13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs

Key Takeaways

  • Automatic Disconnection of Supply (ADS) under BS 7671 Section 411 is the primary measure for shock protection, combining Basic Protection (insulation, enclosures ≥IP2X\ge \text{IP2X}) and Fault Protection (earthing, bonding, automatic disconnection).

  • Maximum permitted disconnection times under Table 41.1 for nominal 230 V final circuits ≤32 A\le 32\text{ A} are 0.4 seconds for TN systems and 0.2 seconds for TT systems.

  • The total earth fault loop impedance of a circuit is calculated using the fundamental equation Zs=Ze+(R1+R2)Z_s = Z_e + (R_1 + R_2), which dictates the prospective fault current under Ohm's law: If=U0/ZsI_f = U_0 / Z_s.

  • To achieve disconnection within 0.4 s, fault current IfI_f must reach the instantaneous magnetic trip threshold of the circuit breaker (5×In5 \times I_n for Type B MCBs, 10×In10 \times I_n for Type C, 20×In20 \times I_n for Type D).

  • When performing testing at ambient temperature (20∘C20^\circ\text{C}), the measured ZsZ_s must not exceed 80% (the 0.8 correction factor) of the maximum tabulated ZsZ_s in BS 7671 to account for increased conductor resistance when cables reach full 70∘C70^\circ\text{C} operating temperature under load.

Last updated: October 2026

13.4 Automatic Disconnection of Supply (ADS) & Maximum Zs

In electrical installation design, Automatic Disconnection of Supply (ADS) is the primary and most widely applied protective measure against electric shock. Defined in BS 7671 Section 411, ADS operates on a fundamental electrical engineering principle: whenever an insulation breakdown occurs between a line conductor and an exposed-conductive-part, the resulting earth fault current must be sufficiently high to trigger a protective device (circuit breaker, RCBO, or fuse) to disconnect the supply automatically before ventricular fibrillation or death can occur.


The Dual Requirements of ADS: Basic Protection & Fault Protection

Under BS 7671 Regulation 411.1, the protective measure ADS requires the coordinated provision of two distinct layers of defense:

                    AUTOMATIC DISCONNECTION OF SUPPLY (ADS)
                               (Section 411)
                    ┌─────────────────┴─────────────────┐
                    ▼                                   ▼
             BASIC PROTECTION                    FAULT PROTECTION
      (Protection under Normal Conditions) (Protection under Single-Fault Conditions)
      • Basic Insulation of live parts     • Protective Earthing (CPCs & MET)
      • Barriers & Enclosures:             • Protective Equipotential Bonding
        - IP2X / IPXXB general             • Automatic Disconnection:
        - IP4X / IPXXD top surfaces          - TN systems: 0.4 s (≤32A)
                                             - TT systems: 0.2 s (≤32A)

1. Basic Protection (Protection Against Direct Contact)

Basic protection prevents humans and livestock from coming into direct physical contact with live electrical conductors under normal, healthy operating conditions. It is achieved through:

  • Basic Insulation: Non-conductive insulation surrounding live copper conductors (e.g. polyvinyl chloride PVC or cross-linked polyethylene XLPE), capable of withstanding the electrical, thermal, and mechanical stresses of normal operation.
  • Barriers and Enclosures: Protective enclosures housing live electrical terminations (e.g. consumer units, junction boxes, switch plates). Under BS 7671 Section 416, accessible outer surfaces of enclosures must provide a minimum degree of ingress protection of IP2X or IPXXB (preventing entry of fingers or objects >12 mm>12\text{ mm} diameter). Furthermore, readily accessible horizontal top surfaces of enclosures (such as the top lid of a consumer unit or distribution board) must achieve at least IP4X or IPXXD (preventing ingress of small wires or tools >1.0 mm>1.0\text{ mm} diameter).

2. Fault Protection (Protection Against Indirect Contact)

Fault protection prevents danger if basic insulation fails, causing exposed metalwork to become energized. Fault protection requires:

  • Protective Earthing: Interconnecting all exposed-conductive-parts via Circuit Protective Conductors (CPCs) to the Main Earthing Terminal (MET).
  • Protective Equipotential Bonding: Linking extraneous services (water, gas, steel) to eliminate touch voltages.
  • Automatic Disconnection: A circuit breaker, fuse, or residual current device that disconnects the line conductor within a strictly mandated time limit.

Maximum Permitted Disconnection Times (BS 7671 Table 41.1)

Human physiological tolerance to electric shock is inversely proportional to duration. A shock voltage of 230 V230\text{ V} sustained for several seconds is lethal, whereas disconnection within fractions of a second prevents fatal heart fibrillation. BS 7671 Table 41.1 specifies maximum permitted disconnection times for circuits operating at nominal AC voltage U0=230 VU_0 = 230\text{ V} to earth:

System Earthing ArrangementFinal Circuits Not Exceeding 32 A32\text{ A}Distribution Circuits & Final Circuits Exceeding 32 A32\text{ A}
TN Systems (TN-S, TN-C-S)0.4 seconds0.4\text{ seconds}5.0 seconds5.0\text{ seconds}
TT Systems0.2 seconds0.2\text{ seconds}1.0 second1.0\text{ second}

Why TT Systems Demand Faster Disconnection (0.2 s0.2\text{ s} vs 0.4 s0.4\text{ s})

A classic City & Guilds examination concept is understanding why TT systems require a faster disconnection time (0.2 s0.2\text{ s}) than TN systems (0.4 s0.4\text{ s}):

  • In a TN system, the earth fault return path is formed by a low-resistance metallic conductor (cable sheath or PEN conductor). During an earth fault, the impedance of the line conductor (R1R_1) and the CPC (R2R_2) are roughly comparable. Consequently, the supply voltage (230 V230\text{ V}) divides approximately equally across the loop, so the touch voltage (VtV_t) appearing on exposed metalwork is approximately 115 V115\text{ V}.
  • In a TT system, the earth return path passes through the consumer's earth electrode (RAR_A) and the surrounding soil. The electrode resistance (21 Ω21\ \Omega to 100+ Ω100+\ \Omega) dwarfs the sub-ohm resistance of the internal copper circuit cables. Under Ohm's voltage divider law, virtually the entire 230 V230\text{ V} supply voltage appears across the exposed appliance casing as touch voltage.
  • Because a touch voltage of 230 V230\text{ V} triggers ventricular fibrillation far more rapidly than 115 V115\text{ V}, the disconnection time on TT systems is halved to 0.2 seconds0.2\text{ seconds} to ensure life safety.
Loading diagram...
The Complete Earth Fault Loop Impedance Path (Zs = Ze + R1 + R2)

The Earth Fault Loop Impedance Path (ZsZ_s)

The earth fault loop is the complete, closed conductive circuit traversed by fault current when a line-to-earth breakdown occurs at an electrical accessory or appliance.

The Fundamental ZsZ_s Formula

Total earth fault loop impedance (ZsZ_s) is calculated using the fundamental equation: Zs=Ze+(R1+R2)Z_s = Z_e + (R_1 + R_2)

Where:

  • ZsZ_s (Total Earth Fault Loop Impedance): The total impedance of the fault path in ohms (Ω\Omega) measured at the furthest, most vulnerable point of the circuit.
  • ZeZ_e (External Earth Fault Loop Impedance): The impedance of the supply network outside the installation origin in ohms (Ω\Omega), comprising the substation transformer secondary winding, the incoming DNO phase conductor, and the external earth return path (lead cable sheath in TN-S, PEN conductor in TN-C-S, or mass of earth in TT).
  • R1R_1: The resistance of the line conductor from the distribution board to the furthest point of the circuit (Ω\Omega).
  • R2R_2: The resistance of the circuit protective conductor (CPC) from the distribution board to the furthest point (Ω\Omega).
  • (R1+R2)(R_1 + R_2): The combined internal circuit loop resistance (Ω\Omega).

Calculating Earth Fault Current (IfI_f)

By Ohm's Law, the prospective earth fault current (IfI_f) flowing through the loop during a fault is determined by: If=U0ZsI_f = \frac{U_0}{Z_s} Where U0U_0 is the nominal line-to-earth AC voltage (230 V230\text{ V}).

For an overcurrent device (such as an MCB or RCBO) to disconnect within 0.4 seconds0.4\text{ seconds}, the fault current IfI_f must be large enough to activate the circuit breaker's instantaneous electromagnetic trip mechanism:

  • Type B MCB (BS EN 60898): Instantaneous magnetic tripping occurs between 3×In3 \times I_n and 5×In5 \times I_n. To guarantee tripping within 0.1 s0.1\text{ s} to 0.4 s0.4\text{ s}, the current must reach Ia=5×InI_a = 5 \times I_n.
  • Type C MCB (BS EN 60898): Instantaneous magnetic tripping occurs between 5×In5 \times I_n and 10×In10 \times I_n. Tripping requires Ia=10×InI_a = 10 \times I_n.
  • Type D MCB (BS EN 60898): Instantaneous magnetic tripping occurs between 10×In10 \times I_n and 20×In20 \times I_n. Tripping requires Ia=20×InI_a = 20 \times I_n.

Maximum Tabulated ZsZ_s Values (BS 7671 Table 41.3)

Under BS 7671, the maximum permitted earth fault loop impedance for a circuit breaker is derived from the formula: Zs≤U0×CminIaZ_s \le \frac{U_0 \times C_{\text{min}}}{I_a} Where:

  • U0=230 VU_0 = 230\text{ V}.
  • Cmin=0.95C_{\text{min}} = 0.95 is the minimum voltage factor BS 7671 uses to allow for variation in the supply voltage (230 V×0.95=218.5 V230\text{ V} \times 0.95 = 218.5\text{ V}).
  • IaI_a is the current causing automatic operation of the protective device within specified time (5×In5 \times I_n for Type B, 10×In10 \times I_n for Type C).

Example: Deriving Maximum ZsZ_s for a 32 A Type B MCB

Ia=5×32 A=160 AI_a = 5 \times 32\text{ A} = 160\text{ A} Zs≤230 V×0.95160 A=218.5 V160 A=1.3656 Ω≈1.37 ΩZ_s \le \frac{230\text{ V} \times 0.95}{160\text{ A}} = \frac{218.5\text{ V}}{160\text{ A}} = \mathbf{1.3656\ \Omega \approx 1.37\ \Omega}

BS 7671 Table 41.3 Maximum ZsZ_s for Type B Circuit Breakers at 0.4 s

Device Rating (InI_n)Instantaneous Trip Current (Ia=5InI_a = 5 I_n)Maximum Tabulated ZsZ_s (BS 7671 Table 41.3)Rule-of-Thumb Max Measured ZsZ_s (0.8×Zs0.8 \times Z_s)
6 A30 A30\text{ A}7.28 Ω7.28\ \Omega5.82 Ω5.82\ \Omega
10 A50 A50\text{ A}4.37 Ω4.37\ \Omega3.50 Ω3.50\ \Omega
16 A80 A80\text{ A}2.73 Ω2.73\ \Omega2.18 Ω2.18\ \Omega
20 A100 A100\text{ A}2.19 Ω2.19\ \Omega1.75 Ω1.75\ \Omega
32 A160 A160\text{ A}1.37 Ω1.37\ \Omega1.10 Ω1.10\ \Omega
40 A200 A200\text{ A}1.09 Ω1.09\ \Omega0.87 Ω0.87\ \Omega
50 A250 A250\text{ A}0.87 Ω0.87\ \Omega0.70 Ω0.70\ \Omega

Note

For a Type C MCB, because Ia=10×InI_a = 10 \times I_n (double the current of Type B), the maximum permitted ZsZ_s is exactly half that of a Type B device. For example, a 32 A32\text{ A} Type C MCB has a maximum tabulated Zs=1.37/2=0.68 ΩZ_s = 1.37 / 2 = \mathbf{0.68\ \Omega}. A 32 A32\text{ A} Type D device (Ia=20×InI_a = 20 \times I_n) has a maximum tabulated ZsZ_s of just 0.34 Ω\mathbf{0.34\ \Omega}.


The 0.8 Rule-of-Thumb Temperature Correction Factor

A critical practical and examination requirement is applying the 0.8 temperature correction factor (a rule of thumb given in IET guidance such as the On-Site Guide and Guidance Note 3).

The Engineering Rationale

  • The maximum ZsZ_s values published in BS 7671 Table 41.3 are calculated assuming that circuit conductors are operating at their maximum permitted conductor operating temperature—which is 70∘C70^\circ\text{C} for standard thermoplastic (PVC) insulated cables, or 90∘C90^\circ\text{C} for thermosetting (XLPE) cables.
  • However, when an electrician conducts initial verification or periodic inspection on site, the installation is unenergized or lightly loaded, meaning the conductors are cold at ambient room temperature (standardized as 20∘C20^\circ\text{C}).
  • Because copper has a positive temperature coefficient of resistance (α=0.00393/∘C\alpha = 0.00393 / ^\circ\text{C}), a cold copper conductor has significantly lower resistance than a hot conductor operating at 70∘C70^\circ\text{C} under full load.
  • If a measured ZsZ_s reading taken at 20∘C20^\circ\text{C} is barely below the tabulated maximum value, once the circuit is loaded to its full capacity and warms up to 70∘C70^\circ\text{C}, the conductor resistance will rise, causing the true operating ZsZ_s to exceed the permitted limit and preventing disconnection within 0.4 s0.4\text{ s}!

Applying the Rule-of-Thumb Formula

To ensure compliance when testing at ambient temperatures, the measured earth fault loop impedance must not exceed 80%80\% (0.80.8) of the tabulated value in BS 7671: Zs(measured)≤0.8×Zs(max tabulated)Z_{s(\text{measured})} \le 0.8 \times Z_{s(\text{max tabulated})}

Worked Example

A ring final circuit wired in 2.5 mm2/1.5 mm22.5\text{ mm}^2 / 1.5\text{ mm}^2 cable is protected by a 32 A32\text{ A} Type B MCB to BS EN 60898. During commissioning testing at 20∘C20^\circ\text{C}:

  • Measured external loop impedance: Ze=0.28 ΩZ_e = 0.28\ \Omega.
  • Measured circuit loop resistance: (R1+R2)=0.76 Ω(R_1 + R_2) = 0.76\ \Omega.
  • Total measured earth loop impedance: Zs=0.28+0.76=1.04 ΩZ_s = 0.28 + 0.76 = \mathbf{1.04\ \Omega}.

Compliance Check:

  1. From BS 7671 Table 41.3, maximum tabulated ZsZ_s for a 32 A32\text{ A} Type B MCB = 1.37 Ω1.37\ \Omega.
  2. Apply the 0.8 rule-of-thumb temperature correction factor: Zs(test limit)=1.37 Ω×0.8=1.096 Ω≈1.10 ΩZ_{s(\text{test limit})} = 1.37\ \Omega \times 0.8 = \mathbf{1.096\ \Omega \approx 1.10\ \Omega}
  3. Compare measured value against the 0.8 limit: Measured Zs (1.04 Ω)≤1.10 Ω  ⟹  COMPLIANT\text{Measured } Z_s\ (1.04\ \Omega) \le 1.10\ \Omega \implies \mathbf{COMPLIANT}

Tip

If a measured reading sits between the 0.8 value and the tabulated value (for instance, 1.20 Ω1.20\ \Omega on a 32 A Type B circuit), the circuit fails the simple rule-of-thumb test. In this case, the inspector must carry out the full temperature correction calculation described in IET Guidance Note 3 (Rhot=Rcold[1+α(70−20)]R_{\text{hot}} = R_{\text{cold}} [1 + \alpha(70 - 20)]) to determine whether the circuit complies.

Warning

Never record a circuit as compliant simply because the measured ZsZ_s is less than the tabulated value in Table 41.3 without applying the 0.8 temperature correction factor. Failing to account for thermal resistance rise can lead to lethal shock conditions where protective devices fail to operate within the statutory 0.4-second window.

Test Your Knowledge

Under BS 7671 Table 41.1, what is the maximum permitted disconnection time for a 230 V final circuit rated at 32 A or below in a TN earthing system?

A

5.0 seconds

B

1.0 second

C

0.2 seconds

D

0.4 seconds

Test Your Knowledge

In the fundamental earth fault loop impedance equation Zs = Ze + (R1 + R2), what does the term (R1 + R2) represent?

A

The combined resistance of the internal circuit line conductor (R1) and the circuit protective conductor (R2) from the distribution board to the furthest point

B

The total external loop impedance of the DNO service cable from the local substation transformer to the cut-out

C

The contact resistance of the independent consumer earth rod to the general mass of earth

D

The sum of the nominal operating breaking capacity of the main switch and the cut-out cartridge fuse

Test Your Knowledge

Why must a measured value of earth fault loop impedance taken at ambient room temperature (20 °C) be compared against 80% (the 0.8 correction factor) of the maximum tabulated Zs in BS 7671?

A

Because digital test instruments have a built-in calibration tolerance error of exactly 20%

B

Because conductor resistance increases as cables warm up to their maximum 70 °C operating temperature under full load

C

Because supply voltages on the National Grid fluctuate by up to 20% under peak winter demand

D

Because BS 7671 mandates a 20% safety margin to prevent nuisance tripping of 30 mA residual current devices

Test Your Knowledge

A domestic ring final circuit is protected by a 32 A Type B MCB complying with BS EN 60898. According to BS 7671 Table 41.3, the maximum tabulated Zs is 1.37 Ω. What is the maximum acceptable measured Zs during testing at ambient temperature using the standard 0.8 rule-of-thumb?

A

1.37 Ω

B

0.68 Ω

C

1.10 Ω

D

0.35 Ω