Idaho Journeyman Electrician Cheat Sheet

Quick Facts

Administrator
PSI
Questions
100
Time limit
270 minutes
Minimum passing score
70
Exam fee
$75
Format
Open book
Exam NEC editions
2020 or 2023
Idaho installation code
2023 NEC with Idaho amendments

Three-Phase Line Values

Root three, line volts, line amps

Balanced three-phase VAWatts also need power factor

Exam Books vs Idaho Installation Code

PSI exam

  • 2020 or 2023 NEC
  • PSI’s listed references

Idaho installations

  • 2023 NEC
  • IDAPA §24.39.10.600 amendments

Identify the question’s governing reference

Power Formula Picker

  1. Resistive voltage drop→V = I × R(Use resistance of relevant path)
  2. Single-phase apparent power→VA = RMS V × RMS I
  3. Balanced three-phase apparent power→VA = √3 × Vₗ × Iₗ(Line voltage and line current)
  4. AC watts from volt-amperes→Multiply by power factor
  5. Energy from constant kW→Multiply by hours(Answer in kWh)

PSI Books and Test Rules

NFPA 70 codebook
2020 or 2023 edition
Ugly’s Electrical References
2023 edition listed
Ferm’s Fast Finder Index
Optional, 2020 or 2023
Tom Henry’s Key Word Index
Optional, 2020 or 2023
Calculator
Silent, nonprinting, nonprogrammable
Marking before exam
Highlight, underline, permanently tab
Loose sheets or sticky notes
Prohibited exam materials
During exam
Keep references free of writing
Arrival
15 minutes before appointment
Pace at 100 questions
2 min 42 sec eachAverage

Circuit Math

Ohm’s law
V = I × RVolts
DC power
P = V × IWatts
Single-phase apparent power
VA = V × IRMS values
Balanced three-phase apparent power
VA = √3 × Vₗ × IₗLine RMS values
AC real power
Watts = VA × power factor
Series resistors
Same current, add resistances
Parallel resistors
Same voltage, add inverse resistancesInvert sum for total resistance
Electrical energy
kWh = kW × hours

NEC Navigation

Code arrangement
§90.3
Defined terms
Start with Article 100
General installation rules
Chapters 1–4
Special applications
Chapters 5–7 modify general rules
Worked NEC examples
Informative Annex D

Two Grounding Lookups

Electrode sees wire, equipment sees breaker

250.66 service conductor size250.122 upstream overcurrent device

Electrode Conductor vs Equipment Ground

Grounding electrode conductor

  • Connects to electrode system
  • Service sizing starts at 250.66

Equipment grounding conductor

  • Part of fault return path
  • Wire sizing starts at 250.122

Identify which conductor is asked

Circuit and Protection Picker

  1. Final overcurrent device to outlets→Article 210(Branch circuit)
  2. Supply to branch overcurrent devices→Article 215(Feeder)
  3. Supply from serving utility→Article 230(Service)
  4. Calculate circuit or service demand→Article 220(Apply method-specific demand rules)
  5. Choose standard breaker rating→§240.6(Check applicable protection rules first)
  6. Size service electrode conductor→Table 250.66(Start with largest ungrounded service conductor)
  7. Size wire-type equipment ground→Table 250.122(Start with upstream protection rating)

Circuits and Loads

Branch circuits
Article 210
Feeders
Article 215
Load calculations
Article 220
Outside circuits and feeders
Article 225
Service equipment
Article 230
Overcurrent protection
Article 240
Continuous load
Maximum current expected ≥3 hours
Typical branch and feeder ampacity
1.25 × continuous + noncontinuousCheck listed exceptions
Dwelling demand calculation
Standard Part III, optional §220.82Check eligibility

GFCI vs AFCI

GFCI

  • Ground-fault current detection
  • Personnel shock protection
  • §210.8 locations

AFCI

  • Abnormal arcing detection
  • Fire risk reduction
  • §210.12 locations

Match protection to the hazard

Grounding and Bonding

Service bonding
§250.24
Separately derived systems
§250.30
Separate building supplied by feeder
§250.32
Electrode types and system
§250.50 and §250.52
Grounding electrode conductor sizing
Table 250.66Check electrode exceptions
Wire-type equipment grounding conductor sizing
Table 250.122Upstream overcurrent device rating
Bonded metal enclosures
Effective ground-fault current path

Idaho Installation Rules

State installation amendments
IDAPA 24.39.10.600
Dwelling GFCI locations
Check Rule 600’s §210.8 edits
One- and two-family AFCI
Bedroom circuits and outletsIdaho §210.12(B) exception
Dwelling service surge protection
Permitted under amended §230.67
One- and two-family emergency disconnect
Permitted under amended §230.85

Volume or Area

Boxes take volume, raceways take area

§314.16 box allowancesChapter 9 fill tables

Box Fill vs Raceway Fill

Box fill

  • Cubic inches
  • Count applicable volume allowances

Raceway fill

  • Cross-sectional area
  • Use applicable percentage limit

Identify enclosure or raceway first

Ampacity or Fill Picker

  1. Select base conductor ampacity→Table 310.16(Check table conditions and terminations)
  2. Ambient temperature differs→Table 310.15(B)(1)(Apply temperature correction as applicable)
  3. More than three current-carrying conductors→Table 310.15(C)(1)(Check bundling exceptions)
  4. Measure available box volume→§314.16(A)(Check box and extension markings)
  5. Count box fill allowances→§314.16(B)(Compare against usable box volume)
  6. Mixed wire sizes in conduit→Chapter 9 Tables 1, 4, 5(Use wire and raceway areas)

Conductor Ampacity

Base ampacity
Table 310.16 where applicable
Terminal temperature limits
§110.14(C)
Ambient temperature correction
Table 310.15(B)(1)
Bundled current-carrying conductors
Table 310.15(C)(1) adjustment
Neutral in conductor count
Check §310.15(E) load conditions
Equipment grounding or bonding conductor
Excluded from ampacity adjustment count§310.15(F)
Qualifying dwelling services and feeders
Check §310.12 scope

Boxes and Raceway Fill

Box fill
§314.16 compares cubic-inch volumes
Conductor volume by gauge
Table 314.16(B)(1)
Device yoke fill
Double allowance under §314.16(B)(4)
Equipment grounds in box
Apply §314.16(B)(5) by edition
Raceway fill limits
Chapter 9 Table 1
Normal fill, 1 conductor
53%
Normal fill, 2 conductors
31%
Normal fill, 3+ conductors
40%
Raceway area
Chapter 9 Table 4
Insulated conductor area
Chapter 9 Table 5
Grounding conductor in raceway
Include in physical fill

Cable and Raceway Articles

General wiring methods
Article 300
Metal-clad cable
Article 330
Nonmetallic-sheathed cable
Article 334
Underground feeder cable
Article 340
Rigid metal conduit
Article 344
Rigid PVC conduit
Article 352
Electrical metallic tubing
Article 358

Table Current vs Nameplate Current

NEC motor table values

  • Typical branch conductor sizing
  • Typical branch fault protection

Motor nameplate current

  • Separate overload protection
  • Special motor cases per §430.6

Choose the sizing task first

Motor Lookup Picker

  1. Typical single-phase motor table current→Table 430.248
  2. Typical three-phase motor table current→Table 430.250
  3. Single continuous-duty motor branch conductors→§430.22(Check §430.6 current basis)
  4. Separate running overload protection→§430.32(Use applicable nameplate factors)
  5. Motor branch short-circuit protection→§430.52(Device type determines table factor)

Motor Sizing

Table vs nameplate selection
§430.6(A)Check exceptions
Single-phase AC full-load current
Table 430.248
Three-phase AC full-load current
Table 430.250
Single continuous-duty motor conductors
Generally 125% of table current§430.22
Separate motor overload
Start with nameplate current§430.32
Motor short-circuit and ground-fault protection
§430.52Select by device type
Motor disconnect
Article 430 Part IX

General Equipment Articles

Flexible cords and cables
Article 400
Switches
Article 404
Receptacles
Article 406
Panelboards
Article 408
Luminaires
Article 410
Appliances
Article 422
Air conditioning and refrigeration
Article 440
Transformers
Article 450

Hazard Class vs Division

Class

  • Identifies hazardous material type
  • Gas, dust, or fibers

Division

  • Describes conditions of hazard presence
  • Check class-specific definitions

Specify both before selecting equipment

Special Installation Picker

  1. Combustible dust under division system→Article 502(Class II)
  2. Fuel dispensing site→Article 514(Check classified boundaries)
  3. Waterfront docking facility→Article 555
  4. Pool equipotential bonding→§680.26
  5. Backup legally required for safety→Classify under Article 700 or 701(Check which category is designated)
  6. Backup serves owner-selected loads→Article 702(Optional standby)

Hazardous Locations

Class and division framework
Article 500
Class I
Flammable gases or vaporsArticle 501
Class II
Combustible dustArticle 502
Class III
Ignitible fibers or flyingsArticle 503
Zone 0, 1, 2
Gas or vapor classificationArticle 505
Zone 20, 21, 22
Dust, fibers, or flyings classificationArticle 506

Occupancy Articles

Commercial repair garages
Article 511
Motor fuel dispensing
Article 514
Health care facilities
Article 517
Assembly occupancies
Article 518
Agricultural buildings
Article 547
Marinas and docking facilities
Article 555
Temporary installations
Article 590

Pool Bonding vs Grounding

Equipotential bonding

  • Reduces voltage differences
  • §680.26

Equipment grounding

  • Provides a fault current path
  • Article 250 and Article 680

Check both applicable rules

Special Equipment Articles

Signs and outline lighting
Article 600
Elevators and escalators
Article 620
Vehicle charging
Article 625
Information technology equipment
Article 645
Pools, spas, and fountains
Article 680
Pool equipotential bonding
§680.26 reduces voltage gradients
Solar photovoltaic systems
Article 690
Fire pumps
Article 695

Standby in Order

Emergency, legally required, optional

700 emergency701 legally required standby702 optional standby

Emergency vs Optional Standby

Emergency system

  • Article 700
  • Legally required and classified emergency

Optional standby system

  • Article 702
  • Serves selected non-life-safety loads

Check required standby under 701

Standby and Limited Energy

Emergency systems
Article 700
Legally required standby
Article 701
Optional standby
Article 702
Interconnected power production
Article 705
Energy storage systems
Article 706
Class 1 edition split
2020 Art. 725, 2023 Art. 724Power-limited Class 1
Class 2 and Class 3
Article 725
Fire alarm systems
Article 760

Common Traps

Check the Approved Book List

NFPA 70 codebook on PSI list ≠ NEC Handbook outside listed references

Open-Book Limits

Permanent tabs before testing ≠ Loose sheets and sticky notes

Power Units

Watts measure real power ≠ Volt-amperes measure apparent power

Ampacity Constraints

Insulation temperature rating ≠ Equipment terminal temperature limit

Grounds in Raceway Calculations

Grounding conductors count for fill ≠ Current-carrying count drives ampacity adjustment

Motor Protection Has Two Jobs

Overloads address sustained excess current ≠ Short-circuit and ground-fault protection

Two Different Class Systems

Class I hazardous locations ≠ Class 1 power-limited circuits

Three Standby Categories

Legally required standby under 701 ≠ Emergency systems under 700

Last Minute

  1. 1.Budget 270 minutes for 100 questions
  2. 2.Bring 2020 or 2023 NEC
  3. 3.Pack the listed 2023 Ugly’s
  4. 4.Use permanent tabs before testing
  5. 5.Bring a silent nonprogrammable nonprinting calculator
  6. 6.Separate continuous and noncontinuous loads
  7. 7.Check ampacity against terminal limits
  8. 8.Service electrode conductor → Table 250.66
  9. 9.Use 250.122 for wire equipment grounds
  10. 10.Distinguish box volume from raceway area
  11. 11.Use nameplate current for separate overloads
  12. 12.Check Class 1 article by edition
  13. 13.Confirm Idaho amendments for field questions
Same family resources

Explore More Electrician License