Oklahoma Journeyman Electrician Cheat Sheet

General Knowledge

4%of exam

Permits & InspectionsStructural IntegrityEstimating & BidsContractor Liability

General Electrical Knowledge

10%of exam

Ohm's Law3-Phase PowerVoltage DropNEC NavigationTemporary Wiring

Electrical Installation Requirements

10%of exam

Working SpaceEquipment ListingTermination RatingsOver 600V Rules

Services, Feeders & Branch Circuits

10%of exam

Service DisconnectsContinuous LoadsMultiwire CircuitsFeeder Taps

Overcurrent Protection

9%of exam

Standard RatingsSmall Conductor RuleTap RulesRestricted Locations

Grounding & Bonding

10%of exam

Grounding ElectrodesGEC SizingEGC SizingBonding Jumpers

Conductors & Cables

8%of exam

THHN vs THWNCable TypesUnderground ConductorsMedium Voltage

Raceways & Boxes

7%of exam

Box FillConduit FillBend LimitsRaceway Selection

Special Occupancies & Equipment

10%of exam

Hazardous LocationsSwimming PoolsHealth CareMobile Homes

Low Voltage & Communications

2%of exam

Class 1/2/3 CircuitsFire AlarmsFiber & PVLow-Voltage Lighting

Lighting & Signs

10%of exam

Closet ClearanceDamp & Wet ZonesIC-Rated FixturesSign Disconnects

Safety

4%of exam

Fall ProtectionTrench SafetyPPE BasicsJob-Site Hazards

Motors & Transformers

6%of exam

Motor FLC SizingMotor DisconnectsTransformer ProtectionIn Sight Rule

Quick Facts

Exam
OK Unlimited Journeyman
Items
100 scored
Time
240 min
Pass
70%
Code
2023 NEC
Format
Open book
Retake
30 days
Experience
8,000 hours

Permits & Estimating

Permit puller
Licensed contractor of record
Inspection
Required before energizing work
Needs analysis
Scope before estimating a job
Estimating
Labor, material, and code compliance

NEC Article Finder

  1. Need working space depth110.26(A)(1)(Table by ground volts)
  2. Need working space width110.26(A)(2)(30 in or equipment)
  3. Need working space height110.26(A)(3)(6.5 ft headroom)
  4. Check termination temp rating110.14(C)(60C at or under 100A)
  5. Confirm equipment install rules110.3(B)(Follow the listing instructions)
  6. Need fire-rated penetration rule300.21(Firestop the opening)

Ohm's & Watt's Law

E = I x R
Volts from amps, ohms
P = E x I
Watts from volts, amps
Series R
Add all resistances
Parallel R
Lowest R gets most current
kWh Cost
kW x hours x rate
Voltage Drop
3% branch, 5% total note

AC & 3-Phase Basics

Wye (Y)
Line = phase x 1.732
Delta
Line equals phase voltage
208Y/120V
120 x 1.732 = 208
Power Factor
True power vs apparent
RMS Voltage
Effective AC value
Frequency
60 Hz U.S. standard

Listed vs Labeled

Listed

  • On a tester's published list
  • Includes follow-up inspection

Labeled

  • Physical mark on the product
  • Meets an identified standard

List entry vs physical mark

Working Space & Listing

110.26(A)(1)
Depth by ground voltage
110.26(A)(2)
Width: 30 in or equipment
110.26(A)(3)
Height: 6.5 ft minimum
110.14(C)
60C at or under 100A
110.3(B)
Follow the listing instructions
300.21
Firestop fire-rated penetrations

125% Rule

125% covers every continuous load calc

Branch conductor: 210.19OCPD: 210.20(A)Motor conductor: 430.22

Service & Feeder Finder

  1. How many service disconnects230.71(1 default, 2-6 in (B))
  2. Size a continuous load210.19 & 210.20(125% conductor and OCPD)
  3. Multiwire circuit disconnect rule210.4(B)(Simultaneous, all ungrounded conductors)
  4. Check voltage drop target210.19 & 215.2 notes(3% branch, 5% total)
  5. Feeder tap under 10 ft240.21(B)(1)(Ampacity of the load)
  6. Feeder tap under 25 ft240.21(B)(2)(One-third feeder OCPD size)

Services & Disconnects

230.71(A)
One disconnect is the default
230.71(B)
Two to six disconnects allowed
210.4(B)
Simultaneous multiwire disconnect
210.19 note
3% branch voltage drop
215.2 note
5% total voltage drop
210.19(A)
125% for continuous loads
210.20(A)
125% sizes the breaker too

10-Foot vs 25-Foot Tap

10-ft tap

  • Ampacity of the load
  • One-tenth feeder OCPD outside

25-ft tap

  • One-third feeder OCPD size
  • Ends in one breaker

Distance sets the ratio

Overcurrent Rating Finder

  1. Small copper conductor breaker cap240.4(D)(15A, 20A, 30A caps)
  2. No standard size matches240.4(B)(Next higher, 800A or less)
  3. Device rated above 800A240.4(C)(Ampacity must meet device)
  4. Where breakers are barred240.24(Bathrooms, closets, stairways)
  5. Transformer secondary protection case240.4(F)(2-wire or delta-delta 3-wire)

Overcurrent Standard Ratings

240.4(D) 14 AWG
15A max breaker
240.4(D) 12 AWG
20A max breaker
240.4(D) 10 AWG
30A max breaker
240.4(B)
Next size up, 800A or less
240.4(C)
Above 800A: match ampacity
240.6(A)
Lists standard breaker sizes
240.24
No breakers in bathrooms, closets

Feeder Tap Rules

240.21(B)(1)
10 ft tap, ampacity of load
240.21(B)(2)
25 ft tap, one-third feeder OCPD
10-ft outside enclosure
One-tenth feeder OCPD minimum
25-ft tap ending
Single breaker limits the tap

Rod, Ufer, Pool Numbers

8 ft rod, 20 ft Ufer, 4 pool points

Rod: 8 ft longUfer: 20 ft rebarPool bond: 4 points

Grounding vs Bonding

Grounding

  • Ties system to earth
  • Uses electrode conductor

Bonding

  • Joins metal parts together
  • Carries fault current back

Earth path vs equipotential

Grounding Table Finder

  1. Size grounding electrode conductorTable 250.66(By largest service conductor)
  2. Size equipment grounding conductorTable 250.122(By breaker ampere rating)
  3. Pick a grounding electrode250.52(A)(Rod, Ufer, ring, or pipe)
  4. Electrode type that is barred250.52(B)(Gas pipe or aluminum)
  5. Bond a swimming pool680.26(B)(3 ft perimeter, 4 points)

Grounding Electrodes

250.52(A)(5)
Ground rod: 8 ft, 0.625 in
250.52(A)(3)
Ufer: 20 ft rebar or copper
250.52(A)(4)
Ground ring: 20 ft, 2 AWG
250.52(A)(1)
Water pipe: 10 ft, needs supplement
250.52(B)
Gas pipe and aluminum barred

GEC vs EGC

GEC

  • Electrode to system
  • Sized from Table 250.66

EGC

  • Equipment back to source
  • Sized from Table 250.122

Different sizing tables entirely

GEC & EGC Sizing

Table 250.66
GEC sized by service conductor
Table 250.122
EGC sized by breaker rating
System bonding jumper
SDS neutral-to-ground bond
Main bonding jumper
Service panel neutral bond
Grounding vs bonding
Earth path vs equipotential

THWN vs THWN-2

THWN

  • 75C rating
  • Wet or dry rated

THWN-2

  • 90C rating
  • Wet and dry both

Dual marking wins ampacity

Conductor & Cable Types

THHN
90C, dry and damp
THWN
75C, wet locations rated
THWN-2
90C, wet and dry
UF cable
Direct burial rated
NM cable
Dry locations, no burial
AC cable
Bonding strip aids grounding path
MC cable
Separate wire-type EGC
MV cable
2,001-35,000 volts, Article 311

NM Cable vs UF Cable

NM

  • Dry locations only
  • Barred from underground burial

UF

  • Direct burial rated
  • Moisture-resistant sheath

Dry only vs burial rated

Conduit Fill Percentages

One wire 53, two wires 31, three-plus 40

1 conductor = 53%2 conductors = 31%3+ conductors = 40%

Box & Conduit Fill

14 AWG box fill
2.00 cubic inches each
12 AWG box fill
2.25 cubic inches each
10 AWG box fill
2.50 cubic inches each
1 conductor fill
53% conduit maximum
2 conductor fill
31% conduit maximum
3+ conductor fill
40% conduit maximum
Bend limit
360 degrees between pull points
PVC conduit
Needs separate wire EGC

Division 1 vs Division 2

Division 1

  • Hazard present under normal use
  • Continuous or likely exposure

Division 2

  • Hazard only if abnormal
  • Failure or rupture triggers it

Normal vs abnormal presence

Hazard & Motor Finder

  1. Flammable gas or vapor presentClass I(Spray booths, fuel areas)
  2. Combustible dust is presentClass II(Grain or flour handling)
  3. Ignitible fibers or flyingsClass III(Textile or sawmill areas)
  4. Size a motor conductor430.22(125% of table FLC)
  5. Locate a motor disconnect430.102(B)(In sight of motor)

Hazardous & Special Occupancies

Class I
Flammable gas or vapor
Class II
Combustible dust present
Class III
Ignitible fibers or flyings
Division 1
Hazard present under normal use
Division 2
Hazard only if abnormal
680.26(B)(2)
Pool perimeter: 3 ft, 4 points
517.13
Hospital: raceway plus wire EGC
550.32
Mobile home service: 30 ft
422.16(B)(5)
OK furnace cord: 9 ft

Class Circuit Article Shift

Class 1 moved to Article 724 now

Class 1 = Article 724Class 2 and 3 = 725

Low Voltage Circuits

Article 724
Class 1 power-limited circuits
Article 725
Class 2 and 3 circuits
Class 2 source
Listed transformer limits power
In sight from
Visible, 50 ft or less

Lighting & Signs Rules

410.16(C) surface
Closet surface fixture: 12 in
410.16(C) recessed
Closet recessed fixture: 6 in
410.10(D)
Bath zone: 3 ft, 8 ft
410.116(A)
Non-IC: 0.5 in from combustibles
600.6(A)
Sign disconnect: three locations allowed
410.130(G)(1)
Ballast swap needs new disconnect
410.16(B)
No open lamps or pendants

OSHA Safety Basics

1926.501(b)(1)
Fall protection at 6 ft
1926.451(g)(1)
Scaffold fall protection at 10 ft
1926.652(a)(1)
Excavation protection at 5 ft
Competent person
Inspects trenches daily
Fall arrest
Full-body harness required

Motor & Transformer Rules

430.22
Motor conductor: 125% of FLC
430.6(A)(1)
Use table FLC, not nameplate
430.102(A)
Controller disconnect in sight
240.4(F)
Primary device protects some secondaries
Table 430.250
Three-phase motor FLC values

Common Traps

Voltage To Ground vs Line

Table 110.26 uses ground volts Not line-to-line voltage

Informational Note vs Mandatory Rule

3% and 5% drop is advisory 240.4(D) caps are mandatory

Listed vs Labeled

Listed means on a list Labeled means a physical mark

Service Disconnect Count

230.71(A) default is one 230.71(B) allows two to six

Class 1 vs Class 2 and 3

Class 1 now sits in 724 Class 2/3 stays at 725

OK GFCI Amendment

Oklahoma exempts lighting and HVAC Base rule covers all outlets

Last Minute

  1. 1.Bound 2023 NEC only, no handbook
  2. 2.Continuous loads size at 125%
  3. 3.GEC size: use Table 250.66
  4. 4.EGC size: use Table 250.122
  5. 5.Ground rod: 8 ft, 0.625 in
  6. 6.Conduit fill: 3+ wires max 40%
  7. 7.Raceway bends: max 360° total
  8. 8.OSHA trenches: 5 ft needs protection
  9. 9.OSHA falls: 6 ft general trigger
  10. 10.Scaffold fall trigger: 10 ft high
  11. 11.Class 1: Article 724, not 725
  12. 12.OK allows temp cord-connected gas furnace
  13. 13.OK GFCI rule skips lighting, HVAC
  14. 14.Service disconnects: 1 default, 6 max