13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs
Key Takeaways
Automatic Disconnection of Supply (ADS) under BS 7671 Section 411 is the primary measure for shock protection, combining Basic Protection (insulation, enclosures ) and Fault Protection (earthing, bonding, automatic disconnection).
Maximum permitted disconnection times under Table 41.1 for nominal 230 V final circuits are 0.4 seconds for TN systems and 0.2 seconds for TT systems.
The total earth fault loop impedance of a circuit is calculated using the fundamental equation , which dictates the prospective fault current under Ohm's law: .
To achieve disconnection within 0.4 s, fault current must reach the instantaneous magnetic trip threshold of the circuit breaker ( for Type B MCBs, for Type C, for Type D).
When performing testing at ambient temperature (), the measured must not exceed 80% (the 0.8 correction factor) of the maximum tabulated in BS 7671 to account for increased conductor resistance when cables reach full operating temperature under load.
13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs
In electrical installation design, Automatic Disconnection of Supply (ADS) is the primary and most widely applied protective measure against electric shock. Defined in BS 7671 Section 411, ADS operates on a fundamental electrical engineering principle: whenever an insulation breakdown occurs between a line conductor and an exposed-conductive-part, the resulting earth fault current must be sufficiently high to trigger a protective device (circuit breaker, RCBO, or fuse) to disconnect the supply automatically before ventricular fibrillation or death can occur.
The Dual Requirements of ADS: Basic Protection & Fault Protection
Under BS 7671 Regulation 411.1, the protective measure ADS requires the coordinated provision of two distinct layers of defense:
AUTOMATIC DISCONNECTION OF SUPPLY (ADS)
(Section 411)
┌─────────────────┴─────────────────┐
▼ ▼
BASIC PROTECTION FAULT PROTECTION
(Protection under Normal Conditions) (Protection under Single-Fault Conditions)
• Basic Insulation of live parts • Protective Earthing (CPCs & MET)
• Barriers & Enclosures: • Protective Equipotential Bonding
- IP2X / IPXXB general • Automatic Disconnection:
- IP4X / IPXXD top surfaces - TN systems: 0.4 s (≤32A)
- TT systems: 0.2 s (≤32A)
1. Basic Protection (Protection Against Direct Contact)
Basic protection prevents humans and livestock from coming into direct physical contact with live electrical conductors under normal, healthy operating conditions. It is achieved through:
- Basic Insulation: Non-conductive insulation surrounding live copper conductors (e.g. polyvinyl chloride PVC or cross-linked polyethylene XLPE), capable of withstanding the electrical, thermal, and mechanical stresses of normal operation.
- Barriers and Enclosures: Protective enclosures housing live electrical terminations (e.g. consumer units, junction boxes, switch plates). Under BS 7671 Section 416, accessible outer surfaces of enclosures must provide a minimum degree of ingress protection of IP2X or IPXXB (preventing entry of fingers or objects diameter). Furthermore, readily accessible horizontal top surfaces of enclosures (such as the top lid of a consumer unit or distribution board) must achieve at least IP4X or IPXXD (preventing ingress of small wires or tools diameter).
2. Fault Protection (Protection Against Indirect Contact)
Fault protection prevents danger if basic insulation fails, causing exposed metalwork to become energized. Fault protection requires:
- Protective Earthing: Interconnecting all exposed-conductive-parts via Circuit Protective Conductors (CPCs) to the Main Earthing Terminal (MET).
- Protective Equipotential Bonding: Linking extraneous services (water, gas, steel) to eliminate touch voltages.
- Automatic Disconnection: A circuit breaker, fuse, or residual current device that disconnects the line conductor within a strictly mandated time limit.
Maximum Permitted Disconnection Times (BS 7671 Table 41.1)
Human physiological tolerance to electric shock is inversely proportional to duration. A shock voltage of sustained for several seconds is lethal, whereas disconnection within fractions of a second prevents fatal heart fibrillation. BS 7671 Table 41.1 specifies maximum permitted disconnection times for circuits operating at nominal AC voltage to earth:
| System Earthing Arrangement | Final Circuits Not Exceeding | Distribution Circuits & Final Circuits Exceeding |
|---|---|---|
| TN Systems (TN-S, TN-C-S) | ||
| TT Systems |
Why TT Systems Demand Faster Disconnection ( vs )
A classic City & Guilds examination concept is understanding why TT systems require a faster disconnection time () than TN systems ():
- In a TN system, the earth fault return path is formed by a low-resistance metallic conductor (cable sheath or PEN conductor). During an earth fault, the impedance of the line conductor () and the CPC () are roughly comparable. Consequently, the supply voltage () divides approximately equally across the loop, so the touch voltage () appearing on exposed metalwork is approximately .
- In a TT system, the earth return path passes through the consumer's earth electrode () and the surrounding soil. The electrode resistance ( to ) dwarfs the sub-ohm resistance of the internal copper circuit cables. Under Ohm's voltage divider law, virtually the entire supply voltage appears across the exposed appliance casing as touch voltage.
- Because a touch voltage of triggers ventricular fibrillation far more rapidly than , the disconnection time on TT systems is halved to to ensure life safety.
The Earth Fault Loop Impedance Path ()
The earth fault loop is the complete, closed conductive circuit traversed by fault current when a line-to-earth breakdown occurs at an electrical accessory or appliance.
The Fundamental Formula
Total earth fault loop impedance () is calculated using the fundamental equation:
Where:
- (Total Earth Fault Loop Impedance): The total impedance of the fault path in ohms () measured at the furthest, most vulnerable point of the circuit.
- (External Earth Fault Loop Impedance): The impedance of the supply network outside the installation origin in ohms (), comprising the substation transformer secondary winding, the incoming DNO phase conductor, and the external earth return path (lead cable sheath in TN-S, PEN conductor in TN-C-S, or mass of earth in TT).
- : The resistance of the line conductor from the distribution board to the furthest point of the circuit ().
- : The resistance of the circuit protective conductor (CPC) from the distribution board to the furthest point ().
- : The combined internal circuit loop resistance ().
Calculating Earth Fault Current ()
By Ohm's Law, the prospective earth fault current () flowing through the loop during a fault is determined by: Where is the nominal line-to-earth AC voltage ().
For an overcurrent device (such as an MCB or RCBO) to disconnect within , the fault current must be large enough to activate the circuit breaker's instantaneous electromagnetic trip mechanism:
- Type B MCB (BS EN 60898): Instantaneous magnetic tripping occurs between and . To guarantee tripping within to , the current must reach .
- Type C MCB (BS EN 60898): Instantaneous magnetic tripping occurs between and . Tripping requires .
- Type D MCB (BS EN 60898): Instantaneous magnetic tripping occurs between and . Tripping requires .
Maximum Tabulated Values (BS 7671 Table 41.3)
Under BS 7671, the maximum permitted earth fault loop impedance for a circuit breaker is derived from the formula: Where:
- .
- is the minimum voltage factor BS 7671 uses to allow for variation in the supply voltage ().
- is the current causing automatic operation of the protective device within specified time ( for Type B, for Type C).
Example: Deriving Maximum for a 32 A Type B MCB
BS 7671 Table 41.3 Maximum for Type B Circuit Breakers at 0.4 s
| Device Rating () | Instantaneous Trip Current () | Maximum Tabulated (BS 7671 Table 41.3) | Rule-of-Thumb Max Measured () |
|---|---|---|---|
| 6 A | |||
| 10 A | |||
| 16 A | |||
| 20 A | |||
| 32 A | |||
| 40 A | |||
| 50 A |
Note
For a Type C MCB, because (double the current of Type B), the maximum permitted is exactly half that of a Type B device. For example, a Type C MCB has a maximum tabulated . A Type D device () has a maximum tabulated of just .
The 0.8 Rule-of-Thumb Temperature Correction Factor
A critical practical and examination requirement is applying the 0.8 temperature correction factor (a rule of thumb given in IET guidance such as the On-Site Guide and Guidance Note 3).
The Engineering Rationale
- The maximum values published in BS 7671 Table 41.3 are calculated assuming that circuit conductors are operating at their maximum permitted conductor operating temperature—which is for standard thermoplastic (PVC) insulated cables, or for thermosetting (XLPE) cables.
- However, when an electrician conducts initial verification or periodic inspection on site, the installation is unenergized or lightly loaded, meaning the conductors are cold at ambient room temperature (standardized as ).
- Because copper has a positive temperature coefficient of resistance (), a cold copper conductor has significantly lower resistance than a hot conductor operating at under full load.
- If a measured reading taken at is barely below the tabulated maximum value, once the circuit is loaded to its full capacity and warms up to , the conductor resistance will rise, causing the true operating to exceed the permitted limit and preventing disconnection within !
Applying the Rule-of-Thumb Formula
To ensure compliance when testing at ambient temperatures, the measured earth fault loop impedance must not exceed () of the tabulated value in BS 7671:
Worked Example
A ring final circuit wired in cable is protected by a Type B MCB to BS EN 60898. During commissioning testing at :
- Measured external loop impedance: .
- Measured circuit loop resistance: .
- Total measured earth loop impedance: .
Compliance Check:
- From BS 7671 Table 41.3, maximum tabulated for a Type B MCB = .
- Apply the 0.8 rule-of-thumb temperature correction factor:
- Compare measured value against the 0.8 limit:
Tip
If a measured reading sits between the 0.8 value and the tabulated value (for instance, on a 32 A Type B circuit), the circuit fails the simple rule-of-thumb test. In this case, the inspector must carry out the full temperature correction calculation described in IET Guidance Note 3 () to determine whether the circuit complies.
Warning
Never record a circuit as compliant simply because the measured is less than the tabulated value in Table 41.3 without applying the 0.8 temperature correction factor. Failing to account for thermal resistance rise can lead to lethal shock conditions where protective devices fail to operate within the statutory 0.4-second window.
Under BS 7671 Table 41.1, what is the maximum permitted disconnection time for a 230 V final circuit rated at 32 A or below in a TN earthing system?
5.0 seconds
1.0 second
0.2 seconds
0.4 seconds
In the fundamental earth fault loop impedance equation Zs = Ze + (R1 + R2), what does the term (R1 + R2) represent?
The combined resistance of the internal circuit line conductor (R1) and the circuit protective conductor (R2) from the distribution board to the furthest point
The total external loop impedance of the DNO service cable from the local substation transformer to the cut-out
The contact resistance of the independent consumer earth rod to the general mass of earth
The sum of the nominal operating breaking capacity of the main switch and the cut-out cartridge fuse
Why must a measured value of earth fault loop impedance taken at ambient room temperature (20 °C) be compared against 80% (the 0.8 correction factor) of the maximum tabulated Zs in BS 7671?
Because digital test instruments have a built-in calibration tolerance error of exactly 20%
Because conductor resistance increases as cables warm up to their maximum 70 °C operating temperature under full load
Because supply voltages on the National Grid fluctuate by up to 20% under peak winter demand
Because BS 7671 mandates a 20% safety margin to prevent nuisance tripping of 30 mA residual current devices
A domestic ring final circuit is protected by a 32 A Type B MCB complying with BS EN 60898. According to BS 7671 Table 41.3, the maximum tabulated Zs is 1.37 Ω. What is the maximum acceptable measured Zs during testing at ambient temperature using the standard 0.8 rule-of-thumb?
1.37 Ω
0.68 Ω
1.10 Ω
0.35 Ω