8.2 AC Circuit Theory: Reactance, Impedance & Power Factor

Key Takeaways

  • In AC circuits, pure resistance exhibits current and voltage in phase (ϕ=0∘\phi = 0^\circ), pure inductance causes current to lag voltage by 90∘90^\circ with inductive reactance XL=2πfLX_L = 2\pi f L, and pure capacitance causes current to lead voltage by 90∘90^\circ with capacitive reactance XC=1/(2πfC)X_C = 1 / (2\pi f C), remembered via mnemonic CIVIL.

  • Total AC circuit opposition is called impedance (ZZ in Ω\Omega); because resistive and reactive voltages are 90∘90^\circ out of phase, impedance must be calculated using phasor addition via Pythagoras: Z=R2+(XL−XC)2Z = \sqrt{R^2 + (X_L - X_C)^2}.

  • Electrical series resonance occurs when XL=XCX_L = X_C, completely cancelling net circuit reactance (X=0X = 0), reducing impedance to pure resistance (Z=RZ = R), and producing maximum current at resonant frequency f0=1/(2πLC)f_0 = 1 / (2\pi \sqrt{LC}).

  • Apparent power (SS in VA/kVA) comprises true active power (P=VIcos⁡ϕP = V I \cos\phi in W/kW) and reactive power (Q=VIsin⁡ϕQ = V I \sin\phi in VAR/kVAR); low lagging power factors cause excessive line currents, requiring parallel capacitor bank correction.

Last updated: October 2026

AC Circuit Theory: Reactance, Impedance & Power Factor

When direct current flows through a closed circuit, the total opposition to current is governed entirely by electrical resistance (R=V/IR = V / I). However, in alternating current systems, current continually alternates in direction and magnitude. This dynamic variation activates additional electromagnetic and electrostatic properties whenever conductors are coiled into inductors or separated across insulating dielectrics as capacitors. In AC circuits, total opposition to current flow—termed impedance (ZZ)—is a composite vector quantity incorporating both pure resistance and frequency-dependent reactance.


Component Behaviour in AC Circuits

To understand composite AC circuits, an electrician must first isolate how pure resistance, pure inductance, and pure capacitance behave when energized by a sinusoidal alternating supply.

1. Pure Resistance (RR)

In a purely resistive AC circuit (such as an incandescent filament or immersion heating element):

  • The current waveform rises, peaks, and crosses zero at the exact same instant as the applied voltage waveform. Current and voltage are in phase; the phase angle is zero (ϕ=0∘\phi = 0^\circ).
  • Ohm's law applies directly using RMS values: V=I×RV = I \times R.
  • Electrical energy is converted irreversibly into thermal energy or light; no energy is stored or returned to the supply.

2. Pure Inductance (LL)

An inductor consists of a coil of wire (such as motor windings, chokes, or transformer coils). When alternating current flows through the coil, it establishes an alternating magnetic flux. By Faraday's Law and Lenz's Law, this changing flux induces a continuous counter-electromotive force (back-EMF) that opposes the change in current (e=−Ldidte = -L \frac{di}{dt}).

  • Phase Relationship: Because the back-EMF is greatest when the current is changing most rapidly (at zero crossings), the current is delayed relative to the applied voltage. In a purely inductive circuit, current lags applied voltage by exactly 90∘90^\circ (π2\frac{\pi}{2} radians, or one quarter of a cycle).
  • Inductive Reactance (XLX_L): The opposition presented by an inductor to alternating current is called inductive reactance, measured in Ohms (Ω\Omega): XL=2πfL=ωLX_L = 2\pi f L = \omega L Where:
    • XLX_L = Inductive reactance in Ohms (Ω\Omega)
    • ff = Supply frequency in Hertz (Hz\text{Hz})
    • LL = Inductance in Henrys (H\text{H})
  • Frequency Dependence: Inductive reactance is directly proportional to frequency. At DC (f=0 Hzf = 0\text{ Hz}), XL=0 ΩX_L = 0\ \Omega (the inductor acts as a short circuit, offering only winding resistance). As frequency rises, the rate of flux change increases, and XLX_L increases linearly.

3. Pure Capacitance (CC)

A capacitor consists of two conductive plates separated by an insulating dielectric medium (such as power factor correction banks or motor run capacitors). When connected to an AC supply, the plates alternately charge, discharge, charge with reverse polarity, and discharge.

  • Phase Relationship: Electric current flows onto the plates most rapidly when the applied voltage is crossing zero and changing at its highest rate (i=Cdvdti = C \frac{dv}{dt}). As the capacitor voltage reaches peak, charging current ceases. In a purely capacitive circuit, current leads applied voltage by exactly 90∘90^\circ (π2\frac{\pi}{2} radians).
  • Capacitive Reactance (XCX_C): The opposition presented by a capacitor to alternating current is called capacitive reactance, measured in Ohms (Ω\Omega): XC=12πfC=1ωCX_C = \frac{1}{2\pi f C} = \frac{1}{\omega C} Where:
    • XCX_C = Capacitive reactance in Ohms (Ω\Omega)
    • ff = Supply frequency in Hertz (Hz\text{Hz})
    • CC = Capacitance in Farads (F\text{F})
  • Frequency Dependence: Capacitive reactance is inversely proportional to frequency. At DC (f=0 Hzf = 0\text{ Hz}), XC=∞ ΩX_C = \infty\ \Omega (a capacitor completely blocks direct current). As frequency increases, the capacitor charges and discharges more frequently, allowing higher current to pass and reducing XCX_C.

The "CIVIL" Phase Mnemonic

Electricians use the standard industry mnemonic CIVIL to instantly recall phase relationships:

  • In a Capacitor, current I leads voltage V (C - I - V).
  • Voltage V leads current I in an inductive coil L (V - I - L).
PropertyPure Resistance (RR)Pure Inductance (LL)Pure Capacitance (CC)
Phase Angle (ϕ\phi)ϕ=0∘\phi = 0^\circ (In Phase)Current lags voltage by 90∘90^\circCurrent leads voltage by 90∘90^\circ
Opposition Symbol & UnitResistance, RR (Ω\Omega)Inductive Reactance, XLX_L (Ω\Omega)Capacitive Reactance, XCX_C (Ω\Omega)
Formula for OppositionR=ρL/AR = \rho L / AXL=2πfLX_L = 2\pi f LXC=1/(2πfC)X_C = 1 / (2\pi f C)
DC Response (f=0f = 0)Unchanged opposition (RR)Zero reactance (XL=0 ΩX_L = 0\ \Omega, short)Infinite reactance (XC=∞ ΩX_C = \infty\ \Omega, open)
Energy ActionDissipated as heatStored in magnetic fieldStored in electrostatic field

Series AC Circuits and Impedance (ZZ)

Practical circuits are rarely purely resistive or purely reactive. Real electrical equipment—such as motors, fluorescent luminaires, and transformers—possesses both resistance and inductance. When resistance and reactance occur in series, the total opposition to alternating current is called impedance (symbol ZZ, measured in Ohms, Ω\Omega).

Why Arithmetic Addition Fails in AC Circuits

In a series DC circuit, component voltages add arithmetically (VT=V1+V2V_T = V_1 + V_2). In an AC circuit containing resistance and reactance, arithmetic addition cannot be used because the voltages are out of phase with each other:

  • The voltage drop across the resistor (VR=IRV_R = I R) is in phase with current.
  • The voltage drop across the inductor (VL=IXLV_L = I X_L) leads current by 90∘90^\circ.
  • The voltage drop across the capacitor (VC=IXCV_C = I X_C) lags current by 90∘90^\circ.

Because VRV_R and VLV_L act at right angles (90∘90^\circ) to each other on a phasor diagram, they must be combined using Pythagoras' Theorem.

Note

If an electrician measures 120 V120\text{ V} across a resistor and 160 V160\text{ V} across an inductor in series, the total applied voltage is NOT 120+160=280 V120 + 160 = 280\text{ V}. Instead, it is the phasor sum: VT=1202+1602=14,400+25,600=40,000=200 VV_T = \sqrt{120^2 + 160^2} = \sqrt{14,400 + 25,600} = \sqrt{40,000} = 200\text{ V}.

Series R-L Circuit Formulas

  • Total Circuit Impedance: Z=R2+XL2Z = \sqrt{R^2 + X_L^2}
  • Total Supply Voltage: VT=VR2+VL2V_T = \sqrt{V_R^2 + V_L^2}
  • Circuit Current: I=VTZI = \frac{V_T}{Z}
  • Phase Angle: cos⁡ϕ=RZ=VRVT,tan⁡ϕ=XLR\cos\phi = \frac{R}{Z} = \frac{V_R}{V_T}, \qquad \tan\phi = \frac{X_L}{R}

Series R-C Circuit Formulas

  • Total Circuit Impedance: Z=R2+XC2Z = \sqrt{R^2 + X_C^2}
  • Total Supply Voltage: VT=VR2+VC2V_T = \sqrt{V_R^2 + V_C^2}
  • Phase Angle: Current leads voltage by ϕ\phi, where cos⁡ϕ=RZ\cos\phi = \frac{R}{Z}.

Series R-L-C Circuit and Electrical Resonance

When resistance, inductance, and capacitance are connected in series, the inductive and capacitive reactances point in diametrically opposite directions on the phasor diagram (180∘180^\circ apart). They directly oppose each other. The net reactance (XX) of the circuit is their arithmetic difference:

X=XL−XCX = X_L - X_C

The total impedance of a series R-L-C circuit is:

Z=R2+(XL−XC)2Z = \sqrt{R^2 + (X_L - X_C)^2}

The Condition of Electrical Series Resonance

A unique operating condition occurs when the supply frequency is adjusted until inductive reactance equals capacitive reactance:

XL=XCX_L = X_C

When this occurs:

  1. The net reactance cancels to zero: X=XL−XC=0 ΩX = X_L - X_C = 0\ \Omega.
  2. Circuit impedance collapses to its absolute minimum value, which is equal to pure resistance alone: Z=RZ = R.
  3. Circuit current reaches its absolute maximum possible value: I=VTRI = \frac{V_T}{R}.
  4. Current and voltage are completely in phase (ϕ=0∘\phi = 0^\circ, unity power factor, cos⁡ϕ=1.0\cos\phi = 1.0).

The frequency at which resonance occurs is the resonant frequency (f0f_0):

2πf0L=12πf0C  ⟹  f02=14π2LC  ⟹  f0=12πLC2\pi f_0 L = \frac{1}{2\pi f_0 C} \implies f_0^2 = \frac{1}{4\pi^2 L C} \implies f_0 = \frac{1}{2\pi\sqrt{LC}}

Warning

At series resonance, because current is limited only by resistance RR, very large currents can flow. These currents produce reactive voltage drops (VL=IXLV_L = I X_L and VC=IXCV_C = I X_C) that can be many times greater than the supply voltage itself. In industrial installations, unintended harmonic resonance can generate voltages of thousands of volts, destroying capacitor banks and puncturing cable insulation.


Power in AC Circuits: The Power Triangle

In DC circuits, electrical power is calculated simply as P=V×IP = V \times I. In AC circuits containing inductive or capacitive reactances, current and voltage are displaced by phase angle ϕ\phi. Consequently, power divides into three distinct components forming the Power Triangle:

1. True Power (PP)

Also known as active power or real power, this is the actual rate at which electrical energy is converted into useful work (mechanical rotation, light) or heat. It is dissipated exclusively in the resistive elements of the circuit.

P=V×I×cos⁡ϕ=I2RP = V \times I \times \cos\phi = I^2 R

True power is measured in Watts (W\text{W}) or kilowatts (kW\text{kW}, where 1 kW=1,000 W1\text{ kW} = 1,000\text{ W}).

2. Reactive Power (QQ)

Reactive power is the power absorbed and returned by reactive components (inductors and capacitors) as their magnetic and electrostatic fields build up and collapse each half-cycle. It performs no net useful work, but is physically necessary to sustain the alternating magnetic flux in motors and transformers.

Q=V×I×sin⁡ϕ=I2XQ = V \times I \times \sin\phi = I^2 X

Reactive power is measured in Volt-Amperes Reactive (VAR\text{VAR}) or kilovar (kVAR\text{kVAR}). By convention, inductive loads consume lagging VARs, while capacitors generate leading VARs.

3. Apparent Power (SS)

Apparent power is the total product of the RMS supply voltage and RMS supply current. It represents the total generating and cable capacity that electricity suppliers must provide to energize the installation.

S=V×I=P2+Q2=I2ZS = V \times I = \sqrt{P^2 + Q^2} = I^2 Z

Apparent power is measured in Volt-Amperes (VA\text{VA}) or kilovolt-amperes (kVA\text{kVA}). Transformers and backup generators are rated in kVA because their heating limits depend on total voltage and current, regardless of phase angle.

4. Power Factor (PF=cos⁡ϕ\text{PF} = \cos\phi)

The power factor is defined as the ratio of true active power to total apparent power:

Power Factor (PF)=True Power (P)Apparent Power (S)=RZ=cos⁡ϕ\text{Power Factor (PF)} = \frac{\text{True Power } (P)}{\text{Apparent Power } (S)} = \frac{R}{Z} = \cos\phi

Power factor is a dimensionless number between 0.00.0 and 1.01.0:

  • Unity Power Factor (1.01.0): Purely resistive load; all power is converted into useful work (P=S,Q=0P = S, Q = 0).
  • Lagging Power Factor: Occurs in inductive circuits (motors, transformers, ballasts) where current lags voltage.
  • Leading Power Factor: Occurs in capacitive circuits where current leads voltage.
Power ComponentSymbolFormulaUnitPhysical Manifestation
True / Active PowerPPV×I×cos⁡ϕV \times I \times \cos\phiWatts (W\text{W}) or kW\text{kW}Useful shaft work, heat, illumination
Reactive PowerQQV×I×sin⁡ϕV \times I \times \sin\phiVAR\text{VAR} or kVAR\text{kVAR}Sustaining magnetic/electrostatic fields
Apparent PowerSSV×IV \times IVA\text{VA} or kVA\text{kVA}Total rating of supply cables & transformers
Power Factorcos⁡ϕ\cos\phiP/SP / S or R/ZR / ZDimensionless (0.00.0 to 1.01.0)Efficiency ratio of real to total power

Practical Consequences of Low Power Factor & Power Factor Correction

Most industrial and commercial loads consist of AC induction motors, welding plant, and fluorescent lighting ballasts. These loads are heavily inductive, operating with uncorrected lagging power factors typically between 0.600.60 and 0.800.80.

Operational and Economic Penalties of Low Power Factor

To deliver a specified quantity of active power (PP) to a factory, the line current drawn from the supply is:

I=PV×cos⁡ϕI = \frac{P}{V \times \cos\phi}

If the power factor drops from 1.01.0 to 0.50.5, the line current drawn by the installation doubles to perform the exact same useful mechanical work:

  1. Increased Cable Heating and Losses: Cable power loss increases with the square of current (I2RI^2R). Doubling line current quadruples thermal distribution losses.
  2. Excessive Voltage Drop: Higher current causes larger voltage drops along distribution feeders (Vd=IZV_d = I Z), impairing terminal voltage at machines and causing luminaire flicker.
  3. Overloaded Infrastructure: Distribution transformers, switchgear, and circuit breakers must be significantly larger (higher kVA ratings) to accommodate the extra reactive current.
  4. Commercial Surcharges: Electricity supply companies (DNOs) meter both active energy (kWh) and reactive energy (kVARh). If a commercial facility operates below a prescribed threshold (typically 0.900.90 or 0.950.95 lagging), heavy financial penalties are levied on monthly bills.

Power Factor Correction (PFC)

To eliminate these penalties, electrical contractors install Power Factor Correction (PFC) capacitor banks connected in parallel across the incoming factory distribution switchboard or directly at motor terminals.

  • Because capacitors draw leading reactive current, they supply the magnetizing VARs required by the inductive motor locally.
  • The leading reactive power of the capacitor cancels the lagging reactive power of the inductor (Qnet=QL−QCQ_{\text{net}} = Q_L - Q_C).
  • The supply network is relieved of transmitting reactive power, causing total line current to fall and raising overall power factor close to unity (typically 0.950.95 to 0.980.98 lagging).

Tip

PFC capacitors must always be connected in parallel with the load, never in series. Connecting capacitors in series would alter the circuit impedance seen by the motor, choking its operating current and risking dangerous series resonance.


Step-by-Step Worked Calculations

Worked Example 1: Inductive Reactance and Capacitive Reactance

Problem: A circuit fed from a 230 V230\text{ V}, 50 Hz50\text{ Hz} supply contains a choke coil with an inductance of 0.15 H0.15\text{ H} and a capacitor with a capacitance of 68 μF68\ \mu\text{F}. Calculate the inductive reactance (XLX_L) of the choke and the capacitive reactance (XCX_C) of the capacitor.

Solution:

  1. Inductive reactance: XL=2πfL=2×π×50×0.15=314.16×0.15=47.12 ΩX_L = 2\pi f L = 2 \times \pi \times 50 \times 0.15 = 314.16 \times 0.15 = 47.12\ \Omega
  2. Capacitive reactance (convert μF\mu\text{F} to Farads: 68 μF=68×10−6 F68\ \mu\text{F} = 68 \times 10^{-6}\text{ F}): XC=12πfC=12×π×50×(68×10−6)=1314.16×6.8×10−5=10.02136=46.81 ΩX_C = \frac{1}{2\pi f C} = \frac{1}{2 \times \pi \times 50 \times (68 \times 10^{-6})} = \frac{1}{314.16 \times 6.8 \times 10^{-5}} = \frac{1}{0.02136} = 46.81\ \Omega

Worked Example 2: Series R-L Circuit Analysis

Problem: A contactor coil has an internal resistance of 30 Ω30\ \Omega and an inductive reactance of 40 Ω40\ \Omega. It is connected across a 230 V230\text{ V}, 50 Hz50\text{ Hz} AC supply. Calculate:

  1. Total circuit impedance (ZZ).
  2. Circuit current (II).
  3. Resistor voltage drop (VRV_R) and inductor voltage drop (VLV_L).
  4. Circuit power factor (cos⁡ϕ\cos\phi).
  5. True power dissipated (PP).

Solution:

  1. Total impedance: Z=R2+XL2=302+402=900+1,600=2,500=50 ΩZ = \sqrt{R^2 + X_L^2} = \sqrt{30^2 + 40^2} = \sqrt{900 + 1,600} = \sqrt{2,500} = 50\ \Omega
  2. Circuit current: I=VTZ=230 V50 Ω=4.60 AI = \frac{V_T}{Z} = \frac{230\text{ V}}{50\ \Omega} = 4.60\text{ A}
  3. Component voltages: VR=I×R=4.60 A×30 Ω=138 VV_R = I \times R = 4.60\text{ A} \times 30\ \Omega = 138\text{ V} VL=I×XL=4.60 A×40 Ω=184 VV_L = I \times X_L = 4.60\text{ A} \times 40\ \Omega = 184\text{ V} (Verification: 1382+1842=19,044+33,856=52,900=230 V\sqrt{138^2 + 184^2} = \sqrt{19,044 + 33,856} = \sqrt{52,900} = 230\text{ V})
  4. Power factor: cos⁡ϕ=RZ=3050=0.60 lagging\cos\phi = \frac{R}{Z} = \frac{30}{50} = 0.60\text{ lagging}
  5. True power: P=VT×I×cos⁡ϕ=230×4.60×0.60=634.8 WP = V_T \times I \times \cos\phi = 230 \times 4.60 \times 0.60 = 634.8\text{ W} (Alternatively: P=I2R=4.602×30=21.16×30=634.8 WP = I^2 R = 4.60^2 \times 30 = 21.16 \times 30 = 634.8\text{ W})

Worked Example 3: Power Triangle and PFC Benefits

Problem: A commercial sub-main supplies a 230 V230\text{ V} load drawing an active power of 9.2 kW9.2\text{ kW} at an uncorrected power factor of 0.640.64 lagging. Calculate the line current drawn. If parallel power factor correction capacitors improve the power factor to 0.960.96 lagging, determine the new line current and the current reduction achieved.

Solution:

  1. Uncorrected line current (I1I_1): I1=PV×cos⁡ϕ1=9,200 W230 V×0.64=9,200147.2=62.50 AI_1 = \frac{P}{V \times \cos\phi_1} = \frac{9,200\text{ W}}{230\text{ V} \times 0.64} = \frac{9,200}{147.2} = 62.50\text{ A}
  2. Corrected line current (I2I_2): I2=PV×cos⁡ϕ2=9,200 W230 V×0.96=9,200220.8=41.67 AI_2 = \frac{P}{V \times \cos\phi_2} = \frac{9,200\text{ W}}{230\text{ V} \times 0.96} = \frac{9,200}{220.8} = 41.67\text{ A}
  3. Reduction in line current: ΔI=62.50 A−41.67 A=20.83 A(33.3% reduction)\Delta I = 62.50\text{ A} - 41.67\text{ A} = 20.83\text{ A} \quad (33.3\%\text{ reduction}) This significant current reduction allows existing cables to run cooler, reduces voltage drop, and avoids DNO reactive power penalty charges.
Loading diagram...
Impedance Triangle and Power Triangle Relationships
Test Your Knowledge

What is the phase relationship between current and voltage in a purely inductive AC circuit?

A

Current and voltage are completely in phase with each other (phase angle is zero)

B

Current lags applied voltage by 90 degrees (pi/2 radians)

C

Current leads applied voltage by 90 degrees (pi/2 radians)

D

Current lags applied voltage by 180 degrees (pi radians)

Test Your Knowledge

Under what condition does electrical resonance occur in a series R-L-C circuit, and what is its effect on circuit impedance?

A

When circuit resistance falls to zero, causing the impedance to rise to an infinite value

B

When inductive reactance is exactly double the capacitive reactance, which maximises the circuit impedance

C

When the supply frequency falls to zero, causing the impedance to drop to zero

D

When inductive reactance equals capacitive reactance, so the impedance falls to its minimum, equal to R

Test Your Knowledge

Which mathematical formula correctly calculates true (active) power in a single-phase AC circuit containing resistance and inductance?

A

P = V x I x cos(phi)

B

P = V x I

C

P = V x I x sin(phi)

D

P = V x I x tan(phi)

Test Your Knowledge

What is the primary operational problem caused by operating an industrial installation with a low lagging power factor?

A

The mains supply frequency drops well below the statutory 50 Hz limit whenever large motors are running

B

Electric motors run in the reverse direction of rotation

C

Higher line currents flow in the supply conductors, causing more cable heating and greater voltage drop

D

Cable insulation resistance increases dramatically because of capacitive charging along the supply cables and distribution boards

Sections you finish are checked off in the contents.