According to the NEC as adopted by Alabama, what is the definition of a 'branch circuit'?

A
B
C
D
to track
2026 Statistics

Key Facts: AL Electrician Exam

70%

Passing Score

AECB / Prov

80

Questions

4-hour limit

$115

Exam Fee

Prov

NEC 2023

Code Edition

AECB

Alabama's journeyman electrician exam is based on the NEC 2023 and administered by Prov. The exam has 80 questions with a 4-hour time limit and requires 70% to pass. The $115 fee is paid to Prov. Alabama requires completion of an apprenticeship program or equivalent experience under a licensed contractor before sitting for the exam.

Sample AL Electrician Practice Questions

Try these sample questions to test your AL Electrician exam readiness. Each question includes a detailed explanation. Start the interactive quiz above for the full 100+ question experience with AI tutoring.

1According to the NEC as adopted by Alabama, what is the definition of a 'branch circuit'?
A.The circuit conductors between the final overcurrent device and the outlet(s)
B.The circuit conductors between the service point and the main disconnect
C.The circuit conductors between the transformer and the service entrance
D.The circuit conductors between two panelboards
Explanation: Per NEC Article 100, a branch circuit is defined as the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s). This definition is fundamental to understanding how electrical systems are divided and protected.
2Under Alabama's adoption of the NEC 2023, what is the minimum size copper grounding electrode conductor required for a 200-ampere service?
A.4 AWG copper
B.6 AWG copper
C.2 AWG copper
D.1/0 AWG copper
Explanation: Per NEC Table 250.66, a 200-ampere service with copper service-entrance conductors sized at 2/0 AWG or 3/0 AWG requires a minimum 4 AWG copper grounding electrode conductor. This table correlates the size of the largest service-entrance conductor to the grounding electrode conductor size.
3Per the NEC 2023 as enforced by the Alabama Electrical Contractors Board, what is the maximum voltage allowed for a Class 2 circuit?
A.30 volts
B.42.4 volts peak
C.150 volts
D.100 volts
Explanation: Per NEC Article 725 and Chapter 9 Table 11(A), Class 2 circuits are limited to 150 volts maximum, with current limitations based on the voltage level. Class 2 power sources must be listed and comply with the power limitations specified in the tables.
4In Alabama, what is the minimum number of 20-ampere small-appliance branch circuits required for the kitchen and dining areas of a dwelling unit?
A.One
B.Two
C.Three
D.Four
Explanation: NEC Section 210.11(C)(1) requires a minimum of two 20-ampere small-appliance branch circuits to serve all wall and floor receptacle outlets in the kitchen, pantry, breakfast room, dining room, and similar areas. These circuits must serve only receptacle outlets in these areas.
5According to the NEC 2023 as adopted in Alabama, what is the ampacity of a 6 AWG copper THWN-2 conductor at 75°C column?
A.55 amperes
B.65 amperes
C.75 amperes
D.85 amperes
Explanation: Per NEC Table 310.16, a 6 AWG copper conductor with THWN-2 insulation rated at 75°C has an ampacity of 65 amperes. While THWN-2 is rated for 90°C, Section 310.15(B)(2) generally requires using the 75°C column for termination purposes unless equipment is rated and listed for higher temperatures.
6Under Alabama's NEC adoption, what is the maximum percentage of conduit fill allowed for three or more conductors in a raceway?
A.31%
B.40%
C.53%
D.60%
Explanation: Per NEC Chapter 9, Table 1, when three or more conductors are installed in a raceway, the maximum fill is 40% of the conduit's total cross-sectional area. This allows adequate space for heat dissipation and ease of pulling conductors.
7Per NEC 2023 in Alabama, what is the minimum burial depth for rigid metal conduit (RMC) containing circuit conductors under a residential driveway?
A.6 inches
B.12 inches
C.18 inches
D.24 inches
Explanation: Per NEC Table 300.5, rigid metal conduit (RMC) under a residential driveway requires a minimum burial depth of 6 inches. RMC provides significant mechanical protection, which is why the NEC allows the shallowest burial depth for this raceway type.
8In Alabama, according to NEC Article 430, what is the maximum rating of a branch-circuit short-circuit and ground-fault protective device for a motor with a full-load current of 40 amperes using an inverse-time circuit breaker?
A.80 amperes
B.100 amperes
C.125 amperes
D.150 amperes
Explanation: Per NEC Table 430.52, an inverse-time circuit breaker used for motor branch-circuit short-circuit and ground-fault protection is permitted at a maximum of 250% of the motor full-load current. For a 40-ampere motor: 40 × 2.50 = 100 amperes. This provides adequate protection while allowing motor starting current.
9Under the NEC 2023 adopted by the AECB, what is the general lighting load in volt-amperes per square foot for a dwelling unit?
A.2 VA per square foot
B.3 VA per square foot
C.3.5 VA per square foot
D.5 VA per square foot
Explanation: Per NEC Table 220.12, the general lighting load for dwelling units is calculated at 3 volt-amperes per square foot of habitable space. This value is used for load calculations to determine the minimum number of branch circuits and service sizing.
10Per NEC 2023 as adopted in Alabama, what is the minimum height above finished grade for service drop conductors over a residential driveway?
A.10 feet
B.12 feet
C.15 feet
D.18 feet
Explanation: NEC Section 230.24(B)(1) requires service drop conductors to maintain a minimum clearance of 12 feet above finished grade over residential driveways and commercial areas not subject to truck traffic. This clearance ensures vehicles can pass safely underneath.

About the AL Electrician Exam

The Alabama journeyman electrician exam is administered by Prov on behalf of the AECB and tests knowledge of the NEC 2023, electrical theory, wiring methods, grounding and bonding, load calculations, and Alabama-specific amendments. Candidates must demonstrate competency across 80 multiple-choice questions within 4 hours.

Questions

80 scored questions

Time Limit

4 hours

Passing Score

70%

Exam Fee

$115 (Alabama Electrical Contractors Board (AECB))

AL Electrician Exam Content Outline

25%

Wiring Methods & Materials

Raceways, cables, conduit fill, conductor ampacity, and NEC Chapter 3 installation requirements

20%

Grounding & Bonding

Article 250 grounding electrode systems, equipment grounding, bonding requirements, and ground-fault protection

20%

Branch Circuits & Overcurrent Protection

Conductor sizing, GFCI/AFCI requirements, receptacle spacing, and overcurrent device ratings

20%

Load Calculations & Services

Dwelling and commercial calculations, demand factors, service entrance, and feeder sizing

15%

Motors, Special Occupancies & NEC General

Motor circuits, transformers, hazardous locations, healthcare facilities, swimming pools, and NEC definitions

How to Pass the AL Electrician Exam

What You Need to Know

  • Passing score: 70%
  • Exam length: 80 questions
  • Time limit: 4 hours
  • Exam fee: $115

Keys to Passing

  • Complete 500+ practice questions
  • Score 80%+ consistently before scheduling
  • Focus on highest-weighted sections
  • Use our AI tutor for tough concepts

AL Electrician Study Tips from Top Performers

1Master NEC Article 250 (Grounding and Bonding) — it is the most heavily tested topic on Alabama's exam
2Practice dwelling unit load calculations per NEC Article 220 until you can complete them quickly and accurately
3Memorize key ampacity values from Table 310.16 for common conductor sizes at 75°C
4Study conduit fill calculations using NEC Chapter 9 tables for common conductor and raceway combinations
5Review motor circuit requirements in Article 430 including overload and short-circuit protection sizing

Frequently Asked Questions

What NEC edition does Alabama use for the electrician exam?

Alabama uses the NEC 2023 edition for the journeyman electrician licensing exam. The Alabama Electrical Contractors Board (AECB) adopted this edition and all exam questions are based on it.

Who administers the Alabama electrician exam?

The exam is administered by Prov (formerly Prometric/PSI) on behalf of the AECB. You register and schedule through Prov's website after your application is approved by the AECB.

Is the Alabama electrician exam open book?

Yes, most Prov-administered electrical exams allow a bound copy of the NEC 2023. No loose pages, handwritten notes, or tabs that can detach are permitted. Check current AECB exam policies before your test date.

What experience is required to take the Alabama journeyman electrician exam?

Alabama typically requires completion of an approved apprenticeship program (usually 4 years / 8,000 hours) or equivalent documented experience working under a licensed electrician before you may sit for the exam.