10.3 Key UPC Definitions and Referenced Standards (UPC Chapters 2 and 17; WA Definition Amendments)

Key Takeaways

  • The UPC defines a trap arm as the portion of a fixture drain between the trap and the vent, and the trap seal as the vertical distance between the crown weir and the top dip of the trap.

  • Developed length is measured along the centerline of the pipe and fittings (UPC Chapter 2).

  • A stack vent is the extension of a soil or waste stack above its highest horizontal drain; a vent stack is a separate vertical vent that circulates air to and from the drainage system.

  • Washington defines hot water as water at 100°F or more and includes water heaters and medical gas systems within the property lines in the plumbing system definition (WA 210.0, 218.0).

  • Standards in UPC Table 1701.1 are mandatory where required by code sections; for example ASSE 1013 covers RP assemblies and ASSE 1016 covers shower and tub-shower valves.

Last updated: September 2026

Why Definitions Matter

Code language is precise. "Building drain" and "building sewer" are different pipes. That difference matters in Washington, where building sewer rules are deleted (Section 6.4). Likewise, a "vent stack" and a "stack vent" are different pipes. Many Part 1 questions are answered by knowing the definition.

Drainage and Vent Definitions (UPC Chapter 2)

TermDefinition in brief
Building drainThe lowest drainage piping inside the building walls, carrying discharge to the building sewer, which begins 2 feet outside the wall
Building sewerHorizontal piping from the end of the building drain to a public or private sewer or other point of disposal
Drainage systemAll piping within public or private premises conveying sewage, storm water, or liquid wastes to a legal point of disposal; not the public sewer or treatment plant
Fixture drainThe drain from a fixture's trap to its junction with any other drain
Trap armThe portion of a fixture drain between the trap and the vent
TrapA fitting or device that provides a liquid seal against the back passage of air, without materially affecting flow
Trap sealThe vertical distance between the crown weir and the top dip of the trap
Crown weir (trap weir)The lowest point in the cross-section of the horizontal waterway at the exit of the trap
Horizontal branchA drain extending laterally from a stack or building drain, receiving one or more fixture drains
StackThe vertical main of soil, waste, or vent piping extending through one or more stories
Soil pipeConveys water closet, urinal, clinical sink, or similar discharge
Waste pipeConveys only liquid waste, free of fecal matter
Branch intervalA length of stack corresponding generally to a story height, but not less than 8 feet, within which one floor's branches connect
Developed lengthLength measured along the centerline of pipe and fittings
GradeThe slope or fall of a pipe, usually expressed as a fraction of an inch or a percentage per foot
OffsetA combination of elbows or bends that moves one pipe section out of line but parallel to the other
Stack ventThe extension of a soil or waste stack above the highest horizontal drain connected to it
Vent stackA vertical vent pipe installed primarily to circulate air to and from any part of the drainage system
Continuous ventA vertical vent that continues the drain it connects to
Individual ventVents one fixture trap, connecting above the fixture or terminating outdoors
Relief ventMainly provides air circulation between drainage and vent systems, or acts as an auxiliary vent
Yoke ventConnects upward from a soil or waste stack to a vent stack to prevent pressure changes in the stacks
Wet ventA vent that also serves as a drain
Dry ventA vent that carries no sewage or waste
Combination waste and vent systemWaste piping that horizontally wet vents sinks or floor drains through an oversized common waste and vent pipe

Water and Backflow Definitions

TermDefinition in brief
Building supplyPipe carrying potable water from the meter or source to the building or point of use on the lot
Fixture branchWater pipe between the fixture supply pipe and the water distribution pipe
Fixture supplyWater pipe connecting the fixture with the fixture branch
Air gap, water distributionUnobstructed vertical distance through free atmosphere from the lowest potable outlet to the flood-level rim
Air gap, drainageSame concept for a pipe or fixture conveying waste, measured to the receptor's flood-level rim
Air breakA physical separation, which may be a low inlet into the indirect waste receptor
Flood-level rimThe top edge of a receptor from which water overflows
Critical levelThe marked point on a backflow device that sets its minimum height above the flood-level rim. With no marking, the bottom of the device
Roof washerA device diverting initial rainfall away from a cistern, also called a first-flush device

Washington Definition Amendments (WAC 51-56-0200)

  • 205.0 Certified backflow assembly tester: certified by the Department of Health under chapter 246-292 WAC to inspect, test, maintain, and repair assemblies, devices, and air gaps (maintenance and repair in compliance with chapter 18.106 RCW).
  • 210.0 Hot water: water at 100°F or more. The unamended UPC uses 120°F.
  • 211.0 Insanitary (2015 amendment): includes a trap that does not keep its seal, an opening without a trap, a fixture without enough water to stay clean, a defective fixture or pipe, an unvented trap, and any cross-connection that could let foreign matter into domestic water.
  • 218.0 Plumbing system: includes potable water, building supply and distribution pipes, alternate and rainwater systems, fixtures and traps, drainage and vent piping, and building drains within the property lines, plus potable water treating equipment, medical gas and medical vacuum systems, and water heaters. No certification is required for installing a plumbing system within the property lines and outside a building.
  • 225.0 Water/wastewater utility: a public or private entity, including a water purveyor as defined in chapter 246-290 WAC, that treats or delivers reclaimed or potable water.

Referenced Standards (UPC Chapter 17)

Section 1701.1: the standards in Table 1701.1 are for design, testing, and installation of materials and devices, and are mandatory where required by code sections. Standard numbers you should recognize:

StandardSubject
ASSE 1001Atmospheric vacuum breakers
ASSE 1002Antisiphon fill valves (ballcocks)
ASSE 1010Water hammer arresters (also PDI-WH 201)
ASSE 1011Hose connection vacuum breakers
ASSE 1013Reduced pressure principle assemblies
ASSE 1015Double check valve assemblies
ASSE 1016Shower and tub-shower control valves
ASSE 1018 and 1044Trap seal primers
ASSE 1020 and 1056Pressure and spill-resistant vacuum breakers
ASSE 1037Flushometers
ASSE 1047 and 1048RP and DC detector fire assemblies
ASSE 1060Outdoor enclosures for backflow assemblies
ASSE 1061Push-fit fittings
ASSE 1069Gang shower mixing valves
ASSE 1070Temperature-limiting devices
ASSE 1079Dielectric unions
ASME A112.1.2Air gaps
ASME A112.18.1 / CSA B125.1Faucets and fixture fittings
ASME A112.19.2 / CSA B45.1Ceramic fixtures
ASTM B88Copper water tube
ASTM B813 and B828Soldering flux and soldering practice
ASTM C564Gaskets for cast-iron soil pipe
CISPI 301 and 310Hubless cast-iron pipe and couplings
NSF 14Plastic piping components
NSF 61Drinking water system components
NSF 350On-site treated nonpotable water systems
Test Your Knowledge

What is the portion of a fixture drain between the trap and the vent called in the UPC?

A

Continuous waste

B

Horizontal branch

C

Fixture branch

D

Trap arm

Test Your Knowledge

What is the difference between a stack vent and a vent stack?

A

A stack vent is horizontal and a vent stack is vertical

B

A vent stack may carry waste; a stack vent may not

C

They are two names for the same pipe

D

A stack vent is the extension of a soil or waste stack above its highest horizontal drain; a vent stack is a separate vertical vent pipe that provides air circulation to and from the drainage system