6.1 DWV Materials, Joints, & Changes in Direction (UPC 701, 704–706; WA 701.2)
Key Takeaways
Washington's 701.2 keeps galvanized steel and 304 stainless steel drainage pipe at least 6 inches aboveground and vitrified clay at least 12 inches belowground.
Copper drainage and vent tube must weigh at least Type DWV (WA 701.2).
Horizontal-to-horizontal and vertical-to-horizontal connections must use 45-degree wyes, combination wye and one-eighth bends, or fittings of equivalent sweep (UPC 706.3, 706.4).
A double sanitary tee may be used only where its barrel is at least two pipe sizes larger than the largest inlet (UPC 706.2).
Caulked cast-iron joints need oakum or hemp and at least 1 inch of molten lead in one continuous pour (UPC 705.2.1).
Why Fittings and Materials Matter on Part 2
The Part 2 drawing shows DWV piping, fittings, and cleanouts. Knowing which fitting belongs at each change of direction, and which material may go underground, helps you spot the violations questions ask about (Section 11.4). Part 1 questions test the same rules directly.
Drainage Materials (Table 701.2 and Washington 701.2)
UPC Table 701.2 lists the approved materials and whether each may be used underground, aboveground, or for building sewers. Common entries include ABS and PVC Schedule 40 (solid and cellular core), co-extruded ABS and PVC, cast iron (ASTM A74, ASTM A888, CISPI 301), copper and copper-alloy Type DWV, galvanized steel and malleable iron, stainless steel 304 and 316L, polyethylene (building sewer), and vitrified clay (extra strength). Washington's amendment to 701.2 adds limits:
| Washington 701.2 item | Rule |
|---|---|
| 1 | Galvanized wrought iron or galvanized steel: not underground; keep at least 6 inches aboveground |
| 2 | ABS and PVC: install per the referenced standards. Except in individual single-family dwellings, plastic exposed in ducts or plenums must have a flame-spread index of 25 or less and smoke-developed index of 50 or less (ASTM E84 or UL 723) |
| 3 | Vitrified clay: not aboveground or where pressurized by a pump or ejector; keep at least 12 inches belowground |
| 4 | Copper: at least the weight of Type DWV |
| 5 | Stainless steel 304: not underground; keep at least 6 inches aboveground |
| 6 | Cast iron: listed and tested to the referenced standards, and marked with the country of origin and original manufacturer |
Other material rules:
- 701.4 Continuous wastes and tailpieces: Use drainage materials, but where exposed or accessible they may be seamless drawn brass at least No. 20 B&S gauge.
- 701.5 Sheet lead: at least 4 lb per sq ft for safe pans and 3 lb per sq ft for flashings. Lead bends and traps must be at least 1/8 inch thick.
- 701.3 Fittings: Drainage-type fittings, the same diameter as the pipe, with a smooth waterway, made to allow 1/4 inch per foot grade. Threaded pipe uses recessed drainage fittings, and burred ends are reamed.
Fixture Connections (UPC 704)
- 704.1: Drainage piping must have approved inlet fittings, located for the size and type of fixture to be connected.
- 704.2: Two fixtures set back-to-back or side-by-side, within the allowed trap-to-vent distance, may share a single vertical drain. Each must waste separately into an approved double fixture fitting with inlets at the same level.
- 704.3 (Washington amendment): Unless a fixture is specifically required to be indirect, or the AHJ approves otherwise, all fixtures, drains, appurtenances, and appliances must be directly connected to the drainage system.
Joints (UPC 705)
| Joint | Key rule |
|---|---|
| Caulked cast iron (705.2.1) | Oakum or hemp, then molten lead at least 1 inch deep in one continuous pour, caulked tight; finished lead not more than 1/8 inch below the hub rim; no coatings until tested |
| Compression gasket, hub and spigot (705.2.2) | ASTM C564 gasket; clean hub and spigot; spigot bottomed in the hub |
| Hubless shielded coupling (705.2.2) | Pipe seated against the center stop; bands tightened with a calibrated torque wrench set for that coupling |
| ABS or PVC solvent cement (705.1.2, 705.5.2) | Clean, square, deburred; PVC uses purple primer (ASTM F656) and ASTM D2564 cement |
| ABS to PVC (705.8.4) | Listed transition solvent cement, ASTM D3138, in building drains and sewers |
| Copper to cast iron (705.9.1) | Listed compression joint or copper-alloy ferrule |
| Slip joints (705.8.1) | Allowed only in fixture drains and traps, per their approval |
| Expansion joints (705.8.2) | Must be accessible, except in vent piping or drainage stacks |
Changes in Direction (UPC 706)
Section 706.1 requires changes in direction to use approved fittings with the angle of a 1/16 bend, 1/8 bend, or 1/6 bend, or fittings of equivalent sweep.
| Change | Allowed fittings |
|---|---|
| Horizontal to vertical (706.2) | 45° wye, 60° wye, combination wye and 1/8 bend, sanitary tee or sanitary tapped tee, or equivalent sweep |
| Horizontal to horizontal (706.3) | 45° wye, combination wye and 1/8 bend, or equivalent sweep |
| Vertical to horizontal (706.4) | 45° wye, combination wye and 1/8 bend, or equivalent sweep. 60° branches or offsets allowed only when installed in a true vertical position |
Multiple inlets at one level (706.2): No fitting with more than one inlet at the same level may be used unless it is built so discharge from one inlet cannot readily enter another. A double sanitary tee is permitted only when the barrel is at least two pipe sizes larger than the largest inlet. The recognized pipe sizes for this count are 2, 2-1/2, 3, 3-1/2, 4, 4-1/2, 5, 6 inches, and so on. For example, 2-inch inlets need at least a 3-inch barrel (2 to 2-1/2 is one size, and 3 is the second).
Why a sanitary tee is prohibited for horizontal-to-horizontal flow: its short-radius turn shoots water across the fitting and slows it, so solids settle and the line stops up. A wye with a 1/8 bend keeps the flow sweeping in the direction of travel.
Related Rules
- 310.1: No double hub, single or double tee branch, side inlet quarter bend, running thread, band, or saddle as a drainage fitting (Section 1.3).
- 310.3: No waste connection to a closet bend or water closet stub.
- 316.1: Use proper increasers and reducers between sizes.
- 711.1 Suds relief: Do not connect any drain within 8 feet of the base of a stack, at its vertical-to-horizontal change, if the stack carries suds-producing fixtures. Those fixtures are bathtubs, laundries, washer standpipes, kitchen sinks, and dishwashers. The rule does not apply to single-family residences or to stacks receiving discharge from fewer than three stories of fixtures.
A horizontal 3-inch branch must join a horizontal 4-inch building drain. Which fitting does UPC 706.3 allow?
A short-sweep quarter bend and a straight tee
A sanitary tee laid on its side
A 45-degree wye or a combination wye and one-eighth bend
A double sanitary tee with a 4-inch barrel
Two 3-inch water closet drains are to enter a vertical stack at the same level through a double sanitary tee. What minimum barrel size does UPC 706.2 require?
4 inches
5 inches
3 inches
3-1/2 inches
Under Washington's amendment to UPC 701.2, which drainage installation is prohibited?
Galvanized steel drainage pipe buried underground
Cast iron marked with its country of origin
Type DWV copper aboveground
PVC Schedule 40 underground