3.2 Temperature and Pressure Relief Valves & Discharge Piping (UPC 504.6, 608; WA 608.3.1 and 608.5)
Key Takeaways
A system with storage water heating needs a listed combination T&P relief valve; listed nonstorage instantaneous heaters with an inside diameter of 3 inches or less are exempt (WA 608.3.1).
Pressure relief valves are set at not more than 150 psi, with no shutoff valve between the relief valve and the system (UPC 608.4).
The relief device's Btu/h or steam relief rating must be at least the water heater's input rating (UPC 504.6).
Washington's 608.5 requires T&P discharge piping equal to the valve outlet size, with no valves, and terminating 6 to 24 inches above the ground pointing down.
Relief valve discharge into a water heater pan is prohibited, and the terminal end of the discharge pipe may not be threaded (WA 608.5).
What the T&P Valve Protects Against
A storage water heater is a closed pressure vessel. If the thermostat and high-limit control both fail, water keeps heating past 212°F without boiling, because it is under pressure. At 50 psi, water stays liquid to about 298°F. At 150 psi it stays liquid to about 366°F. If the tank then ruptures, the superheated water flashes to steam and expands about 1,600 times in volume. A properly sized, properly piped T&P relief valve prevents that event by discharging water before the tank reaches those conditions.
When a T&P Valve Is Required
| Section | Rule |
|---|---|
| 608.3.1 (Washington amendment) | A water system containing storage water heating equipment needs an approved, listed, adequately sized combination temperature and pressure relief valve. Exception: a listed nonstorage instantaneous heater with an inside diameter not more than 3 inches. |
| 608.3.1 location | The valve goes on the heater in the location its listing and the manufacturer's instructions require, and it gets a drain per 608.5. |
| 505.2 (Washington) | Non-gas storage heaters need an over-temperature safety device and a combination T&P valve |
| 608.6 | A water-heating device connected to a separate storage tank, with valves between heater and tank, needs its own pressure relief valve |
| 608.7 | A hot water storage tank or indirect water heater located above the fixture outlets it serves needs a vacuum relief valve (CSA Z21.22) |
Ratings and Settings
- Pressure (608.4): Each pressure relief valve is an approved automatic type with a drain, set at not more than 150 psi. No shutoff valve may be installed between the relief valve and the system.
- Capacity (504.6): The relief valve's hourly Btu discharge capacity or rated steam relief capacity must be not less than the input rating of the heater. A 199,000 Btu/h commercial heater needs a valve rated for at least 199,000 Btu/h.
- Temperature: Standard residential T&P valves (ANSI Z21.22/CSA 4.4) open on temperature at about 210°F. The temperature-sensing element must sit in the hottest water near the top of the tank, in the heater's designated tapping. Never extend the valve out on a nipple or tee that holds the probe away from the tank water.
- No shutoffs anywhere in the relief path (504.6): Do not install a valve between the relief valve and the heater, or on the discharge pipe between the valve and atmosphere.
Discharge Piping: Washington 608.5
Washington's amended 608.5 reads as a checklist. The discharge piping serving a temperature relief valve, pressure relief valve, or combination valve must have no valves, obstructions, or means of isolation, and must be:
- Full size: equal to the size of the valve outlet, discharging full size to the flood level of the receiving area, pointing down.
- Rated material: rated for at least the operating temperature of the system and approved for the use.
- Gravity discharge: discharging independently by gravity through an air gap into the drainage system, or outside the building with the end of the pipe not more than 2 feet and not less than 6 inches above the ground, pointing downward.
- Safe: discharging so as not to cause personal injury or structural damage.
- Not trapped: no part may be trapped or subject to freezing.
- Unthreaded: the terminal end may not be threaded, so the outlet cannot be capped.
- Not into the pan: discharge from a relief valve into a water heater pan is prohibited.
Washington exception: Where no drainage was provided, replacement water heating equipment only needs a drain pointing down from the relief valve and ending between 2 feet and 6 inches from the floor. No additional floor drain is required.
| Discharge detail | Compliant | Violation |
|---|---|---|
| Size | 3/4-inch pipe from a 3/4-inch outlet | Reducing to 1/2-inch tubing |
| Path | Continuous fall by gravity | Uphill run, sag, or trap |
| End | Plain, unthreaded, 6 to 24 inches above grade or floor, pointing down | Threaded end, hose adapter, or cap |
| Isolation | None | Ball valve, check valve, or tee with a plug |
| Termination | Through an air gap to an approved receptor, or outdoors | Into the water heater drain pan |
Why 6 to 24 inches? Below 6 inches the outlet can be blocked by snow, water, or debris. Above 24 inches the discharge splashes and can scald someone standing nearby.
Related Pan Rule
A drain pan under a heater in an attic or over a floor-ceiling assembly (Section 3.3) catches leaks from the tank. It is not a receptor for relief valve discharge. A T&P line that ends over the pan violates item 7, even if the pan has a drain.
Exam trap: "Relief valves may be tested by installing a ball valve in the discharge so the line can be isolated." Any valve or means of isolation in the discharge piping is prohibited.
Which T&P discharge installation violates Washington's 608.5?
A discharge pipe that falls continuously by gravity to an air gap above a floor drain
A discharge pipe with an unthreaded, plain end
3/4-inch hard copper from a 3/4-inch valve outlet, ending 12 inches above an exterior grade and pointing down
A discharge pipe that ends over the water heater's drain pan
A commercial water heater has an input of 250,000 Btu/h. What must be true of its T&P relief valve under UPC 504.6?
The valve may be rated for 150,000 Btu/h if the discharge pipe is upsized
The relief capacity must equal 150% of input
Any listed residential valve is acceptable
The valve's relief capacity must be at least 250,000 Btu/h
A hot water storage tank is installed in an attic above the fixtures it serves. Which additional device does UPC 608.7 require?
A vacuum relief valve complying with CSA Z21.22 on the tank or heater
A pressure-reducing valve on the hot outlet
An atmospheric vacuum breaker on the discharge line
A second T&P valve on the cold inlet