12.4 Part 3 Worked Example: Sizing the Meter, Building Supply, and Every Branch with Table 610.4

Key Takeaways

  • To size the meter and building supply, follow down the chosen Table 610.4 column to the first fixture-unit value equal to or greater than the load, and read the two left-hand columns (UPC 610.8).

  • Each branch is sized by its own fixture units, the system's total developed length, and the meter size, and no branch needs to exceed the building supply size (UPC 610.9).

  • Piping to a flushometer valve may never be smaller than the valve inlet, and Table 610.3 sets 1-inch minimum branches for flushometer water closets and 3/4-inch for flushometer urinals.

  • In the 46-60 psi range at 150 feet, Table 610.4 allows 4 fixture units on 1/2-inch pipe, 14 on 3/4-inch, 28 on 1-inch, and 128 on 1-1/2-inch pipe with a 1-1/2-inch meter.

  • The example office's 99.5 fixture units at 58 psi and 140 feet require a 1-1/2-inch meter and a 1-1/2-inch building supply.

Last updated: September 2026

The Column We Are Using

From Section 12.3: 58 psi, so the 46–60 psi range, and 140 feet, so the 150-foot column. Table 610.4, 46–60 psi, 150-foot column:

Meter and street serviceBuilding supply and branchesMax fixture units
3/41/24
3/43/414
3/4128
1130
3/41-1/439
11-1/452
1-1/21-1/466
11-1/285
1-1/21-1/2128
21-1/2150
1285
1-1/22272
22368
22-1/2535

Step 1: Meter and Building Supply (610.8)

Load = 99.5 FU. Reading down the column: 4, 14, 28, 30, 39, 52, 66, 85, then 128. That row gives a 1-1/2-inch meter and street service and a 1-1/2-inch building supply. It satisfies the 3/4-inch minimum.

If the drawing states an existing 1-inch meter, the 1-inch rows (30, 52, 85, and 85 for 2-inch pipe) cannot carry 99.5 FU. The meter itself would have to be upsized, which is why the meter and supply are chosen together.

Step 2: Branches (610.9)

Section 610.9 sizes each branch from its own fixture units, the total developed length of the system (the same 150-foot column), and the meter size. Two limits bracket the answer:

  • Upper limit: no branch needs to be larger than the building supply (1-1/2 inches here).
  • Lower limit: the Table 610.3 minimum fixture branch size, and for flushometers, never smaller than the valve inlet (610.10).

Reading method: Stay in the same column. Find the smallest branch size whose fixture-unit value is at least the branch load, using rows for the installed 1-1/2-inch meter. For the small sizes (1/2, 3/4, and 1 inch), the table only lists 3/4-inch or 1-inch meters. Those smaller-meter rows are conservative for a building with a larger meter, so use them.

SegmentLoad (FU)Table 610.4 resultCode minimumSize
S2 main to heater tee97.01-1/2 (128)—1-1/2 in
S3 cold main to restroom95.41-1/2 (128)—1-1/2 in
S4 flushometer branch (2 WC + 1 UR)901-1/4 carries 66 at most, so 1-1/2 (128)1 in1-1/2 in
S4a single water closet401 in carries 30 at most; 1-1/4 carries 661 in (Table 610.3)1-1/4 in
S4b single urinal203/4 carries 14; 1 in carries 283/4 in1 in
S5 cold branch to lavatories, sinks, fountain5.3751/2 carries 4; 3/4 carries 141/2 in3/4 in
Lavatory, cold or hot0.751/2 (4)1/2 in1/2 in
Mop sink, cold or hot2.251/2 (4)1/2 in1/2 in
Hose bibb branch2.5 (note 8)1/2 (4)1/2 in1/2 in
S6 cold feed to water heater4.8753/4 (14)—3/4 in
H1 hot main4.8753/4 (14)—3/4 in
H2 hot to lavatories1.51/2 (4)1/2 in1/2 in
H3 hot to sinks3.3751/2 (4)1/2 in1/2 in

Observations:

  • The flushometer water closet branch is 1-1/4 inches, not 1 inch. The 1-inch minimum in Table 610.3 is a floor. At 46–60 psi and 150 feet, 1-inch pipe carries only 28 or 30 FU, less than a flushometer's 40.
  • The urinal branch is 1 inch, larger than its 3/4-inch minimum, for the same reason: 3/4 inch carries only 14 FU in this column.
  • Hot branches are small because only three-quarters of each fixture's value lands on the hot side.

Step 3: Velocity and Special Cases

  • Section 610.12 limits copper velocity to 8 ft/s cold and 5 ft/s hot, and 610.1 requires every design to stay within the code's maximum velocities.
  • Flushometer tanks (pressure-assist tanks) are sized like flush tank water closets, not flushometer valves (610.11).
  • Section 610.13 exempts engineered systems acceptable to the AHJ, minor alterations and additions where the AHJ finds the supply adequate, replacement fixtures, and piping that is part of fixture equipment.

The Complete Answer Set for the Example

QuestionAnswer
Total fixture units on the building supply99.5
Pressure range46–60 psi
Length column150 feet
Meter and street service size1-1/2 inch
Building supply size1-1/2 inch
Flushometer branch serving 2 WC + 1 UR90 FU; 1-1/2 inch
Single flushometer water closet branch40 FU; 1-1/4 inch
Cold feed to water heater4.875 FU; 3/4 inch
Hot main4.875 FU; 3/4 inch

If You Get Stuck

  1. Recheck the occupancy column (public or private).
  2. Recheck the flushometer count per section (40, 70, 90, 105, or 115 plus 10 each).
  3. Recheck 1/2 psi per foot, not 0.433.
  4. Confirm the length column is at or above the developed length.
  5. Confirm the building supply is at least 3/4 inch and no branch exceeds the building supply.
Test Your Knowledge

In the 46-60 psi range and the 150-foot column of Table 610.4, a building has a load of 99.5 fixture units. What meter and building supply sizes does the table give?

A

2-inch meter, 2-inch supply

B

1-1/2-inch meter, 1-1/4-inch supply

C

1-inch meter, 1-1/2-inch supply

D

1-1/2-inch meter, 1-1/2-inch supply

Test Your Knowledge

A single flushometer water closet branch carries 40 fixture units. In the 46-60 psi, 150-foot column, 1-inch pipe allows at most 30 and 1-1/4-inch pipe allows 66 with a 1-1/2-inch meter. What size is required?

A

3/4 inch

B

1 inch, the Table 610.3 minimum

C

1-1/4 inch

D

1-1/2 inch

Test Your Knowledge

Under UPC 610.9, what is the largest size any branch must be when Table 610.4 is used?

A

One size larger than the building supply

B

No larger than the size Table 610.4 requires for the building supply

C

2 inches

D

The size of the street main