10.1 Alternate Water Sources: Reclaimed, Gray, and On-Site Treated Water (UPC Chapter 15 as Amended by Washington)
Key Takeaways
Washington does not adopt UPC Section 1502, Gray Water Systems; gray water may not be used for irrigation except as permitted by Department of Health rules.
Washington prohibits reclaimed water for toilet flushing or other indoor use in any residential property or dwelling unit where residents can access the plumbing for repairs or modifications (WA 1501.1.1).
Alternate water source piping must have a purple background (Pantone 512 or 522C) with uppercase lettering such as "CAUTION: NONPOTABLE RECLAIMED WATER, DO NOT DRINK" (UPC 601.3.3).
During a cross-connection test, the alternate water system stays depressurized for a period the AHJ sets, never less than 1 hour, while potable outlets are checked (UPC 1501.11.2.2).
If a cross-connection is found, Washington requires chlorinating the potable system at 50 ppm for 24 hours and a Washington-certified lab bacteriological test before recharging (WA 1501.11.2.3).
Scope
L&I lists UPC Chapter 15 in the Part 1 content. The chapter covers alternate water sources for nonpotable applications:
- Reclaimed (recycled) water: treated wastewater delivered by a utility (1503).
- Gray water: untreated wastewater from bathtubs, showers, lavatories, and clothes washers (1502).
- On-site treated nonpotable water: gray water or other water treated on site for uses such as flushing (1504).
Rainwater catchment is in Chapter 16 (Section 10.2).
Washington Amendments to Chapter 15
| Section | Washington rule |
|---|---|
| 1501.1.1 Allowable use | Where approved or required by the AHJ, reclaimed, gray, and on-site treated water may replace potable water for the uses in the chapter. Reclaimed water may not be used to flush toilets or for other indoor use in any residential property or dwelling unit where residents can access the plumbing for repairs or modifications |
| 1501.2 System design | Designed by a registered design professional or a person who demonstrates competency as the AHJ requires. Components, piping, and fittings must be listed |
| 1501.7 Water quality | Meets the AHJ's quality requirements for the use, with EPA/625/R-04/108 as guidance. Gray water used to flush toilets or urinals must be oxidized, coagulated, filtered, and disinfected, consistently at Washington Class A reclaimed water quality or better |
| 1501.13.1 Abandonment | Disconnect, drain, plug, and cap abandoned systems. Their pipe, tubing, fittings, and valves may not be reused for potable water |
| 1502.0 Gray water systems | Not adopted. "Gray water shall not be used for irrigation except as permitted by the department of health rules" |
| 1503.4 Reclaimed connections | No connection to potable or other alternate water. Potable makeup water to a reclaimed storage tank only through an approved air gap |
| 1504.1 and 1504.7 On-site treated | Supplies water closets, urinals, trap primers for floor drains and floor sinks, and other AHJ-approved uses. Treatment for flushing or surface irrigation must oxidize, coagulate, filter, and disinfect to Class A reclaimed quality or better, and be AHJ-approved |
Exam trap: Questions built on UPC 1502 gray water details (surge tanks, mulch basins, emitters, irrigation field sizing) describe provisions that Washington does not adopt. In Washington, gray water irrigation falls under Department of Health rules.
General Requirements Still in Effect (UPC 1501)
- 1501.3 Permit: A permit is required to build, install, or alter an alternate water source system.
- 1501.5 Maintenance: Inspect and maintain per Table 1501.5 and the manufacturer. The property owner keeps a maintenance log for permitted systems. The designer supplies an operation and maintenance manual.
- 1501.9: No mercury-containing controls may contact alternate water.
- 1501.10 Signs: Restrooms in commercial, industrial, and institutional buildings that flush with reclaimed or on-site treated water get signs with 1/2-inch letters. Equipment rooms get signs with 1-inch letters.
- 1501.12 Separation: Treated nonpotable pipes may share a trench with potable pipes at 12 inches minimum vertical and horizontal separation when both materials are approved for use within a building.
- 1501.14 Sizing: Size alternate water piping per Chapter 6, like potable piping.
Identification (UPC 601.3)
| System | Background | Lettering |
|---|---|---|
| Potable | Green | White |
| Nonpotable (general) | Yellow | Black uppercase: "CAUTION: NONPOTABLE WATER, DO NOT DRINK," with the liquid named and the flow direction shown |
| Alternate water sources | Purple (Pantone 512, 522C, or equivalent) | Uppercase, black: "CAUTION: NONPOTABLE GRAY WATER, DO NOT DRINK," "CAUTION: NONPOTABLE RECLAIMED WATER, DO NOT DRINK," "CAUTION: ON-SITE TREATED NONPOTABLE WATER, DO NOT DRINK," or "CAUTION: NONPOTABLE RAINWATER WATER, DO NOT DRINK" |
Reclaimed water valves, except fixture supply controls, have locking features (1503.8). Hose bibbs on reclaimed systems are not allowed in areas accessible to the public. Public access uses a quick-disconnect different from potable, and bibbs are labeled (1503.9). Reclaimed pipes may share a potable trench at 12 inches vertical and horizontal separation; otherwise the horizontal separation increases to 60 inches, and potable is always above reclaimed (1503.11).
Cross-Connection Inspection and Testing (UPC 1501.11)
- Supply test (1501.11.1): Test alternate water piping like potable piping (Section 1.2).
- Initial and annual inspection and test (1501.11.2): Isolate potable and alternate systems and test each independently. A visual inspection checks meters, pumps, signs, exposed piping, and valve lock seals. Cross-connection testing is required annually by the AHJ unless site conditions do not require it, but never less than once every 4 years.
- Cross-connection test (1501.11.2.2):
- Pressurize the potable system. Shut down, depressurize, and drain the alternate system.
- Keep the alternate system empty for the time the AHJ sets, never less than 1 hour.
- Check the alternate system's drain and all outlets. Flow from an alternate outlet indicates a cross-connection. No flow from a potable outlet means it is connected to the alternate system.
- Then reverse the procedure: depressurize the potable system and test the other way.
- Discovery of a cross-connection (Washington 1501.11.2.3):
- Shut down the reclaimed water piping at the meter and drain the riser.
- Shut down the potable water at the meter.
- Uncover and disconnect the cross-connection.
- Retest the building.
- Chlorinate the potable system at 50 ppm for 24 hours.
- Flush, then have a bacteriological test performed by a laboratory certified for drinking water in Washington. Recharge only when the AHJ, the health authority, and the purveyor accept the results.
A developer proposes piping reclaimed (recycled) water to flush toilets in new condominium units whose residents can access the plumbing. What does Washington's amendment to UPC 1501.1.1 say?
It is allowed with a purple meter
Reclaimed water may not be used to flush toilets or for other indoor use in any residential property or dwelling unit where residents can access the plumbing for repairs or modifications
It is allowed if a double check valve is installed
It is allowed only in single-family homes
Under the 2015 UPC as amended by Washington, how is residential gray water irrigation regulated?
By the L&I plumber certification rules
It is prohibited in all cases
By UPC Section 1502, including mulch basins and subsurface irrigation fields
UPC 1502 is not adopted; gray water may not be used for irrigation except as permitted by Department of Health rules
A cross-connection is discovered between a building's reclaimed water system and its potable water system. Which step does Washington's 1501.11.2.3 require for the potable system after the connection is removed and retested?
Flush only
Chlorinate at 50 ppm for 24 hours, flush, and obtain a satisfactory bacteriological test from a Washington-certified drinking water laboratory before recharging
Chlorinate at 200 ppm for 1 hour
Replace all potable piping