12.2 Voltage Drop Principles & Calculations
Key Takeaways
Conductor internal electrical resistance causes a drop in electrical potential between the supply origin and the load terminals, impairing equipment performance.
BS 7671 Appendix 4 gives maximum voltage drops for installations supplied from a public low-voltage network of 3% for lighting ( at 230 V) and 5% for other uses ( at 230 V), which are deemed to satisfy Regulation 525.
Tabulated values express the millivolts dropped per ampere of load current per meter of circuit run across both line and neutral conductors.
The standard voltage drop formula is , calculated strictly using the circuit design current , NOT the protective device nominal rating .
If calculated voltage drop exceeds permitted regulatory limits, the conductor cross-sectional area must be upsized to the next standard size with a lower value.
12.2 Voltage Drop Principles & Calculations
When electric current flows through an installation cable, it encounters the internal electrical resistance of the metallic conductors. By Ohm's law (), this resistance produces an internal drop in electrical potential along the length of both the outgoing line conductor and the returning neutral conductor. As a result, the terminal voltage available at the point of utilization (such as a luminaire, electric motor, or appliance socket) is lower than the nominal supply voltage present at the origin of the consumer unit or distribution board.
Controlling voltage drop within strict regulatory limits is essential for electrical safety, energy efficiency, and equipment longevity.
Detrimental Effects of Excessive Voltage Drop
Allowing cables to operate with excessive voltage drop impairs the operational efficiency and lifespan of connected loads:
- Lighting Luminaires: In incandescent and halogen lamps, a small voltage drop causes a substantial decrease in luminous output (lumen output falls by approximately 3% for every 1% drop in voltage). In modern LED and fluorescent luminaires, under-voltage causes high-frequency driver flicker, stroboscopic effects, or complete failure to strike.
- Electric Motors: The starting and running torque developed by an induction motor is proportional to the square of the applied voltage (). Excessive voltage drop causes prolonged motor starting periods, increased stator winding currents, severe overheating, and premature tripping of thermal overloads.
- Electronic Control Gear & Computers: Microprocessor equipment, programmable logic controllers (PLCs), contactor coils, and sensitive instrumentation may malfunction, suffer data corruption, or shut down when supply potential drops below minimum tolerance thresholds.
- Heating Appliances: Thermal power output decreases as the square of the voltage (). An immersion heater or electric shower operating under severe volt drop will produce substantially less hot water, increasing energy run times.
Permitted Voltage Drop Limits under BS 7671
BS 7671 Regulation 525 and Appendix 4 set the maximum voltage drop, between the origin of the installation and any load point, that is deemed to satisfy the regulations.
For low-voltage installations supplied directly from a public distribution network (with nominal voltages of single-phase and three-phase), the maximum allowable limits are:
| Installation Circuit Classification | Permitted Percentage Drop | Permitted Voltage Drop on 230 V Supply | Permitted Voltage Drop on 400 V Supply |
|---|---|---|---|
| Lighting Circuits | 3.0% | () | () |
| Other Uses (Power, Sockets, Heating) | 5.0% | () | () |
For private high-voltage supplies (where the consumer owns the supply substation and HV/LV step-down transformer), the limits are relaxed to 6.0% for lighting () and 8.0% for other uses (). Most domestic, commercial and small industrial installations are supplied from the public network, so the 3% and 5% values are the ones you will design to.
┌──────────────────────────────────────────────────┐
│ BS 7671 Maximum Permitted Voltage Drop │
│ (Public Low-Voltage Supply) │
└─────────────────────────┬────────────────────────┘
│
┌────────────────────────────┴────────────────────────────┐
▼ ▼
Lighting Circuits (3.0%) Power Circuits (5.0%)
• 230 V single-phase: 6.9 V • 230 V single-phase: 11.5 V
• 400 V three-phase: 12.0 V • 400 V three-phase: 20.0 V
Note
In mixed circuits—such as a fused connection unit feeding a bathroom extraction fan and mirror light spur off a power radial—it is good practice to design the circuit to the stricter 3.0% () lighting limit if lighting equipment is connected.
Tabulated Millivolt per Ampere per Meter ()
To make voltage drop calculations straightforward on site, BS 7671 and the On-Site Guide publish pre-calculated millivolt drop figures known as values.
What Does Mean?
The rating defines the potential drop in millivolts that will occur across both line and neutral conductors when an electric current of 1 Ampere travels through a cable run length of 1 Meter.
Because electrical resistance is inversely proportional to conductor cross-sectional area (), larger conductors have lower resistance, resulting in smaller ratings:
| Conductor Cross-Sectional Area () | Tabulated Value ( Thermoplastic Flat Twin & Earth) |
|---|---|
| 1.0 | 44 |
| 1.5 | 29 |
| 2.5 | 18 |
| 4.0 | 11 |
| 6.0 | 7.3 |
| 10.0 | 4.4 |
| 16.0 | 2.8 |
Values from BS 7671 Table 4D5 (reproduced in the On-Site Guide) for single-phase circuits at normal conductor operating temperature.
The Voltage Drop Calculation Formula
The actual voltage drop () across any cable run is calculated using the standard formula:
Where:
- = Actual voltage drop along the circuit run in Volts (V).
- = Tabulated millivolt drop figure from BS 7671 / On-Site Guide tables for the specific cable conductor size.
- = Circuit design current in Amperes (A).
- = One-way route length of the circuit run in meters (m) (measured from the consumer unit to the furthest load terminal).
- = Mathematical divisor converting millivolts (mV) to Volts (V).
Percentage Voltage Drop
To express the calculated volt drop as a percentage of the nominal supply voltage ():
Warning
Critical Exam Pitfall: Always use the circuit design current () when calculating voltage drop, NEVER the nominal rating of the protective device (). The protective device rating () represents the trip rating during an overload; voltage drop occurs as a consequence of the actual current drawn by connected appliances during normal service (). Using instead of will produce an artificially high volt drop and cause you to oversize cables unnecessarily.
Verification & Upsizing Methodology
Once is calculated, it must be evaluated against the permitted threshold:
- If , the cable conductor cross-sectional area satisfies BS 7671 voltage drop criteria.
- If , the cable is non-compliant. The installer must upsize the conductor cross-sectional area to the next standard manufactured size with a lower value and re-run the calculation until falls within the permitted limit.
Maximum Permissible Circuit Length ()
By transposing the voltage drop formula, an electrician can determine the maximum distance a circuit can extend before exceeding the voltage drop limit:
For a 230 V single-phase power circuit with a maximum volt drop of :
Worked Calculation Examples
Example 1: Workshop Radial Power Circuit
Scenario: A dedicated 230 V single-phase radial socket-outlet circuit is being installed to feed machinery in a detached garage workshop. The circuit design current is , protected by a 20 A Type B MCB. The physical route length from the house consumer unit to the workshop socket is . The installer initially selects flat twin and earth cable ().
-
Determine Permitted Voltage Drop: For a power circuit supplied at 230 V, permitted drop is :
-
Calculate Voltage Drop for Conductor:
-
Evaluate Compliance: The cable produces a voltage drop, exceeding the limit.
-
Upsize Conductor to : From Table 4D5, a cable has .
-
Re-evaluate Compliance: The cable complies fully with BS 7671 Regulation 525.
Example 2: Commercial Office Lighting Circuit
Scenario: A 230 V commercial office LED lighting installation has a total connected design load of operating at unity power factor (). The one-way run length from the distribution board to the furthest luminaire is . The specification calls for cable (). Determine if this cable meets BS 7671 requirements.
-
Calculate Design Current ():
-
Determine Permitted Voltage Drop: For a lighting circuit on a public supply, permitted drop is :
-
Calculate Voltage Drop for Conductor:
-
Evaluate Compliance: Although it exceeds the limit by only (giving ), the design does not meet the limit and must be changed.
-
Upsize Conductor to : From Table 4D5, a cable has .
-
Re-evaluate Compliance: The cable is compliant, ensuring no luminaire flicker or premature driver failure.
Under BS 7671, what is the maximum permissible voltage drop for a 230 V single-phase domestic lighting circuit supplied directly from a low-voltage public distribution network?
11.5 V (5%)
9.2 V (4%)
6.9 V (3%)
4.6 V (2%)
When performing a voltage drop calculation using the standard formula Vd = ((mV/A/m) × I × L) / 1000, which electrical current value must be substituted for I?
The prospective short-circuit fault current (Ipfc)
The tabulated current-carrying capacity of the cable (It)
The nominal rated current of the protective device (In)
The calculated design current of the circuit load (Ib)
A 230 V single-phase radial socket circuit has a design current of 15 A and a run length of 28 m, wired in 2.5 mm² flat twin and earth cable with a tabulated value of 18 mV/A/m. What is the calculated voltage drop and is it compliant with BS 7671?
7.56 V, which is compliant because it is below the 11.5 V limit for power circuits
7.56 V, which is non-compliant because it exceeds the 6.9 V limit for power circuits
12.60 V, which is non-compliant because it exceeds the 11.5 V limit for power circuits
4.20 V, which is compliant because it is below the 6.9 V limit for power circuits
If a calculated circuit voltage drop exceeds the maximum permitted regulatory limit, what is the standard engineering corrective action required?
Replace the circuit breaker with a higher nominal current rating to boost supply potential
Increase the cable conductor cross-sectional area to the next standard size with a lower mV/A/m value
Install a power factor correction capacitor at the origin of the consumer unit
Shorten the circuit by removing the circuit protective conductor (CPC) to decrease resistance