounted AVBs. No control valve downstream (5) (h)
Pressure vacuum breaker assemblyAt least 12 inches above the flood rim, highest downstream point and injection ports
Spill-resistant vacuum breaker assemblyAt least 12 inches above the same points
Water-fed trap seal primer valveAt least 12 inches above the trap connection and highest downstream point
Hose connection vacuum breaker or backflow preventerOnly on the discharge side of a faucet or bibb; no more than 10 ft of backpressure; continuous pressure only at campgrounds and marinas
Freeze-resistant wall and yard hydrantsNo more than 10 ft of backpressure
Intermediate atmospheric vent (ASSE 1012)No more than 150 psig backpressure; may not serve boilers set above 15 psig steam or 30 psig water
RP, RPDA, DC, DCDABackpressure no more than twice the rated working pressure
RP or DC on fire systems, 2 inches or smallerNo test cock required on the number 1 control valve; RP may have a test outlet between check 2 and valve 2
Hand-held showerNo more than 5 ft of backpressure
Laboratory faucet backflow preventerNo more than 6 ft of backpressure; no valve downstream
Device on an exterior hose bibbMay not defeat the frost-proof, self-draining feature

Installation rules (SPS 382.41 (5))

  • Install per the manufacturer and the code. Devices must be accessible for inspection, testing, maintenance and replacement, and protected from freezing.
  • No device may be in an uninhabitable space subject to flooding, unless it has no vent port. A device with vent ports may never be in a pit, vault or depression below grade or floor, even one with a floor drain.
  • Vent ports must face down or be shielded from debris, stay away from toxic fumes, drain dry, and discharge through an air gap.
  • Inside a building, a PVB, RP or RPDA needs a drain or receptor for its vent-port discharge, with an air gap, and the discharge path may not create a nuisance. Local waste piping from a device must have a visible outlet, not inside a concealed space.

Clearances for testable assemblies (RP, RPDA, DC, DCDA, PVB, SVB):

DimensionRequirement
Access floor to lowest point of assemblyAt least 12 inches, no more than 7 feet
Ceiling or obstruction to highest pointAt least 18 inches
Wall to back and endsAt least 4 inches
Wall to frontAt least 24 inches

Barometric loop: rises at least 35 feet above the highest downstream backpressure point and the discharge point, with no potable outlets downstream of the peak. Vacuum breaker tee (for water treatment device drains): the bottom of the horizontal portion is at least 1 inch above the receptor rim, and the tee and its vent are at least the drain's inside diameter. Chemical dispensers need an individually connected fixture supply or a pressure-bleeding device that creates a visible free flow into the drain.

Worked selections

  1. Boiler with an automatic chemical feeder (high hazard, continuous, backpressure): an RP assembly or an air gap. A double check is not allowed.
  2. Lawn sprinkler zone with a fertilizer injector, fed from a valve that stays open (high hazard, continuous pressure, back-siphonage only because there is no pump or elevated outlet): a PVB at least 12 inches above the highest head and the injection port, or an RP.
  3. A low hazard process connection under continuous pressure with possible backpressure (the manufacturer specifies only nontoxic solutions): a double check assembly, dual check (ASSE 1024) or intermediate atmospheric vent device (ASSE 1012) satisfies the table, as would an RP or air gap. Footnote c reminds you to check SPS 384 for application-specific devices before choosing.
  4. Mop sink faucet in a public building (high hazard, noncontinuous after the faucet, back-siphonage): an AVB on the faucet at least 6 inches above the sink rim, with no valve downstream, or a hose connection vacuum breaker.
Loading diagram...
Picking a device from Table 382.41-1
Test Your Knowledge

A boiler makeup line has an automatic chemical feeder, a high hazard backpressure situation under continuous pressure. Which device does Table 382.41-1 permit?

A

Double check backflow prevention assembly

B

Dual check backflow preventer

C

Reduced pressure principle backflow prevention assembly

D

Pressure vacuum breaker assembly

Test Your Knowledge

How high must a pressure vacuum breaker assembly be installed under SPS 382.41 (4) (k)?

A

At least 6 inches above the flood rim and highest downstream point

B

At least 12 inches above the flood rim, highest downstream point and injection ports

C

At least 1 inch above the receptor

D

At least 35 feet above the highest outlet

Test Your Knowledge

A reduced pressure principle assembly is installed indoors. What is the maximum height from the access floor to the lowest point of the assembly?

A

4 feet

B

5 feet

C

6 feet

D

7 feet