6.2 Drainage Fixture Units, Trap Sizes, & Flow Conversions (UPC Table 702.1, 702.2, 702.3)

Key Takeaways

  • In UPC Table 702.1, a 1.6 gpf water closet has a 3-inch minimum trap and carries 3 DFU private, 4 DFU public, and 6 DFU assembly.

  • A lavatory has a 1-1/4-inch minimum trap and 1.0 DFU; a bathtub or bath/shower has a 1-1/2-inch trap and 2.0 DFU; a single-head shower has a 2-inch trap and 2.0 DFU.

  • UPC Table 702.2(1) limits trap and trap arm loads to 1, 3, 4, 6, and 8 DFU for 1-1/4, 1-1/2, 2, 3, and 4-inch sizes.

  • Continuous flow from pumps, ejectors, or air-conditioning equipment counts 2 DFU per gallon per minute (UPC 702.3).

  • A battery of three or more clothes washers is rated at 6 DFU each when sizing common horizontal and vertical piping (Table 702.1 note 5).

Last updated: September 2026

What a Drainage Fixture Unit Represents

A drainage fixture unit (DFU) measures a fixture's probable load on the drainage system, based on its discharge rate, volume, and frequency of use. Section 702.1 says the unit values in Table 702.1 are based on the size of the trap required. Fixtures not listed are rated by their trap or trap arm size. You add DFUs along the direction of flow, then size each pipe from Table 703.2 (Section 6.3).

Occupancy columns: Private covers dwellings and private rooms, public covers general commercial use, and assembly covers public-use assembly occupancies. Public and assembly values are higher because those fixtures are used more often. Part 2 drawings state which column to use. When the drawing does not say, a single-family house is private.

Selected Rows of Table 702.1

FixtureMin. trap and trap armPrivatePublicAssembly
Bathtub or combination bath/shower1-1/2 in2.02.0—
Bidet1-1/4 in1.0——
Clothes washer, domestic, standpipe2 in3.03.03.0
Dishwasher, domestic, independent drain1-1/2 in2.02.02.0
Drinking fountain or water cooler1-1/4 in0.50.51.0
Floor drain2 in2.02.02.0
Floor drain, emergency2 in—0.00.0
Shower, single-head trap2 in2.02.02.0
Shower, each additional head2 in1.01.01.0
Lavatory1-1/4 in1.01.01.0
Lavatories in sets1-1/2 in2.02.02.0
Sink, kitchen, domestic (with or without disposer or dishwasher)1-1/2 in2.02.0—
Sink, laundry1-1/2 in2.02.02.0
Sink, bar (private)1-1/2 in1.0——
Sink, commercial with food waste1-1/2 in—3.03.0
Sink, clinical3 in—6.06.0
Service or mop basin2 in—3.03.0
Service sink, flushing rim3 in—6.06.0
Urinal, integral trap, 1.0 gpf2 in2.02.05.0
Urinal, exposed trap1-1/2 in2.02.05.0
Water closet, 1.6 gpf (gravity tank, flushometer tank, or flushometer valve)3 in3.04.06.0
Water closet, over 1.6 gpf3 in4.06.08.0
Mobile home trap3 in12.0——

Table notes worth memorizing

  1. Indirect waste receptors are sized by the total drainage capacity of the fixtures that drain into them, using Table 702.2(2).
  2. Some fixtures (kitchen and laundry sinks, dishwashers, bar and special-purpose sinks, urinals) require a 2-inch minimum drain.
  3. A battery of three or more clothes washers is rated at 6 DFU each when sizing common horizontal and vertical drainage piping.
  4. Water closets count as 6 DFU when sizing septic tanks under Appendix H.
  5. Trap sizes may not be increased to the point that the fixture discharge can no longer scour the trap.

Maximum Load on a Trap (Table 702.2(1))

Trap and trap arm sizeMaximum DFU
1-1/4 in1
1-1/2 in3
2 in4
3 in6
4 in8

The table does not apply to self-service laundries. It lets you rate an unlisted fixture from its trap size and check that a trap is not overloaded.

Converting Flow to DFU

Intermittent flow, Table 702.2(2), applies to devices that discharge occasionally at a known rate:

Discharge rateDFU
Up to 7-1/2 gpm1
Over 7-1/2 to 15 gpm2
Over 15 to 30 gpm4
Over 30 to 50 gpm6

Rates over 50 gpm are set by the AHJ.

Continuous flow (702.3): A pump, sump ejector, air-conditioning unit, or similar device discharging continuously counts 2 DFU per gpm. A 12 gpm continuous discharge therefore adds 24 DFU. Section 710.5 applies the same 2 DFU per gpm to building drains that receive pump or ejector discharge.

Worked Example: Totaling a Bathroom Group

A private bathroom has a 1.6 gpf water closet (3.0), a lavatory (1.0), and a bathtub/shower (2.0). Total: 6.0 DFU.

  • The same group in a public restroom (water closet, lavatory, and a public shower instead of a tub): 4.0 + 1.0 + 2.0 = 7.0 DFU.
  • A single-family house with two such private bathrooms, a kitchen sink (2.0), a dishwasher (2.0), a clothes washer (3.0), and a laundry sink (2.0): 6.0 + 6.0 + 2.0 + 2.0 + 3.0 + 2.0 = 21 DFU on the building drain.

Common Exam Traps

  • Lavatory trap 1-1/4 in, but shower trap 2 in. A shower is not a 1-1/2-inch fixture in the UPC.
  • Water closet DFU depends on the column. Private 3, public 4, assembly 6.
  • Kitchen sink with disposer and dishwasher on the same trap is still 2.0 DFU private. The row reads "with or without food waste disposer, dishwasher, or both." A dishwasher with its own independent drain adds 2.0.
  • Clothes washer standpipe trap is 2 inches. Standpipe height rules are in Chapter 8 (Section 7.3).
Test Your Knowledge

A public restroom has two 1.6 gpf water closets, two lavatories, and one integral-trap 1.0 gpf urinal. Using UPC Table 702.1 public values, what is the total DFU?

A

11.0

B

10.0

C

12.0

D

16.0

Test Your Knowledge

A condensate pump discharges continuously at 6 gallons per minute into a building drain. How many drainage fixture units does it add under UPC 702.3?

A

12

B

4

C

6

D

3