3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves

Key Takeaways

  • A return vent rises as high as possible under the fixture enclosure, returns downward and connects with a wye; piping below the floor uses drainage fittings sloped 1/4 inch per foot with cleanouts.

  • A combination drain and vent stack may serve no more than 3 fixtures, each on a separate floor and each 2.0 dfu or less, sized by Table 382.31-5 (0.5 dfu = 1-1/2 in., 1.0 = 2 in., 2.0 = 3 in.).

  • A building drain used as a combination drain and vent may take no more than 2 water closets, and floor drain traps on it must be at least 3 inches.

  • An AAV must sit within 15 degrees of vertical, at least 4 inches above the horizontal pipe served, no more than 20 inches below the flood rim and at least 6 inches above insulation.

  • AAVs are prohibited in health care facilities, licensed restaurant kitchens, residential bedrooms, daycares, sumps, POWTS tanks and FOG treatment devices, among others.

Last updated: October 2026

Return vents for islands and enclosures (SPS 382.31 (12))

A kitchen island sink has no wall to carry a vent up. Wisconsin's answer is the return vent:

  1. Extend an individual vent, vertical wet vent or common vent as high as possible under the fixture enclosure, then return it vertically downward and connect it to the fixture drain or branch drain with a wye-pattern fitting.
  2. Horizontal vent piping connects to the vertical section of the fixture vent and runs to a point where it can rise to a vent terminal or join another vent.
  3. All vent piping below the floor must use drainage fittings and slope at least 1/4 inch per foot to the drainage point, because it can fill with water during a stoppage.
  4. Provide cleanouts on the vent piping under SPS 382.35.

Combination drain and vent systems (SPS 382.31 (17))

A combination drain and vent system uses oversized drain piping to carry both water and air. Wisconsin permits four types.

Stacks

ConditionRule
Fixture countNo more than 3 fixtures, each on a separate floor
Fixture loadEach fixture 2.0 dfu or less; no urinals into the combination portion
OffsetsNone above the lowest fixture drain connection
Fixture drainsWithin Table 382.31-1 developed lengths
Size (Table 382.31-5)Largest fixture 0.5 dfu: 1-1/2 in.; 1.0 dfu: 2 in.; 2.0 dfu: 3 in.

A second stack option serves one kitchen sink above one wall-outlet fixture of 2 dfu or less in a dwelling unit, with no other fixtures. The stack is at least 2 inches below the sink and 4 inches below the lower fixture, or 3 inches for its entire length below the sink. It may not offset above the lower fixture's connection.

Building drains and subdrains

A building drain may serve as a combination drain and vent for floor drains and floor-outlet fixtures if:

  • A vent or drain of at least 2 inches connects upstream of any building drain branch.
  • No more than 2 water closets connect through building drain branches.
  • The building drain between the branch and the upstream vent is one pipe size larger than Table 382.30-3 requires, and at least 3 inches. The vent is at least half that diameter and at least 2 inches.
  • Floor drain and floor-outlet fixture traps (other than water closets) are at least 3 inches.
  • No branch connects within 20 pipe diameters downstream of a stack base fitting.
  • Branch pitch and length meet Table 382.31-1.

Island laboratory sinks and elevator threshold drains

Island laboratory sinks may use a horizontal combination drain one size larger than Table 382.30-2 requires. It needs a 2-inch minimum vent or drain stack upstream, 3-inch fixture drains, individual connections, and a looped vent under each sink with a cleanout. Elevator threshold drain stacks are a minimum of 6 inches with 4-inch traps, no offsets, and a vent at least 3 inches (and half the largest stack diameter) rising from above the highest branch.

Air admittance valves (SPS 382.31 (17m))

An air admittance valve (AAV) opens to admit air on negative pressure and closes by gravity. Wisconsin treats it only as a termination point. Amendments to (17m) took effect September 1, 2026 under CR 26-019.

Where an AAV may serve. It may terminate a branch vent, circuit vent, common vent, individual vent, wet vent or combination drain and vent system. It may serve a pumped-discharge clothes washer standpipe only when the fixture drain downstream of the vent point is at least 3 inches. A branch with AAV-vented fixtures that connects to a stack with 4 or more branch intervals above it needs a relief vent between the most downstream fixture and the stack.

Where an AAV may not be the vent termination (selected items from the 18-item list):

  • Negative-pressure areas, laboratories and commercial parking structures
  • Vents that relieve positive pressure, and stack vents serving 2 or more branch intervals
  • Vent stacks required by SPS 382.31 (4) (a), and vents serving sumps
  • Chemical waste fixtures, POWTS holding or treatment tanks, and FOG treatment devices
  • Supply or return air plenums, enclosed stairwells, and pits or vaults below grade
  • Clean rooms, health care facilities, licensed restaurant kitchens, residential bedrooms and daycares

Sizing. Table 382.31-6 limits the developed length from the fixture to the AAV:

Max dfu1-1/4 in.1-1/2 in.2 in.
135 ftno limitno limit
328 ft140 ftno limit
6NP100 ft200 ft
20NP60 ft (no more than 2 water closets)110 ft
160NPNP25 ft

Installation. The AAV must be:

  1. Vertical, within plus or minus 15 degrees of plumb.
  2. At least 4 inches above the top of the horizontal pipe it serves.
  3. No more than 20 inches below the flood rim of any fixture it serves.
  4. At least 6 inches above insulation.
  5. Accessible, in a space that admits air.
  6. Backed by at least one 3-inch or larger vent on the same building drain that extends outdoors.

The vent system an AAV serves may offset horizontally less than 36 inches above the floor if it doesn't connect to another vent.

Testing and documentation. Test the AAV before or after installation at 1 inch of water column. If the pressure falls 0.5 inch or less in 1 minute, it passes. The contractor must give the owner a copy of the manufacturer's written AAV description.

Loading diagram...
Is an AAV allowed here?
Test Your Knowledge

Which location is on the SPS 382.31 (17m) list of places where an air admittance valve may NOT be the vent termination?

A

A residential bathroom vanity

B

A residential bedroom

C

A kitchen island in a single-family home

D

A laundry room with a gravity clothes washer

Test Your Knowledge

How is a newly installed air admittance valve field-tested under SPS 382.31 (17m) (f)?

A

At 5 psi of air for 15 minutes, with no drop allowed on the gauge

B

At 10 inches of mercury for 5 minutes before the valve is installed

C

By a smoke test at roof level after all fixtures are set and trapped

D

At 1 inch of water column, passing if it drops 0.5 inch or less in 1 minute

Test Your Knowledge

A drain stack will serve as a combination drain and vent for three lavatories on three separate floors. What stack size does Table 382.31-5 require?

A

2 inches

B

1-1/2 inches

C

3 inches

D

4 inches