9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment

Key Takeaways

  • Table 383.43-1 places soil dispersal components at least 10 feet from buildings, 5 feet from property lines, 15 feet from pools and 50 feet from navigable waters, and treatment or holding tanks at least 5 feet from buildings.

  • NR 812.08 sets well separations of 25 feet to septic and holding tanks and 50 feet to dispersal components under 12,000 gpd (250 feet at 12,000 gpd or more).

  • Inspection, evaluation, maintenance and servicing reports go to the governmental unit within 30 days, and the governmental unit keeps them at least 6 years.

  • Pre-July 2000 POWTS with in situ soil components must be visually inspected for surface ponding at least every 3 years, by a plumber, POWTS inspector, septage operator or POWTS maintainer.

  • Abandoned tanks and pits are disconnected, have their piping sealed, are pumped, and are removed or have their covers removed and are filled with soil, gravel or inert solid material.

Last updated: October 2026

Setbacks (SPS 383.43 (8) (i) and Table 383.43-1)

Physical featureSoil treatment or dispersal componentExterior subsurface treatment tank or holding tankForcemains, service suction and pump discharge lines
Building10 ft5 ft (except RV transfer tanks)None (access permitting)
Property line5 ft2 ft2 ft
Swimming pool15 ftNoneNone
Ordinary high-water mark of navigable waters50 ft10 ft10 ft
Water service and private water main10 ft10 ft5 ft
Public water mainPer NR 811Per NR 811Per NR 811
WellPer NR 811 and 812Per NR 811 and 812Per NR 811 and 812

Road right-of-way lines may be more restrictive than property lines, and WisDOT has its own highway setbacks.

Well separation (NR 812.08, Table A, selected). NR 812 is DNR's well code. It is not on the exam's reference list, but the plumbing code points to it for every well setback:

SourceMinimum distance to a well
POWTS treatment component (septic tank, aerobic unit, filter)25 ft
POWTS holding tank25 ft
POWTS dispersal component under 12,000 gpd50 ft (200 ft for school wells)
POWTS dispersal component 12,000 gpd or more250 ft
Grease interceptor (buried)25 ft
Sanitary building sewer8 ft
Sanitary collector sewer25 ft
Pit privy / vault privy50 ft / 25 ft

Worked check. A mound proposed 45 feet from a private well serving a house (design flow 600 gpd) fails NR 812.08's 50-foot dispersal setback. The septic tank, 30 feet from the well, passes its 25-foot setback. The same mound must also be at least 10 feet from the house and 10 feet from the water service.

The management plan (SPS 383.54 (1))

Every POWTS has a management plan, submitted with plan review. It lists the maintenance needed to keep the system working as designed:

  • Solids removal requirements
  • Influent and effluent quantity and quality
  • Metering and monitoring schedules
  • Load and rest schedules
  • Servicing frequencies
  • Installation and inspection checklists
  • Mechanical component schedules
  • Start-up and shutdown procedures
  • Abandonment procedure

Changing how the system is operated requires a written request to the agency that reviewed the plans. Metering, when required, may use event counters and elapsed-time meters, water meters on the supply, or wastewater meters.

Responsibilities (SPS 383.52 and 383.55)

PartyDuty
OwnerEnsures operation and maintenance per the plan, keeps access covers locked or secured, and is responsible for reporting
Owner with a plan requiring evaluation or maintenance at intervals of 12 months or lessKeeps a contract with a registered POWTS maintainer
Owner with a plan requiring servicing at 12 months or lessKeeps a contract with a certified septage servicing operator (NR 114)
Owner or agentFiles each inspection, evaluation, maintenance or servicing report with the governmental unit within 30 calendar days (POWTS ID, location, date and the license, certification or registration number of the person)
Governmental unitKeeps records at least 6 years; runs an inventory of all POWTS and a maintenance program that tracks reports, notifies delinquent owners and reports annually to DSPS

A POWTS not maintained per its plan, or per SPS 383.54 (4) for older systems, is considered a human health hazard. Chemical or physical restoration products may be used only if department-approved (SPS 383.53).

Older systems (SPS 383.54 (4))

POWTS existing before July 1, 2000 still follow the 1/3 sludge-and-scum and 1-foot-below-inlet servicing triggers. Those with in situ soil components must be visually inspected at least once every 3 years for effluent ponding on the ground surface. The inspection may be done by:

  • a licensed master plumber or master plumber-restricted service
  • a licensed journeyman plumber or journeyman plumber-restricted service
  • a certified POWTS inspector
  • a certified septage servicing operator
  • a registered POWTS maintainer

A county with a completed inventory may extend the interval to 5 years for occasionally occupied structures.

Abandonment (SPS 383.33)

A subsurface tank or pit that is no longer used as a POWTS component must be abandoned by:

  1. Disconnecting all piping to the tanks and pits.
  2. Sealing all disconnected piping.
  3. Pumping and properly disposing of the contents.
  4. Either removing the tanks, or removing the covers and filling the tanks and pits with soil, gravel or an inert solid material.

Municipalities may require connection to an available public sewer under s. 281.45, Stats. That is the usual reason a POWTS is abandoned.

Other ch. SPS 386 and 387 items

Ch. SPS 386, under s. 30.71, Stats., regulates sewage from boats equipped with toilets: holding tanks, overboard discharge inactivation and on-shore disposal facilities. Ch. SPS 387 is the Wisconsin Fund financial assistance program for replacing or rehabilitating failing POWTS. Its printed note says the chapter is repealed effective June 30, 2021 under CR 17-065. Both chapters are in the permitted SPS 381 to 387 binder, but neither is central to journeyman installation questions.

Loading diagram...
POWTS life cycle after installation
Test Your Knowledge

What is the minimum horizontal setback from a soil dispersal component to a building under Table 383.43-1?

A

5 feet

B

10 feet

C

15 feet

D

25 feet

Test Your Knowledge

Within how many days must a POWTS servicing report be submitted to the governmental unit under SPS 383.55 (2)?

A

10 calendar days

B

60 calendar days

C

30 calendar days

D

Within 1 year

Test Your Knowledge

Which step is part of abandoning an unused septic tank under SPS 383.33?

A

Leaving the inlet pipe open so a future system can reuse the tank

B

Filling the tank with clean water and capping the inlet and outlet

C

Covering the existing tank with 12 inches of topsoil and seeding it

D

Pumping it, then removing the tank or removing the cover and filling it with soil, gravel or inert material