General Electrical Knowledge
13%of exam
Wiring and Protection
25%of exam
Wiring Methods and Materials
19%of exam
Equipment for General Use
19%of exam
Special Occupancies
12%of exam
Special Equipment
6%of exam
Special Conditions
6%of exam
Quick Facts
- Administrator
- PSI
- Questions
- 100
- Time limit
- 270 minutes
- Minimum passing score
- 70
- Exam fee
- $75
- Format
- Open book
- Exam NEC editions
- 2020 or 2023
- Idaho installation code
- 2023 NEC with Idaho amendments
Three-Phase Line Values
Root three, line volts, line amps
Exam Books vs Idaho Installation Code
PSI exam
- 2020 or 2023 NEC
- PSI’s listed references
Idaho installations
- 2023 NEC
- IDAPA §24.39.10.600 amendments
Identify the question’s governing reference
Power Formula Picker
- Resistive voltage drop→V = I × R(Use resistance of relevant path)
- Single-phase apparent power→VA = RMS V × RMS I
- Balanced three-phase apparent power→VA = √3 × Vₗ × Iₗ(Line voltage and line current)
- AC watts from volt-amperes→Multiply by power factor
- Energy from constant kW→Multiply by hours(Answer in kWh)
PSI Books and Test Rules
- NFPA 70 codebook
- 2020 or 2023 edition
- Ugly’s Electrical References
- 2023 edition listed
- Ferm’s Fast Finder Index
- Optional, 2020 or 2023
- Tom Henry’s Key Word Index
- Optional, 2020 or 2023
- Calculator
- Silent, nonprinting, nonprogrammable
- Marking before exam
- Highlight, underline, permanently tab
- Loose sheets or sticky notes
- Prohibited exam materials
- During exam
- Keep references free of writing
- Arrival
- 15 minutes before appointment
- Pace at 100 questions
- 2 min 42 sec eachAverage
Circuit Math
- Ohm’s law
- V = I × RVolts
- DC power
- P = V × IWatts
- Single-phase apparent power
- VA = V × IRMS values
- Balanced three-phase apparent power
- VA = √3 × Vₗ × IₗLine RMS values
- AC real power
- Watts = VA × power factor
- Series resistors
- Same current, add resistances
- Parallel resistors
- Same voltage, add inverse resistancesInvert sum for total resistance
- Electrical energy
- kWh = kW × hours
Two Grounding Lookups
Electrode sees wire, equipment sees breaker
Electrode Conductor vs Equipment Ground
Grounding electrode conductor
- Connects to electrode system
- Service sizing starts at 250.66
Equipment grounding conductor
- Part of fault return path
- Wire sizing starts at 250.122
Identify which conductor is asked
Circuit and Protection Picker
- Final overcurrent device to outlets→Article 210(Branch circuit)
- Supply to branch overcurrent devices→Article 215(Feeder)
- Supply from serving utility→Article 230(Service)
- Calculate circuit or service demand→Article 220(Apply method-specific demand rules)
- Choose standard breaker rating→§240.6(Check applicable protection rules first)
- Size service electrode conductor→Table 250.66(Start with largest ungrounded service conductor)
- Size wire-type equipment ground→Table 250.122(Start with upstream protection rating)
Circuits and Loads
- Branch circuits
- Article 210
- Feeders
- Article 215
- Load calculations
- Article 220
- Outside circuits and feeders
- Article 225
- Service equipment
- Article 230
- Overcurrent protection
- Article 240
- Continuous load
- Maximum current expected ≥3 hours
- Typical branch and feeder ampacity
- 1.25 × continuous + noncontinuousCheck listed exceptions
- Dwelling demand calculation
- Standard Part III, optional §220.82Check eligibility
GFCI vs AFCI
GFCI
- Ground-fault current detection
- Personnel shock protection
- §210.8 locations
AFCI
- Abnormal arcing detection
- Fire risk reduction
- §210.12 locations
Match protection to the hazard
Grounding and Bonding
- Service bonding
- §250.24
- Separately derived systems
- §250.30
- Separate building supplied by feeder
- §250.32
- Electrode types and system
- §250.50 and §250.52
- Grounding electrode conductor sizing
- Table 250.66Check electrode exceptions
- Wire-type equipment grounding conductor sizing
- Table 250.122Upstream overcurrent device rating
- Bonded metal enclosures
- Effective ground-fault current path
Idaho Installation Rules
- State installation amendments
- IDAPA 24.39.10.600
- Dwelling GFCI locations
- Check Rule 600’s §210.8 edits
- One- and two-family AFCI
- Bedroom circuits and outletsIdaho §210.12(B) exception
- Dwelling service surge protection
- Permitted under amended §230.67
- One- and two-family emergency disconnect
- Permitted under amended §230.85
Volume or Area
Boxes take volume, raceways take area
Box Fill vs Raceway Fill
Box fill
- Cubic inches
- Count applicable volume allowances
Raceway fill
- Cross-sectional area
- Use applicable percentage limit
Identify enclosure or raceway first
Ampacity or Fill Picker
- Select base conductor ampacity→Table 310.16(Check table conditions and terminations)
- Ambient temperature differs→Table 310.15(B)(1)(Apply temperature correction as applicable)
- More than three current-carrying conductors→Table 310.15(C)(1)(Check bundling exceptions)
- Measure available box volume→§314.16(A)(Check box and extension markings)
- Count box fill allowances→§314.16(B)(Compare against usable box volume)
- Mixed wire sizes in conduit→Chapter 9 Tables 1, 4, 5(Use wire and raceway areas)
Conductor Ampacity
- Base ampacity
- Table 310.16 where applicable
- Terminal temperature limits
- §110.14(C)
- Ambient temperature correction
- Table 310.15(B)(1)
- Bundled current-carrying conductors
- Table 310.15(C)(1) adjustment
- Neutral in conductor count
- Check §310.15(E) load conditions
- Equipment grounding or bonding conductor
- Excluded from ampacity adjustment count§310.15(F)
- Qualifying dwelling services and feeders
- Check §310.12 scope
Boxes and Raceway Fill
- Box fill
- §314.16 compares cubic-inch volumes
- Conductor volume by gauge
- Table 314.16(B)(1)
- Device yoke fill
- Double allowance under §314.16(B)(4)
- Equipment grounds in box
- Apply §314.16(B)(5) by edition
- Raceway fill limits
- Chapter 9 Table 1
- Normal fill, 1 conductor
- 53%
- Normal fill, 2 conductors
- 31%
- Normal fill, 3+ conductors
- 40%
- Raceway area
- Chapter 9 Table 4
- Insulated conductor area
- Chapter 9 Table 5
- Grounding conductor in raceway
- Include in physical fill
Cable and Raceway Articles
- General wiring methods
- Article 300
- Metal-clad cable
- Article 330
- Nonmetallic-sheathed cable
- Article 334
- Underground feeder cable
- Article 340
- Rigid metal conduit
- Article 344
- Rigid PVC conduit
- Article 352
- Electrical metallic tubing
- Article 358
Table Current vs Nameplate Current
NEC motor table values
- Typical branch conductor sizing
- Typical branch fault protection
Motor nameplate current
- Separate overload protection
- Special motor cases per §430.6
Choose the sizing task first
Motor Lookup Picker
- Typical single-phase motor table current→Table 430.248
- Typical three-phase motor table current→Table 430.250
- Single continuous-duty motor branch conductors→§430.22(Check §430.6 current basis)
- Separate running overload protection→§430.32(Use applicable nameplate factors)
- Motor branch short-circuit protection→§430.52(Device type determines table factor)
Motor Sizing
- Table vs nameplate selection
- §430.6(A)Check exceptions
- Single-phase AC full-load current
- Table 430.248
- Three-phase AC full-load current
- Table 430.250
- Single continuous-duty motor conductors
- Generally 125% of table current§430.22
- Separate motor overload
- Start with nameplate current§430.32
- Motor short-circuit and ground-fault protection
- §430.52Select by device type
- Motor disconnect
- Article 430 Part IX
General Equipment Articles
- Flexible cords and cables
- Article 400
- Switches
- Article 404
- Receptacles
- Article 406
- Panelboards
- Article 408
- Luminaires
- Article 410
- Appliances
- Article 422
- Air conditioning and refrigeration
- Article 440
- Transformers
- Article 450
Hazard Class vs Division
Class
- Identifies hazardous material type
- Gas, dust, or fibers
Division
- Describes conditions of hazard presence
- Check class-specific definitions
Specify both before selecting equipment
Special Installation Picker
- Combustible dust under division system→Article 502(Class II)
- Fuel dispensing site→Article 514(Check classified boundaries)
- Waterfront docking facility→Article 555
- Pool equipotential bonding→§680.26
- Backup legally required for safety→Classify under Article 700 or 701(Check which category is designated)
- Backup serves owner-selected loads→Article 702(Optional standby)
Hazardous Locations
- Class and division framework
- Article 500
- Class I
- Flammable gases or vaporsArticle 501
- Class II
- Combustible dustArticle 502
- Class III
- Ignitible fibers or flyingsArticle 503
- Zone 0, 1, 2
- Gas or vapor classificationArticle 505
- Zone 20, 21, 22
- Dust, fibers, or flyings classificationArticle 506
Occupancy Articles
- Commercial repair garages
- Article 511
- Motor fuel dispensing
- Article 514
- Health care facilities
- Article 517
- Assembly occupancies
- Article 518
- Agricultural buildings
- Article 547
- Marinas and docking facilities
- Article 555
- Temporary installations
- Article 590
Pool Bonding vs Grounding
Equipotential bonding
- Reduces voltage differences
- §680.26
Equipment grounding
- Provides a fault current path
- Article 250 and Article 680
Check both applicable rules
Special Equipment Articles
- Signs and outline lighting
- Article 600
- Elevators and escalators
- Article 620
- Vehicle charging
- Article 625
- Information technology equipment
- Article 645
- Pools, spas, and fountains
- Article 680
- Pool equipotential bonding
- §680.26 reduces voltage gradients
- Solar photovoltaic systems
- Article 690
- Fire pumps
- Article 695
Standby in Order
Emergency, legally required, optional
Emergency vs Optional Standby
Emergency system
- Article 700
- Legally required and classified emergency
Optional standby system
- Article 702
- Serves selected non-life-safety loads
Check required standby under 701
Standby and Limited Energy
- Emergency systems
- Article 700
- Legally required standby
- Article 701
- Optional standby
- Article 702
- Interconnected power production
- Article 705
- Energy storage systems
- Article 706
- Class 1 edition split
- 2020 Art. 725, 2023 Art. 724Power-limited Class 1
- Class 2 and Class 3
- Article 725
- Fire alarm systems
- Article 760
Common Traps
Check the Approved Book List
NFPA 70 codebook on PSI list ≠ NEC Handbook outside listed references
Open-Book Limits
Permanent tabs before testing ≠ Loose sheets and sticky notes
Power Units
Watts measure real power ≠ Volt-amperes measure apparent power
Ampacity Constraints
Insulation temperature rating ≠ Equipment terminal temperature limit
Grounds in Raceway Calculations
Grounding conductors count for fill ≠ Current-carrying count drives ampacity adjustment
Motor Protection Has Two Jobs
Overloads address sustained excess current ≠ Short-circuit and ground-fault protection
Two Different Class Systems
Class I hazardous locations ≠ Class 1 power-limited circuits
Three Standby Categories
Legally required standby under 701 ≠ Emergency systems under 700
Last Minute
- 1.Budget 270 minutes for 100 questions
- 2.Bring 2020 or 2023 NEC
- 3.Pack the listed 2023 Ugly’s
- 4.Use permanent tabs before testing
- 5.Bring a silent nonprogrammable nonprinting calculator
- 6.Separate continuous and noncontinuous loads
- 7.Check ampacity against terminal limits
- 8.Service electrode conductor → Table 250.66
- 9.Use 250.122 for wire equipment grounds
- 10.Distinguish box volume from raceway area
- 11.Use nameplate current for separate overloads
- 12.Check Class 1 article by edition
- 13.Confirm Idaho amendments for field questions