5.2 SI Units of Measurement in Electrotechnology
Key Takeaways
The International System of Units (SI) establishes four primary base units used in electrotechnology: meter (m) for length, kilogram (kg) for mass, second (s) for time, and ampere (A) for electric current.
Derived electrotechnical units are formed from combinations of base units: the Volt (), the Ohm (), the Coulomb (), and the Watt ().
Magnetic and alternating current parameters have dedicated derived units: magnetic flux in Webers (Wb), magnetic flux density in Teslas (), inductance in Henrys (H), capacitance in Farads (F), and frequency in Hertz ().
SI prefixes scale base and derived units in powers of ten; engineering calculations primarily utilize multiples of three: Mega (), Kilo (), Milli (), Micro (), Nano (), and Pico ().
Converting conductor cross-sectional area from square millimeters () to square meters () requires multiplying by because area scales with the square of the linear conversion factor ().
5.2 SI Units of Measurement in Electrotechnology
In electrotechnical engineering, accurate communication and calculation depend on the International System of Units (Système International d'Unités, abbreviated SI). Standardized units ensure that electrical quantities measured on site—such as loop impedance, insulation resistance, voltage drop, and luminous flux—can be directly verified against the criteria published in BS 7671 (IET Wiring Regulations).
SI Base Units in Electrotechnology
The SI system is constructed upon seven fundamental base units, four of which form the bedrock of electrical and mechanical calculations:
- Length — Meter (): The fundamental unit of distance, cable runs, and physical dimensions.
- Mass — Kilogram (): The fundamental measure of the quantity of matter in an object, used to calculate gravitational weight and mechanical force.
- Time — Second (): The fundamental unit of time duration, used in defining frequency, current rate, velocity, and power.
- Electric Current — Ampere (): The fundamental electrical base unit, formally defined in terms of elementary charge flow ( electrons passing a cross-section per second).
Note
In the SI system, the Ampere (A) is the base unit, not the Coulomb (C). The Coulomb is a derived unit defined as the quantity of electric charge transported by a constant current of one ampere in one second ().
Derived Electrotechnical Units
All electrical and magnetic units other than the Ampere are derived units, constructed by combining the base units of mass, length, time, and electric current.
| Quantity | Symbol | Unit Name | Unit Abbr. | Base SI / Physical Definition | Electrical Relationship |
|---|---|---|---|---|---|
| Potential Difference / EMF | or | Volt | Energy transferred per unit electric charge | ||
| Electrical Resistance | Ohm | Opposition to the flow of electric current | |||
| Electric Charge | Coulomb | Charge transferred by in () | |||
| Electrical Power | Watt | Rate of doing work or transferring electrical energy | |||
| Energy / Work | or | Joule | Work done when a force of moves through | ||
| Frequency | Hertz | Number of complete alternating cycles per second | |||
| Magnetic Flux | Weber | Total quantity of magnetic field lines produced | |||
| Magnetic Flux Density | Tesla | Magnetic flux passing per unit perpendicular area | |||
| Capacitance | Farad | Charge stored per unit potential difference | |||
| Inductance | Henry | Induced EMF of when current changes at |
In-Depth Unit Analysis
- The Volt (): A potential difference of one volt exists between two points if one joule of energy is released or absorbed in moving one coulomb of charge between those points (). It also represents the potential difference that drives one ampere of current through a resistance of one ohm ().
- The Ohm (): Named after Georg Simon Ohm, one ohm is the electrical resistance between two points of a conductor when a constant potential difference of one volt applied between these points produces a current of one ampere ().
- The Watt (): Named after James Watt, one watt represents one joule of energy transferred per second (). In direct current circuits, one watt is produced when a current of one ampere flows under a pressure of one volt ().
- The Joule () and the Kilowatt-Hour (): While the Joule is the coherent SI unit of energy, commercial electricity metering uses the kilowatt-hour (), commonly called a "Unit" of electricity:
SI Prefixes and Scaling Multipliers
Metric prefixes are attached to base and derived units to represent very large or very small quantities. In electrotechnology, prefixes generally scale in steps of (thousands):
| Prefix Name | Symbol | Mathematical Factor | Power of 10 | Electrotechnical Practical Example |
|---|---|---|---|---|
| Giga | National grid generation capacity: | |||
| Mega | Insulation resistance test minimum: | |||
| Kilo | Substation line voltage: ; Fault level: | |||
| (Unit) | — | Supply voltage: ; Current: | ||
| Milli | RCD trip sensitivity: ; Millivolts: | |||
| Micro | Power factor correction capacitor: | |||
| Nano | High-frequency cable capacitance: | |||
| Pico | Radio frequency filter capacitor: |
Tip
When converting from a smaller prefix to a larger prefix (e.g., to ), divide by the factor (or multiply by ). When converting from a larger prefix to a smaller prefix (e.g., to ), multiply by the factor (or multiply by ).
Step-by-Step Unit Conversion Worked Examples
Example 1: Current and Resistance Conversions
- Convert a leakage current of to Amperes ():
- Convert an insulation resistance reading of to Ohms ():
- Convert a prospective fault current of to Amperes ():
Example 2: Cable Cross-Sectional Area ( to )
This conversion is a critical step in conductor resistance calculations using . Resistivity is given in ohm-meters (), and length is in meters (). Consequently, the cross-sectional area must be expressed in square meters (), not square millimeters ().
Because : Therefore, to convert from to , you must divide by (multiply by ):
- For a conductor:
- For a sub-main conductor:
Warning
Never multiply by to convert to . A factor of converts linear millimeters to linear meters (). Area requires squaring the linear factor: . Using will cause calculated cable resistance to be incorrect by a factor of .
Example 3: Period to Frequency Conversion
An alternating waveform displays a single cycle periodic time of . Calculate the supply frequency ():
- Convert periodic time to seconds: .
- Use the frequency formula : This confirms the standard UK mains electrical supply frequency.
Other SI Quantities in Unit 202
The Unit 202 range also covers the SI units for everyday physical quantities and for the a.c. quantities you meet later:
| Quantity | SI unit | Symbol | Notes |
|---|---|---|---|
| Area | square metre | m² | Cable cross-sections are quoted in mm² () |
| Volume | cubic metre | m³ | litres, so a 150-litre cylinder holds |
| Density | kilogram per cubic metre | kg/m³ | Mass divided by volume; copper is about 8,900 kg/m³ and aluminium about 2,700 kg/m³ |
| Velocity | metre per second | m/s | Distance divided by time in a stated direction |
| Temperature | kelvin | K | Practical work uses degrees Celsius; a temperature difference of 1 K equals 1°C, and 0°C is about 273 K |
| Impedance | ohm | Ω | The total opposition to alternating current () |
| Inductive reactance | ohm | Ω | , where inductance is in henrys (H) |
| Capacitive reactance | ohm | Ω | , where capacitance is in farads (F) |
| Power factor | no unit | none | A ratio between 0 and 1 () |
Instruments for Measuring Electrical Quantities
Unit 202 LO2 also asks you to identify the right instrument for each electrical quantity:
| Quantity | Instrument | How it is connected |
|---|---|---|
| Current | Ammeter (or clamp meter) | In series with the load so that all the current passes through it; an ammeter has a very low resistance. A clamp meter measures current without breaking the circuit by clamping around a single conductor. |
| Voltage | Voltmeter | In parallel (across) the component or supply; a voltmeter has a very high resistance so it draws almost no current. |
| Resistance | Ohmmeter (or a multimeter's resistance range; a low-resistance ohmmeter for continuity tests) | Across the component with the circuit isolated and dead, because the meter drives its own test current from a battery. |
| Power | Wattmeter | Current coil in series and voltage coil in parallel with the load. |
| Energy | Energy (kWh) meter | Installed at the supply intake, recording the kilowatt-hours used. |
A multimeter combines several of these functions, but remember the rule from Section 3.1: never use a multimeter to prove an installation dead.
Tip
Series measures current (ammeter); parallel measures voltage (voltmeter). Connecting an ammeter in parallel across a supply creates a near short circuit and can blow the meter's fuse or damage it.
Measurement Tolerances and Instrument Scales
When using test equipment (such as multifunction installation testers complying with BS EN 61557), readings must be interpreted with an understanding of measurement resolution and scale tolerance.
- Analogue Meter Scales: Feature a physical pointer moving over a graduated arc. Reading analogue scales requires avoiding parallax error (viewing the needle from an angle). Quality analogue instruments incorporate an anti-parallax mirrored scale strip behind the needle; the user aligns their line of sight so the needle directly obscures its own reflection.
- Digital Meter Resolution: Displays numerical values on an LCD/OLED screen. A meter reading on a resolution scale has an inherent quantization uncertainty of least significant digit.
- Instrument Accuracy Tolerance: Typically expressed as . For instance, an instrument rated at displaying has an allowable variance of , meaning the actual voltage lies between and .
Which of the following correctly defines the derived electrotechnical unit 'Volt' in terms of fundamental mechanical and electrical work?
One Watt of power expended over a distance of one meter
One Ampere of current flowing through a force of one Newton
One Coulomb of charge stored across a magnetic flux of one Weber
One Joule of electrical energy transferred per Coulomb of charge
In a calculation to determine conductor resistance using R = (ρ × L) / A, the cross-sectional area of a cable is specified as 4.0 mm². What numerical value must be entered into the equation for area (A) in square meters?
4.0 × 10⁻³ m²
4.0 × 10⁻⁶ m²
4.0 × 10⁻⁹ m²
4.0 × 10⁻² m²
What is the SI unit of magnetic flux density, and what is its equivalent physical definition?
Weber (Wb), defined as one Volt-second per meter
Henry (H), defined as one Ohm per second
Tesla (T), defined as one Weber per square meter (Wb/m²)
Coulomb (C), defined as one Ampere per second
How should an ammeter be connected to measure the current taken by an immersion heater?
In parallel across the heater terminals, so it sees the full supply voltage
In series with the heater, so the load current flows through the meter
Between the line conductor and earth
Across the supply with the heater disconnected