12.1 Part 3 Explained: Reading the Water Sizing Drawing and Gathering the 610.7 Data
Key Takeaways
Part 3 of the Washington journey level exam has 25 items in 90 minutes, requires 70 percent, and is closed book (PSI candidate bulletin).
L&I states Part 3 asks for fixture units and pipe sizes for hot and cold distribution, using minimum sizing allowed by the UPC.
UPC 610.7 requires four inputs for Table 610.4 sizing: total fixture units, developed length from the meter to the most remote outlet, elevation difference to the highest outlet, and the minimum street pressure.
Where street pressure fluctuates during the day, the system is designed on the minimum pressure available (UPC 610.7).
No building supply pipe may be smaller than 3/4 inch (UPC 610.8).
What L&I and PSI Say About Part 3
| Fact | Source |
|---|---|
| 25 items, 90 minutes, 70%, closed book | PSI Washington Plumbing Candidate Information Bulletin |
| "A water pipe sizing exercise taken from Chapter 6 of the UPC and amendments" | L&I |
| "A drawing of a building … showing elevated views of plumbing fixtures along with the illustrated piping for the hot and cold-water distribution system" | L&I |
| "You will provide the fixture units and pipe sizes. Use minimum sizing as allowed by the UPC" | L&I |
| Tables 610.3, 610.4, and 610.10 are provided (with 702.1 for Part 2) | L&I |
Washington's 610.4 amendment keeps the choice of sizing from Table 610.4 or by Appendix A (610.5). The exam exercise uses Table 610.4, the table L&I provides.
What the Drawing Shows
- Meter and street service, the building supply entering the building, the water heater, and the cold and hot mains and branches to each fixture.
- Line types: typically cold water in one line style and hot in another. Check the legend.
- Segment labels (letters or numbers) at each branch point. Questions ask for fixture units or minimum size at a named segment.
- Notes giving the street pressure, the elevation of the highest fixture above the meter, the developed length, the occupancy type (private, public, or assembly), and whether water closets are flushometer or tank type.
The Four Facts Section 610.7 Requires
- Total fixture units from Table 610.3, with flushometer valves from Table 610.10.
- Developed length of supply pipe from the meter to the most remote outlet. Developed length is measured along the centerline of pipe and fittings and includes vertical rises.
- Elevation difference between the meter or other source and the highest fixture or outlet.
- Street main pressure. Where the pressure fluctuates during the day, design on the minimum pressure available.
Also watch for:
- A pressure regulator: size from 80% of its reduced setting (608.2).
- Devices with pressure loss: filters, softeners, backflow preventers, and tankless heaters. Section 610.2 requires their losses to be included in the pressure calculation.
- Continuous demands such as irrigation or process equipment: add them separately in gpm (Table 610.3 note 5).
A Worksheet Before Any Lookup
Build one line per segment. Record which fixtures it serves, whether it is cold, hot, or both, its fixture units, and its size. Then fill in the one-time values: available pressure, pressure range, and length column.
| Item | Value in the Section 12.2 through 12.4 example |
|---|---|
| Minimum street pressure at the meter | 62 psi |
| Highest outlet above the meter | 8 feet |
| Developed length, meter to most remote outlet | 140 feet |
| Occupancy | Public (office) |
| Water closets and urinal | Flushometer valves |
| Water heater | Storage type, serving lavatories and sinks |
The Example Building (Used Through Section 12.4)
A one-story office has:
- 2 flushometer water closets (1.6 gpf)
- 1 flushometer urinal (1.0 gpf)
- 2 lavatories (public)
- 1 service (mop) sink (public)
- 1 kitchen sink in a break room (domestic-type sink)
- 1 drinking fountain
- 1 hose bibb
- 1 storage water heater supplying hot water to the lavatories and sinks
The cold main runs from the meter to the water heater tee, then to the restroom, where it splits to the flushometer branch and the lavatory, sink, and fountain branch. The hot main leaves the water heater for the restroom lavatories, the mop sink, and the break-room sink.
How Part 3 Questions Are Usually Phrased
Expect the same handful of question forms, each tied to a segment label on the drawing:
- "How many water supply fixture units are carried by segment ___?" (Section 12.2)
- "What is the minimum size of segment ___?" (Section 12.4)
- "What size meter and building supply are required?" (Section 12.4)
- "Which pressure range and length column of Table 610.4 apply?" (Section 12.3)
- "What is the minimum size of the branch to the flushometer valve?" (Tables 610.3 and 610.10)
Because every size depends on the same pressure range and length column, a mistake in the first lookup repeats in every later answer. Settle those two values first and write them at the top of your scratch paper.
Abbreviations and Symbols to Recognize
| Mark | Meaning |
|---|---|
| CW / HW | Cold water / hot water |
| WM or M | Water meter |
| WH | Water heater |
| FV or FLV | Flushometer valve |
| HB | Hose bibb |
| PRV | Pressure-reducing valve (use 80% of its setting) |
| BFP, RP, or DC | Backflow preventer (its pressure loss counts under 610.2) |
| Elevation marks | Heights above the meter or finished floor, used for the 1/2 psi per foot adjustment |
Reading Traps to Avoid
- Developed length is not straight-line distance. Add every horizontal run and vertical rise from the meter to the most remote outlet.
- "Most remote" means farthest by developed length, which is not always the highest fixture. Elevation uses the highest outlet. The two can be different fixtures.
- Use the minimum pressure if the drawing gives a range such as "55 to 70 psi."
- Minimum building supply is 3/4 inch even if the table would allow 1/2 inch (610.8).
Under UPC 610.7, from where to where is the developed length for Table 610.4 sizing measured?
From the water heater to the highest fixture
Straight-line distance from the meter to the farthest fixture
From the street main to the building wall
From the meter to the most remote outlet, along the centerline of pipe and fittings
A drawing states that street pressure varies from 52 to 68 psi during the day. Which pressure should be used under UPC 610.7?
52 psi, the minimum available
80 psi, the code maximum
68 psi, the maximum
60 psi, the average
A Table 610.4 lookup shows that a small house could use a 1/2-inch building supply. What is the minimum building supply size under UPC 610.8?
3/4 inch
1 inch
Same as the meter
1/2 inch
Sections you finish are checked off in the contents.