7.4 Interceptors and Separators: Grease, Sand, Oil, Laundry, & Bottling (UPC 1009–1017)

Key Takeaways

  • Each fixture discharging into a grease interceptor must be individually trapped and vented (UPC 1014.1.1).

  • The total capacity in gallons of fixtures draining to a hydromechanical grease interceptor may not exceed 2.5 times its certified gpm rating (UPC 1014.2.1).

  • UPC Table 1014.3.6 sizes gravity grease interceptors from 500 gallons for 8 DFU through 750 for 21, 1,000 for 35, and 1,250 for 90.

  • Toilets, urinals, and similar fixtures may not drain through a gravity grease interceptor (UPC 1014.3.2.1).

  • Sand interceptors must have a water seal of at least 6 inches, be vented, and have an outlet of at least 3 inches (UPC 1016.3, 1016.4).

Last updated: September 2026

When Interceptors Are Required (UPC 1009)

  • 1009.1: The AHJ requires interceptors (clarifiers) where needed to handle wastes containing grease, flammable wastes, sand, solids, acid or alkaline substances, or other ingredients harmful to the drainage system, sewer, or sewage disposal.
  • 1009.2: The AHJ approves size, type, and location. Only wastes that need treatment go into an interceptor.
  • 1009.3: Interceptors for sand and heavy solids have a water seal of at least 6 inches and must be readily accessible for cleaning.
  • 1009.4: Interceptors must not become air-bound where closed covers are used; each is properly vented.
  • 1009.5: Covers must be readily accessible. Needing a ladder or removing bulky equipment to service an interceptor is an accessibility violation. The location appears on the approved plans.
  • 1009.6: Interceptors are maintained by periodic removal of grease, scum, oil, and solids.
  • 707.7: The cleanout for an interceptor is outside the interceptor.

Grease Interceptors (UPC 1014)

When the AHJ requires pretreatment, fixtures and equipment producing grease-laden waste in food-preparation areas discharge into an approved grease interceptor. It must meet ASME A112.14.3, ASME A112.14.4, CSA B481, PDI G-101, or PDI G-102, and be sized per 1014.2.1 or 1014.3.6.

RuleRequirement
1014.1.1Each fixture discharging into a grease interceptor is individually trapped and vented
1014.1.2Collected grease may not go into drainage piping or a sewer. The AHJ may mandate added equipment and a maintenance program if an interceptor is neglected
1014.1.3No food waste disposer or dishwasher may connect to or discharge into a grease interceptor. Commercial disposers may discharge directly to the building drainage system

Hydromechanical grease interceptors (HGI)

  • 1014.2.1 Capacity: The total capacity in gallons of the fixtures discharging into an HGI may not exceed 2.5 times the interceptor's certified gpm flow rate (Table 1014.2.1).
  • 1014.2.2: A vent is installed downstream of the HGI.
  • Fixture capacity method (Example 1014.2.1): gallons = length × width × depth (in inches) ÷ 231. Multiply by a 0.75 fill factor, then divide by the drain period (1 or 2 minutes) to get gpm.
    • One 24 × 24 × 12-inch compartment holds 6,912 ÷ 231 ≈ 29.9 gallons. At a 0.75 fill, that is about 22.4 gallons, and two compartments about 44.9 gallons.
    • At a 1-minute drain period, the load is about 45 gpm, so the code example selects a 50 gpm unit. At a 2-minute drain period, the load is about 22.4 gpm, so a 25 gpm unit.
  • Table 1014.2.1 (gravity flow rates at 1/4 inch per foot): 2-inch pipe, 20 gpm full flow; 3-inch, 60 gpm; 4-inch, 125 gpm; 5-inch, 230 gpm; 6-inch, 375 gpm.

Gravity grease interceptors (GGI)

  • Serve the commercial kitchen; toilets, urinals, and similar fixtures may not drain through them (1014.3.2.1). Waste enters through the inlet pipe.
  • Scullery and pot sinks, dishwashers, soup kettles, and floor drains in grease areas may drain through the interceptor where the AHJ approves (1014.3.2).
  • Located as close as practical to the fixtures, accessible to pumping equipment. An IAPMO Z1001 interceptor may not be installed inside a building where food is handled (1014.3.4).
  • Each business establishment needing one has its own, unless the AHJ approves otherwise.

Table 1014.3.6, gravity grease interceptor sizing:

DFU82135901722163073424285767202,1122,640
Volume (gallons)5007501,0001,2501,5002,0002,5003,0004,0005,0007,50010,00015,000

When DFU are unknown, size from the maximum horizontal DFU of the inlet pipe in Table 703.2. For equipment with no DFU value, add the known flow in gpm multiplied by 30 minutes.

Code example 1014.3.6: three floor drains (2 DFU each = 6), a mop sink (3), and a food-prep sink (3) total 12 DFU. That exceeds 8, so the next row applies: a 750-gallon interceptor.

Abandoned gravity interceptors are pumped and filled like abandoned sewers (1014.3.7). FOG disposal systems must produce effluent of no more than 100 mg/L FOG, per ASME A112.14.6 (1015.4).

Other Interceptors

SectionUseKey requirement
1010.1Slaughterhouses, meat and fish packing, rendering, soap and hide-curing plantsApproved grease interceptor
1011.1Wash racks for vehicles and machineryProtected from storm water and drained to an approved interceptor
1012.1Commercial and industrial laundries without integral strainersInterceptor with a removable basket that stops solids 1/2 inch or larger
1013.1Bottling plantsInterceptor that separates broken glass and solids
1016 SandWastes heavier than waterTwo-section baffled design. Outlet the same size as the inlet, minimum 3 inches. Inlet section at least 2 sq ft net free opening, plus 1 sq ft per 5 gpm over 20 gpm. At least 2 feet deep below the outlet invert. 6-inch seal, vented
1017 Oil and flammable liquidRepair garages, gas stations with grease racks or pits, and oily process wastesSeparation or vapor compartment independently vented outdoors. A shared header must be at least 6 inches above the spill line of the lowest floor drain. Flammable vapor vent at least 2 inches. Rated units carry a stamped full-flow gpm rating and an overflow line to an underground tank
Test Your Knowledge

A restaurant's two-compartment pot sink has compartments of 24 × 24 × 12 inches. Using the UPC fixture capacity method with a 0.75 fill factor and a 1-minute drain period, what is the approximate calculated flow load on the hydromechanical grease interceptor?

A

45 gpm

B

60 gpm

C

20 gpm

D

30 gpm

Test Your Knowledge

A commercial kitchen line has 30 DFU draining to a gravity grease interceptor. What minimum volume does UPC Table 1014.3.6 require?

A

500 gallons

B

750 gallons

C

1,000 gallons

D

1,250 gallons

Test Your Knowledge

Which statement about a sand interceptor complies with UPC 1016?

A

Multiple floor drains may not discharge into one sand interceptor

B

It may have a 2-inch outlet if the flow is small

C

It needs a 6-inch water seal, must be vented, and its outlet must be at least 3 inches and match the inlet

D

It may be installed without a baffle if it is round

Sections you finish are checked off in the contents.