10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
Key Takeaways
A multipurpose piping system must be designed and installed under SPS 382.40 and NFPA 13D, with materials acceptable under both NFPA 13D and SPS 384.30.
Fire department connections are prohibited on an MPP system, and a flow test must be performed at the controlling sprinkler before the system is put into operation.
Five gpm is added to the multipurpose calculation for each dwelling connected to a common water supply system.
An MPP system in a one- or 2-family dwelling built of water distribution materials and joints is not a cross connection, and is exempt from the 8 ft/s velocity limit.
NFPA 13D requires a 10-minute water supply for the sprinkler demand (7 minutes for one-story dwellings under 2,000 square feet using stored water), typically designed around two operating sprinklers.
What an MPP system is
A multipurpose piping system is a water distribution system that serves both plumbing fixtures and residential fire sprinklers (SPS 381.01 (156)). Water flows through the sprinkler piping every time a fixture is used, so no stagnant line needs backflow protection, and the occupants notice right away if the water is shut off. NFPA 13D (2019) and the Multi-Purpose Piping Systems Design Manual are both on DSPS's list of permitted exam references.
Code requirements (SPS 382.40 (3) (e))
- Design and install per SPS 382.40 and NFPA 13D; materials must be acceptable under NFPA 13D and SPS 384.30, specifically 384.30 (4) (e) and (5).
- A partial or single sprinkler may be installed in a dwelling unit not required to be sprinklered under NFPA 13D. Limited-purpose or limited-area sprinklers may be installed in areas not required to be sprinklered.
- Fire department connections are prohibited.
- Add 5 gpm to the multipurpose calculation for each dwelling connected to a common water supply system.
- Perform a flow test at the controlling sprinkler before the system is put into operation.
A code note points to the Uniform Dwelling Code (SPS 321.095) and the Commercial Building Code (SPS 362.0903 (10)) for when sprinklers are required.
How MPP fits the rest of the plumbing code
| Topic | Rule |
|---|---|
| Velocity | The 8 ft/s limit does not apply to an MPP system (SPS 382.40 (7) (e)) |
| Cross connection | Not a cross connection in a one- or 2-family dwelling when the sprinkler piping uses water distribution materials and joints (SPS 382.41 (3) (b) 7.) |
| Plan review | MPP systems are on Table 382.20-1 line 12 (department review), but footnote d excludes one- and 2-family dwellings |
| Fixture counts | MPP fire sprinklers are counted as fixtures when deciding whether a project reaches the 16-fixture plan-review threshold |
| Backflow assemblies on fire systems | Need not be registered with DSPS or tagged with a DSPS number |
| Licensing | Master plumbers licensed before January 1, 2002 must complete an approved MPP course before being responsible for an MPP installation (SPS 305.91 (6) (b)); exams after 2001 include MPP questions |
NFPA 13D essentials (2019 edition)
NFPA 13D, Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, is a life-safety standard. It aims to prevent flashover in the room of origin long enough for occupants to escape. It doesn't require sprinklers in every space.
- Water supply duration: the sprinkler demand for 10 minutes. Where stored water is the sole source, 7 minutes of the two-sprinkler demand is allowed for dwellings that are one story and less than 2,000 sq ft.
- Design: typically up to two operating sprinklers in the most demanding compartment, at the listed flow for each sprinkler.
- Multipurpose systems: acceptable when the 13D conditions are met. In common supply connections serving more than one dwelling, 5 gpm is added to the sprinkler demand when sizing common piping. This matches the Wisconsin rule above.
The MPP manual provides the tables and worksheets for sizing an MPP system: listed sprinkler flow and pressure, pipe friction, meter and elevation losses, and available supply pressure. The approach mirrors the empirical method in SPS 382.40 (7) (section 5.2), except that the governing demand is the sprinkler flow plus domestic allowances rather than fixture units alone.
Worked example
A duplex shares one water service. Each unit's controlling sprinkler design needs 26 gpm (two sprinklers at 13 gpm each). Wisconsin and NFPA 13D both add 5 gpm per dwelling connected to the common supply. The common water service must deliver the most demanding unit's 26 gpm plus 2 x 5 = 36 gpm at the required pressure, so the service, meter and any treatment equipment must be checked at 36 gpm.
The installer then:
- Uses piping listed for both potable water and sprinkler service.
- Omits any fire department connection.
- Performs and documents the flow test at the controlling sprinkler before occupancy.
Common MPP inspection problems
- Unlisted fittings or pipe for sprinkler service, or a sprinkler branch built in a material acceptable for water distribution but not listed under NFPA 13D.
- Undersized meters or treatment devices that pass domestic flow but starve the sprinkler demand; the pressure loss must be in the calculation.
- Stagnant sprinkler legs. The appeal of an MPP system is that water moves through it, so dead-end sprinkler piping defeats the purpose.
- A fire department connection added by habit from commercial work; it is prohibited.
- No documented flow test at the controlling sprinkler before occupancy.
Related references
- Combination water services that also feed fire protection: test and disinfect per NFPA 24 (section 5.5).
- Mixing valves and treatment devices on the MPP supply must not starve sprinkler flow, so check their pressure losses in the hydraulic calculation.
- Larger residential and commercial sprinkler systems (NFPA 13 and 13R) are installed by licensed sprinkler contractors under ch. 145 and SPS 305 Subchapter V, not as plumbing MPP systems.
Which feature is prohibited on a multipurpose piping system under SPS 382.40 (3) (e)?
A fire department connection
PEX tubing acceptable under NFPA 13D
A partial sprinkler system
A flow test at the controlling sprinkler
Three dwelling units share a common water supply serving their multipurpose piping systems. How much must be added to the multipurpose calculation for the units?
5 gpm total
10 gpm total
15 gpm total
26 gpm per unit
Under NFPA 13D, what water supply duration is required when stored water is the sole source for a one-story dwelling of less than 2,000 square feet?
10 minutes
30 minutes
7 minutes
60 minutes