6.3 Sizing Drainage Piping with Table 703.2 (Vertical, Horizontal, Water Closet Limits, & WA Note 4)
Key Takeaways
UPC Table 703.2 allows 3-inch drainage pipe to carry 48 DFU vertically and 35 DFU horizontally, and 4-inch pipe to carry 256 DFU vertically and 216 DFU horizontally.
No water closet may discharge into 2-inch drainage pipe (Table 703.2 note 3).
A 3-inch vertical drain may serve no more than four water closets, and a 3-inch horizontal drain no more than three (Table 703.2 note 4).
Washington's exception to note 4 allows four 1.6 gpf water closets on a 3-inch horizontal drain in a single-family addition or alteration when 4-inch is not readily available and the AHJ approves.
Horizontal Table 703.2 values assume 1/4 inch per foot; at 1/8 inch per foot, multiply the horizontal fixture units by 0.8 (Table 703.2 note 5).
The Table You Must Memorize
L&I states that Tables 702.1, 610.3, 610.4, and 610.10 are provided on the journey level exam, and Table 703.2 is not. Part 2 asks you to provide fixture units and pipe sizes for a waste and vent drawing using minimum sizing, so you need this table in your head.
UPC Table 703.2: Maximum Unit Loading and Maximum Length of Drainage and Vent Piping
| Pipe size (in) | 1-1/4 | 1-1/2 | 2 | 3 | 4 | 5 | 6 | 8 |
|---|---|---|---|---|---|---|---|---|
| Drainage, vertical (max DFU) | 1 | 2 | 16 | 48 | 256 | 600 | 1,380 | 3,600 |
| Drainage, horizontal (max DFU) | 1 | 1 | 8 | 35 | 216 | 428 | 720 | 2,640 |
| Drainage, vertical max length (ft) | 45 | 65 | 85 | 212 | 300 | 390 | 510 | 750 |
| Vent, max DFU (horizontal and vertical) | 1 | 8 | 24 | 84 | 256 | 600 | 1,380 | 3,600 |
| Vent, max length (ft) | 45 | 60 | 120 | 212 | 300 | 390 | 510 | 750 |
For 10-inch pipe, drainage is 5,600 vertical and 4,680 horizontal. For 12-inch, it is 8,400 vertical and 8,200 horizontal. Horizontal drainage length is unlimited.
The notes (where most exam questions come from)
- Unit loadings exclude the trap arm; trap arms are sized from Table 702.1 and Table 1002.2.
- 1-1/2-inch vertical (2 DFU): except sinks, urinals, and dishwashers, which may not exceed 1 fixture unit on this size.
- 2-inch pipe (16 vertical, 8 horizontal): except six-unit traps or water closets. No water closet may drain into 2-inch pipe.
- 3-inch pipe: only four water closets or six-unit traps on a vertical pipe or stack, and not more than three on a horizontal branch or drain.
- Washington exception: In a single-family dwelling addition or alteration where a 4-inch horizontal waste is not readily available, four water closets not exceeding 1.6 gpf each may be allowed on a 3-inch horizontal waste when approved by the AHJ.
- Horizontal values are based on 1/4 inch per foot slope. At 1/8 inch per foot, multiply horizontal fixture units by 0.8.
- Vent notes (used in Chapter 8): an individual vent is at least 1-1/4 inches and at least one-half the diameter of the drain it serves. No more than one-third of a vent's permitted length may be horizontal. Increasing a vent one pipe size for its entire length removes the length limits.
How to Size a Drain
- Total the DFU entering each section of pipe, working downstream from the most remote fixture (Table 702.1).
- Decide whether the section is vertical or horizontal. Horizontal limits are lower because the pipe runs partly full.
- Pick the smallest size whose limit is equal to or greater than the load.
- Apply the notes: check water closet counts (notes 3 and 4) and slope (note 5).
- Check the trap and trap arm minimums from Table 702.1. A pipe can never be smaller than the trap it serves.
- Do not reduce size in the direction of flow. A smaller pipe downstream retards the flow, which 310.5 prohibits, so a drain should never be smaller than any drain upstream of it.
Worked Examples
Example 1: Single-family house. Two private bathrooms (3 + 1 + 2 each), a kitchen sink (2), a dishwasher (2), a clothes washer (3), and a laundry sink (2) total 21 DFU, with 2 water closets.
- Building drain (horizontal): 3 inches allows 35 DFU and up to 3 water closets. 3 inches works.
- If the design grows to 4 water closets, note 4 forces a 4-inch horizontal drain. In Washington, the exception permits 3 inches only in a single-family addition or alteration, with 1.6 gpf closets, when 4-inch is not readily available and the AHJ approves.
Example 2: Commercial restroom branch. Public values: 6 water closets (6 × 4 = 24), 4 lavatories (4), 3 integral urinals (6), and 1 floor drain (2) total 36 DFU.
- DFU alone: 3-inch horizontal allows only 35, so 36 already needs 4 inches.
- Water closet count: 6 closets on a horizontal branch exceeds note 4's limit of three. 4 inches either way.
Example 3: Reduced slope. A 4-inch horizontal drain installed at 1/8 inch per foot (permitted for 4-inch and larger by 708.1 when the AHJ approves) carries at most 216 × 0.8 = 172.8, so 172 DFU.
Example 4: Stack. A three-story stack carrying 3 floors of private bathrooms (3 × 6 = 18 DFU, 3 water closets): 3-inch vertical allows 48 DFU and 4 water closets, and the stack height must stay within 212 feet. 3 inches works.
Vertical Length Limits
The "maximum length" rows limit how tall a vertical drain or vent of that size may be. A 2-inch vertical drain may be no taller than 85 feet, and a 2-inch vent no longer than 120 feet of developed length. Part 2 drawings rarely approach these limits, but Part 1 may ask for the number directly.
Memory Aids
- "16-8, 48-35, 256-216" gives vertical and horizontal DFU for 2, 3, and 4-inch pipe.
- "Two-inch: no toilets. Three-inch: 4 up, 3 across."
- Vent DFU row: "1-8-24-84-256" for 1-1/4 through 4-inch. It matches the drainage vertical row from 4 inches up.
A horizontal building drain in a new commercial building carries 30 DFU, including four 1.6 gpf water closets. What is the minimum size under UPC Table 703.2?
3 inches
4 inches
5 inches
2 inches
What is the maximum DFU load for a 4-inch horizontal drain installed at 1/8 inch per foot slope under Table 703.2 note 5?
256
172
108
216
A 2-inch horizontal branch serves two lavatories and a bathtub. A plumber wants to connect a 1.6 gpf water closet to the same branch. What does Table 703.2 require?
The closet may connect because the total is under 8 DFU
The branch must be at least 3 inches, because water closets may not drain into 2-inch pipe
The branch must be 2-1/2 inches
The closet may connect if the branch is vertical