8.4 Island Fixture Venting, Combination Waste and Vent Systems, & Engineered Vent Systems (UPC 909, 910, 912)
Key Takeaways
An island sink vent rises as high as possible, at least to drainboard height, then returns down to connect through a wye immediately downstream of the vertical fixture drain (UPC 909.1).
The island return vent needs a foot vent taken off below the floor, drainage fittings below the floor, a slope of at least 1/4 inch per foot back to the drain, and an accessible cleanout (UPC 909.1).
Combination waste and vent systems require AHJ approval of construction documents before installation and are allowed only where structural conditions preclude conventional venting (UPC 910.1, 910.2).
Waste pipes and traps in a combination waste and vent system are at least two pipe sizes larger than Chapter 7 requires, and no water closet or urinal may connect (UPC 910.4, 910.7).
In a combination waste and vent system, vent area is at least half the drain's area, and branches over 15 feet are separately vented (UPC 910.3).
Island Fixture Venting (UPC 909.1)
A sink in a kitchen island has no wall to carry a vent up through. Section 909.1 allows a returned (loop) vent:
- Trap above the floor: The trap is roughed in above the floor.
- Rise: The vent rises from the fixture drain as high as possible, but not lower than the drainboard height.
- Return bend: Under the drainboard, the vent turns down with a one-piece return fitting or an assembly of a 45°, a 90°, and a 45° elbow, in that order.
- Return connection: The vent comes back down and connects to the horizontal sink drain immediately downstream of the vertical fixture drain, through a wye-branch fitting.
- Foot vent: A foot vent is taken off the vertical fixture vent through a wye branch immediately below the floor. It extends to the nearest partition and then through the roof, or it connects to other vents at a point at least 6 inches above the flood-level rim of the fixtures served.
- Drainage-grade vent: Below the floor, the vent uses drainage fittings and slopes at least 1/4 inch per foot back to the drain, because it can receive water if the drain backs up.
- Cleanout: An accessible cleanout goes in the vertical portion of the foot vent.
- Dedicated drain: The island sink drain upstream of the returned vent serves no other fixtures.
Pipe sizes follow the normal rules for drains and vents. For Part 2 drawings, recognize the loop shape and check each element: the wye connections, the foot vent, the cleanout, and the slope.
Why the wye and the foot vent? If the sink drain stops, water can rise into the returned vent. The drainage-pattern fittings and slope let it drain back out. The foot vent keeps a true air connection to the vent system even if the loop fills.
Combination Waste and Vent Systems (UPC 910)
The UPC defines a combination waste and vent system as a specially designed system of waste piping that horizontally wet vents one or more sinks or floor drains through a common waste and vent pipe. The pipe is sized large enough that air moves freely above the flow line. It is used for large floor areas, such as markets and warehouses, where floor drains and sinks are far from walls.
| Section | Requirement |
|---|---|
| 910.1 Where permitted | Only where structural conditions preclude conventional venting |
| 910.2 Approval | Construction documents approved by the AHJ before any part is installed |
| 910.3 Vents | Vents adequate for free air circulation. Any branch over 15 feet long is separately vented. Vent area is at least one-half the inside cross-sectional area of the drain served. The vent connects downstream of the uppermost fixture |
| 910.4 Size | Each waste pipe and trap is at least two pipe sizes larger than Chapter 7 requires, and at least two sizes larger than the fixture tailpiece or connection |
| 910.5 No vertical waste | No vertical waste pipe except the tailpiece between fixture and trap, which must be as short as possible and not over 2 feet. Branch lines may have 45° vertical offsets |
| 910.6 Cleanouts | An accessible cleanout in each vent. None is required on a wet-vented branch serving a single trap if the tailpiece is at least 2 inches and gives cleaning access through the trap |
| 910.7 Fixtures | No water closets or urinals. Other one-, two-, or three-unit fixtures nearby may connect conventionally, if the two-size increase is based on the total load |
Appendix B (adopted in Washington) gives explanatory notes on designing these systems.
Example: A floor drain normally needs a 2-inch trap and drain. On a combination waste and vent system, two pipe sizes larger is 3 inches, counting 2 to 2-1/2 as one size and 2-1/2 to 3 as the second. If the combination drain is 3 inches, its vent must be at least one-half of the 3-inch area: 7.07 ÷ 2 = 3.53 square inches. A 2-inch vent is only 3.14, so use 2-1/2 inches (4.91).
Engineered Vent Systems (UPC 912)
- 912.1: A vent system may be designed and sized by accepted engineering practice. It must be designed by a registered design professional and approved under 301.5, alternative engineered design.
- 912.2: It must still protect trap seals to the 1-inch water column limit of 901.3.
Single-Stack Systems
Section 310.4 prohibits single-stack drainage and venting systems with unvented branch lines. Washington's amendment to 310.4 keeps the exceptions of 908 through 911 and Appendix C. A combination waste and vent system is one of those exceptions. An unvented branch on a single stack is not.
Quick Comparison of Special Venting Methods
| Method | Typical use | Signature requirement |
|---|---|---|
| Vertical wet vent (908.1) | Stacked small fixtures on one story | 2-inch minimum sections; 6-foot maximum; up to 4 fixtures |
| Horizontal wet vent (908.2) | Bathroom group on one floor | 2 inches for 4 DFU or less, 3 inches for 5 or more |
| Circuit vent (911) | Batteries of fixtures on a horizontal branch | Up to 8 fixtures; 2-inch vent; relief vent with 4 or more water closets |
| Island loop vent (909) | Island sinks | Wye return, foot vent, cleanout, 1/4-inch slope |
| Combination waste and vent (910) | Large open floor areas | Two sizes larger; AHJ-approved plans; no water closets or urinals |
Which element is required when venting an island sink with a returned vent under UPC 909.1?
A sanitary tee connecting the return vent to the drain
An air admittance valve under the counter
A vent that rises only to the height of the trap
A foot vent taken off the vertical fixture vent by a wye immediately below the floor, with an accessible cleanout in its vertical portion
A floor drain would normally need a 2-inch trap and drain. What size is required on a combination waste and vent system under UPC 910.4?
2 inches
2-1/2 inches
3 inches
4 inches
Which fixture may not be connected to a combination waste and vent system under UPC 910.7?
A floor sink
A water closet
A 3-compartment sink
A floor drain