11.1 Health Care & Related Facilities (SPS 382.50)

Key Takeaways

  • Health care hot water is initiated and stored at 140 degrees F or more, and outlets accessible to patients may not exceed 115 degrees F; limit stops may not be used to achieve that limit.

  • Patient showers, therapeutic equipment and baths use pressure-balanced and thermostatic valves holding 110 to 115 degrees F, cutting flow to 0.5 gpm or less above 115 degrees F or on cold water loss.

  • Hospitals need at least 2 water services, connected to different mains where available, each able to serve the full building demand.

  • Hot water systems are under constant recirculation and disinfected by storage at 140 degrees F with a 124 degrees F return, chlorine (0.5 mg/L), chloramine, chlorine dioxide or another approved method.

  • Floor drains are prohibited in operating and delivery rooms; cystoscopic room drains need a non-splash flushing bowl.

Last updated: October 2026

Why health care is different

Patients are vulnerable to scalding, waterborne pathogens such as Legionella, and cross-contamination. SPS 382.50 adds requirements on top of the general code for "health care and related facilities." Health care plumbing is reviewed only by the department. Table 382.20-1 line 1 sends all new work, additions and alterations in hospitals, nursing homes, ambulatory surgery centers, renal dialysis centers, CBRFs and inpatient hospices to DSPS regardless of fixture count. Line 5 adds the testable backflow assemblies serving these facilities.

Fixtures and equipment (SPS 382.50 (2))

ItemRequirement
Ice machines and storageLocated where not subject to contamination
Sterilizers and washer-sanitizersIndirect waste discharging through an air gap
Water aspiratorsApproved cross connection control
Spouts at lavatories and sinks accessible to patientsFixed spout discharging at least 5 inches above the flood level rim; laminar flow where required
Actions for staff, patients, residents and food handlersHands-free; wrist blades no longer than 4-1/2 inches, except scrub and clinical sinks at least 6 inches; single-lever handles allowed
Self-closing lavatory faucets accessible to patientsHot water flow calculated to purge the piping back to the recirculated supply
Floor drainsProhibited in operating and delivery rooms; allowed in cystoscopic rooms with a non-splash, horizontal-flow flushing bowl

Table 382.50-1 assigns spout and action types room by room (nursing, nursery, surgical and other departments). Psychiatric-care areas where gooseneck spouts endanger patients are exempt from the spout rules.

Water supply (SPS 382.50 (3))

Hospitals must have at least 2 water services, connected to different water mains where more than one is available. Each must be able to supply the total building demand (non-essential additions excepted). A code note warns that two services or a private main may require a check valve under NR 811.

All health care facilities must provide hot and cold water to patient-accessible sinks:

  • Hot water initiated and stored at 140 degrees F minimum.
  • Maximum temperature at patient-accessible outlets 115 degrees F.

Hospitals, CBRFs, inpatient hospices and nursing homes must also meet these requirements:

RequirementDetail
ValvingOne control valve may serve up to 4 patient care units with no more than 2 persons each; intensive care units are individually valved
InsulationAll distribution piping insulated per chs. SPS 361 to 366
Cold waterSupplied to lavatories and sinks in patient rooms
RecirculationConstant recirculation to every hot outlet; with thermal disinfection, uncirculated branches no longer than 3 feet
Temperature controlAutomatic valves regulate any supply over 140 degrees F to patient-accessible fixtures
Showers, therapy equipment, bathsPressure-balanced and thermostatic valves holding 110 to 115 degrees F, reducing flow to 0.5 gpm or less if the outlet exceeds 115 degrees F or cold pressure is lost
Limit stopsProhibited as the way to meet the 115 degrees F maximum
Absolute maximumNo outlet over 180 degrees F; patient-accessible outlets 115 degrees F maximum
Laminar flowAt outlets accessible to patients
Heat recoveryNot allowed on hot water distribution systems
Expansion tanksFlow-through type with a check valve upstream; any bypass valve closed and locked

Disinfection methods (one is required):

  1. Thermal: storage and circulation initiated at 140 degrees F or more with a return of at least 124 degrees F.
  2. 0.5 mg/L residual chlorine.
  3. Chloramine.
  4. Chlorine dioxide.
  5. Another department-approved method, or municipal disinfectant with an approved residual and site approval.

Hot water piping is labeled with the disinfection method:

  • At the injection point.
  • Within 5 feet of it.
  • Every 25 feet within the mechanical room.
  • On the inside of each mechanical room door.

Lettering is at least 1/2 inch high.

Water management plans are required in facilities with more than 250 occupants. They cover:

  • Emergency water contingencies
  • Pathogen control
  • Routine and emergency disinfection
  • The person responsible for water quality
  • Periodic flushing
  • The hot water balancing valve report

Adult day care centers are also limited to 115 degrees F at participant-accessible outlets.

Related provisions elsewhere

  • Dialysis: a dialysis machine's indirect waste may discharge to a water closet or lavatory in a single-occupancy patient toilet room through a 1-inch air gap (SPS 382.33 (8) (d) 9.). A dialysis box in a patient room must be lockable, with its receptor sealed when not in use. A hose outlet for a portable dialysis machine in a lockable box is not a cross connection.
  • Sterilizer rooms: a room containing recessed or concealed sterilizer parts needs a floor drain serving the whole floor (SPS 382.30 (11) (b) 3. b.).
  • Air admittance valves may not be used in health care facilities (SPS 382.31 (17m)).
  • Health care appliances must meet the drain, vent, supply and backflow rules of SPS 382 (SPS 384.15).

Worked example

A nursing home renovation adds 10 patient rooms (2 beds each) and a therapy tub room.

  • Plans go to DSPS, not an agent municipality.
  • Valving: no more than 4 rooms per control valve.
  • The therapy tub gets a combination pressure-balanced and thermostatic valve set for 110 to 115 degrees F with high-temperature flow cutback.
  • The loop is designed for thermal disinfection at 140 degrees F with a 124 degrees F return, so uncirculated branches stay at 3 feet or less.
  • Every patient sink spout discharges at least 5 inches above the rim.
  • Handles are wrist blades of 4-1/2 inches or less.
Loading diagram...
Health care hot water design
Test Your Knowledge

What maximum water temperature may reach fixture fitting outlets accessible to patients in a Wisconsin health care facility?

A

110 degrees F

B

120 degrees F

C

115 degrees F

D

125 degrees F

Test Your Knowledge

How many water services must a hospital have under SPS 382.50 (3) (a)?

A

At least 2, on different mains where more than one is available

B

One water service with a full-size bypass around the meter

C

One water service for each building wing or addition

D

At least 3, each sized for half of the total building demand