13.5 Micro-Renewable Energy Technologies
Key Takeaways
Unit 203 lists solar thermal, ground source and air source heat pumps, biomass, solar PV, micro-wind, micro-hydro, heat-led micro-CHP, rainwater harvesting and greywater re-use.
Solar PV produces d.c. that an inverter converts to a.c.; generators up to 16 A per phase connect under G98 (notify the DNO within 28 days of commissioning), and larger ones need prior approval under G99.
Heat pumps move heat from the air or ground using a refrigeration cycle, typically delivering 3 to 4 units of heat for each unit of electricity (the COP).
Heat-led micro-CHP generates electricity as a by-product while producing the heat the building needs.
Installation requirements include planning or permitted development, Building Regulations, BS 7671, DNO connection rules, MCS certification for export payments and grants, and location factors such as orientation, wind, head and flow.
13.5 Micro-Renewable Energy Technologies
Unit 203 learning outcome 6 (3 of the 40 test questions) asks you to describe the types of micro-renewable energy, identify the requirements for installing them (legal, regulatory and location), and identify their advantages and disadvantages. The range lists ten technologies: solar thermal (hot water), ground source heat pump, air source heat pump, biomass, solar photovoltaic, micro-wind, micro-hydro, micro-combined heat and power (heat led), rainwater harvesting and greywater re-use.
Technologies That Produce Heat
Solar thermal (hot water)
Collectors on the roof (flat-plate or evacuated-tube) absorb heat from the sun. A pump circulates a water and glycol (antifreeze) solution through a sealed loop to a coil in a twin-coil hot water cylinder. A differential temperature controller runs the pump only when the collector is hotter than the cylinder. A boiler coil or immersion heater tops up the temperature when solar input is low. The electrician supplies the pump station and controller and wires the temperature sensors.
Heat pumps (air source and ground source)
A heat pump moves heat from a low-temperature source to the building using a vapour-compression refrigeration cycle:
- Evaporator: cold refrigerant absorbs heat from the outside air or a ground loop and evaporates.
- Compressor: an electrically driven compressor raises the refrigerant's pressure and temperature.
- Condenser: the hot refrigerant gives up its heat to the heating water and condenses.
- Expansion valve: the pressure drops and the cycle repeats.
The coefficient of performance (COP) is the heat delivered divided by the electrical energy used; typical values are about 3 to 4. Heat pumps work best with low flow temperatures, such as underfloor heating or larger radiators.
- Air source (ASHP): an outdoor unit extracts heat from the air. It is cheaper to install but less efficient in very cold weather, and the unit needs careful siting for noise and airflow.
- Ground source (GSHP): pipes in horizontal trenches (needing a large area of land) or vertical boreholes extract heat from the ground, which stays at a steadier temperature.
The electrician provides a dedicated circuit sized for the unit's running and starting current, with the protective device and RCD type the manufacturer specifies, and a local isolator.
Biomass
Boilers or stoves burn wood pellets, wood chips or logs. They need space for fuel storage and access for deliveries, a suitable flue, and regular ash removal. In smoke control areas only approved (exempt) appliances may be used. Biomass is treated as low carbon because new growth reabsorbs the carbon dioxide released.
Micro-CHP (heat led)
A micro combined heat and power unit, usually gas-fired, uses a small engine, Stirling engine or fuel cell to produce heat for the building and electricity as a by-product. "Heat led" means it runs when the building needs heat, so its electrical output follows the heating demand.
Technologies That Produce Electricity
Solar photovoltaic (PV)
PV cells convert daylight directly into d.c. electricity. Panels are connected in strings, and an inverter converts the d.c. into a.c. synchronised with the supply. The installation needs d.c.-rated isolators, an a.c. isolator, a generation meter and warning labels, and must meet BS 7671 Section 712. Output depends on orientation (south-facing is best in the UK), tilt and shading. Battery storage is increasingly added; Amendment 4 introduced a new Chapter 57 for stationary secondary batteries.
Connection to the network: generators rated up to 16 A per phase connect under Engineering Recommendation G98, with the DNO notified within 28 days of commissioning. Larger systems need the DNO's approval before connection under G99.
Micro-wind
Small wind turbines on masts or buildings drive generators, usually through an inverter. They need a good average wind speed and smooth airflow; turbines on buildings in towns often perform poorly because of turbulence. Planning, noise, vibration and mast structure all need considering.
Micro-hydro
A turbine driven by flowing water generates electricity continuously where a suitable stream or river has enough head (height difference) and flow. Schemes usually need permissions such as an abstraction licence from the environmental regulator, and protection for fish and wildlife.
Technologies That Save Water
Rainwater harvesting
Rainwater from roofs is filtered into a storage tank (often underground), and a pump supplies non-drinking uses such as WC flushing, washing machines and garden taps. A mains top-up feeds the tank through an air gap so that drinking water cannot be contaminated. The electrician wires the pump and its control panel.
Greywater re-use
Lightly used water from baths, showers and basins is collected, filtered or treated, and stored for WC flushing or garden use. It must not be stored for long because bacteria can grow, and the pipework must be clearly marked. The electrician wires the pumps, treatment units and controls.
Installation Requirements
| Requirement | What to consider |
|---|---|
| Legal | Planning permission or permitted development (size, position, listed buildings and conservation areas); Building Regulations (structural loading of roofs, Part P electrical work, Part L energy efficiency, Part G for hot water systems); water regulations for rainwater and greywater systems; abstraction licences for micro-hydro; smoke control rules for biomass. |
| Regulatory | BS 7671 (for example Section 712 for PV and Chapter 57 for batteries), DNO connection under G98 or G99, manufacturers' instructions, F-gas rules for work on heat pump refrigerant circuits, and MCS (Microgeneration Certification Scheme) certification of the installer and products, which is normally needed to receive Smart Export Guarantee payments or grants such as the Boiler Upgrade Scheme. |
| Location | Orientation, tilt and shading (PV and solar thermal); roof strength and space; average wind speed and turbulence (micro-wind); head and flow (micro-hydro); land area or borehole access (GSHP); outdoor unit position and noise (ASHP); fuel storage and delivery access (biomass); space for tanks (rainwater and greywater). |
Advantages and Disadvantages
| Technology | Advantages | Disadvantages |
|---|---|---|
| Solar thermal | Free heat for hot water; low running costs; low maintenance | Needs a suitable roof and cylinder; little output in winter; needs a back-up heat source |
| Air source heat pump | High efficiency; no fuel deliveries; can also provide cooling | Less efficient in very cold weather; outdoor unit noise; may need larger radiators |
| Ground source heat pump | Very efficient with a steady source temperature; long life | High installation cost; needs land or boreholes |
| Biomass | Low net carbon; can use local fuel | Fuel storage and handling; ash and emissions; needs a flue |
| Solar PV | Free electricity; export income; silent with few moving parts | Daylight only and variable; high initial cost; inverter replacement during its life |
| Micro-wind | Can generate day and night when windy | Needs a good wind site; planning issues; noise and vibration; poor in urban turbulence |
| Micro-hydro | Continuous, reliable output | Very site-specific; permissions needed; environmental impact |
| Micro-CHP (heat led) | Uses one fuel for both heat and power efficiently | Usually still burns fossil fuel; generates only when heat is needed |
| Rainwater harvesting | Cuts mains water use and bills; reduces surface water run-off | Tank cost and space; pump energy; maintenance |
| Greywater re-use | Saves water | Needs treatment and maintenance; cannot be stored for long; hygiene risk |
Related Low-Carbon Installations
- Battery storage: stores surplus PV output for use later; installed to BS 7671 Chapter 57 (new in Amendment 4) and the manufacturer's instructions.
- EV charging points (BS 7671 Section 722): on a PME supply an outdoor charge point needs measures against a broken PEN conductor, such as an open-PEN protection device, a TT earth electrode or an isolating transformer, and the right RCD protection (for example a Type A RCD with a 6 mA d.c. detecting device, or a Type B RCD). Amendment 4 also recognises RDC protective devices for EV charging.
Which micro-renewable technology converts daylight directly into electricity?
Solar thermal
Solar photovoltaic (PV)
Ground source heat pump
Biomass boiler
What does 'heat led' mean for a micro-CHP unit?
It runs when the building needs heat, generating electricity as a by-product
It runs only when electricity prices are high, exporting all the power it generates
It produces heat only from solar collectors
It exports all its heat to the grid
A single-phase PV inverter rated at no more than 16 A per phase is connected to the public network under which procedure?
G99, with the DNO's approval required before connection
Building Regulations Part B notification
MCS planning standards only
G98, with the DNO notified within 28 days of commissioning
Which technology collects water from baths, showers and basins and reuses it for WC flushing?
Rainwater harvesting
Micro-hydro
Greywater re-use
Solar thermal
Which certification is normally required for a micro-generation installation to qualify for Smart Export Guarantee payments or a Boiler Upgrade Scheme grant?
MCS certification of the installer and products
A CSCS card held by the person who fits the panels
A PASMA certificate for the access tower used
Gas Safe registration only