7.3 Transformer Principles, Construction & Calculations
Key Takeaways
A double-wound transformer is a static AC machine that transfers electrical power between circuits via mutual electromagnetic induction, providing complete galvanic isolation between primary and secondary circuits.
The transformer turns ratio links voltages, currents, and turns through V_p / V_s = N_p / N_s = I_s / I_p = k; because apparent power is conserved, stepping up voltage inversely steps down current.
Transformers are universally rated in Volt-Amperes (VA or kVA) rather than Watts (kW) because internal thermal heating depends solely on voltage and current, irrespective of the load power factor.
Transformer losses divide into constant iron core losses (hysteresis and eddy currents present whenever energized) and variable copper losses (I^2R resistive heating in windings proportional to the square of load current).
Autotransformers utilize a single tapped winding to achieve smaller physical dimensions, but they lack galvanic isolation—creating severe electric shock risks if the common neutral fails, which strictly prohibits their use in SELV/PELV and shaver installations.
Transformer Principles, Construction & Calculations
The electrical transformer is arguably the most critical piece of equipment within alternating current (AC) power systems. It is a static electromagnetic device with no moving parts that transfers electrical power between two or more circuits at the same operating frequency (50 Hz in the UK) through mutual electromagnetic induction.
Transformers make modern long-distance electrical transmission economically feasible by stepping generator voltages up to hundreds of thousands of volts (minimizing transmission currents and line losses), before progressively stepping voltages down to safe utilization levels for domestic and commercial consumers.
Working Principle of the Double-Wound Single-Phase Transformer
A basic single-phase double-wound transformer consists of two electrically independent, insulated copper windings wound on a common high-permeability laminated ferromagnetic steel core:
- Primary Winding: Connected to the incoming alternating voltage source (). It carries an alternating primary current () that sets up an alternating magnetic flux () throughout the core.
- Magnetic Core: Provides an unbroken, low-reluctance magnetic circuit that couples and confines the alternating flux, linking the turns of both windings.
- Secondary Winding: Links with the alternating core flux. By Faraday's Law of Electromagnetic Induction, the continuous reversal of flux induces an alternating electromotive force () across the secondary winding, driving secondary load current () into connected equipment.
Primary Input (Vp, Ip) Secondary Output (Vs, Is)
| |
v v
||--[ Winding ]--|| Laminated Core ||--[ Winding ]--||
|| (Np turns) ||======================|| (Ns turns) ||
|| || Mutual Flux Φ || ||
||--[ Winding ]--||======================||--[ Winding ]--||
(Galvanic Isolation)
Galvanic Isolation
In a standard double-wound transformer, there is zero direct electrical connection between the primary and secondary conductors. Electrical energy is converted into magnetic energy within the core and reconverted into electrical energy in the secondary winding. This complete physical separation is termed galvanic isolation (or electrical separation). It prevents transient DC voltages and high-voltage supply faults from directly propagating to the secondary side, forming the basis of specialized safety systems such as Separated Extra-Low Voltage (SELV) and isolated construction site supplies.
The Transformer Equation and Turns Ratio
Because the exact same alternating magnetic flux () links every turn of both the primary and secondary windings through the shared magnetic core, the induced voltage per turn is identical in both windings:
Rearranging this relationship gives the fundamental Transformer Turns Ratio Equation:
Where:
- = Primary terminal voltage in volts ()
- = Secondary terminal voltage in volts ()
- = Number of turns on primary winding
- = Number of turns on secondary winding
- = Primary full-load current in amperes ()
- = Secondary full-load current in amperes ()
- = Transformation ratio
Step-Up versus Step-Down Transformers
Transformers are classified according to how they modify voltage levels:
- Step-Up Transformer ():
- Secondary turns exceed primary turns.
- Secondary voltage is greater than primary voltage ().
- Secondary current is lower than primary current ().
- Example: Power station generator transformers stepping up from to for high-voltage grid transmission.
- Step-Down Transformer ():
- Secondary turns are fewer than primary turns.
- Secondary voltage is lower than primary voltage ().
- Secondary current is higher than primary current ().
- Example: Substation distribution transformers stepping down to , or domestic bell transformers stepping down to .
The Inverse Current Relationship and Power Conservation
Assuming an ideal transformer with 100% efficiency, input electrical power equals output electrical power:
This conservation principle explains the inverse current relationship ():
- When a transformer steps voltage up by a factor of 10, current is simultaneously stepped down by a factor of 10.
- When a transformer steps voltage down by a factor of 10, current is simultaneously stepped up by a factor of 10.
Tip
This inverse relationship is the reason electrical energy is transmitted at super-high voltages ( and ). Transmitting power at rather than reduces line current by a factor of 1,000. Because transmission cable heat loss is governed by , reducing current by 1,000 slashes cable power losses by a factor of —a million-fold reduction in energy dissipation!
Transformer Power Rating: Volt-Amperes (VA and kVA)
The capacity of an electrical transformer is universally quoted in Volt-Amperes (VA) or kilo-Volt-Amperes (kVA), representing Apparent Power ():
Why Transformers Are Rated in kVA, Not Kilowatts (kW)
In electrical engineering exams, candidates are frequently asked why transformers are rated in kVA rather than kW:
- Unknown Load Power Factor: Active (true) power in Watts depends on the circuit power factor (). A transformer manufacturer builds the machine without knowing what type of load the end user will connect (e.g. resistive heaters with , induction motors with , or electronic power supplies).
- Thermal Heating Limits: Internal winding heating is dictated by Joule losses (), which depend solely on current (), regardless of phase displacement. Core magnetic saturation and iron loss depend solely on voltage (). Therefore, the physical thermal rating of the transformer depends strictly on the product of and (Volt-Amperes), not real power (Watts).
Step-by-Step Worked Calculations
Worked Example 1: Turns, Voltage, and Current Calculations
Problem: A single-phase double-wound step-down transformer is connected to a , supply. The primary winding has and the secondary winding has . If the secondary feeds a resistive heating load drawing , determine:
- The secondary terminal voltage ()
- The primary full-load current ()
- The transformer apparent power rating in
Solution:
- Calculate secondary voltage:
- Calculate primary current using inverse current ratio:
- Calculate apparent power rating: (Check with primary: —identical values confirm calculation accuracy.)
Worked Example 2: Determining Primary Turn Count
Problem: A site transformer steps down single-phase supply to Centre-Tapped-to-Earth. The secondary winding contains . Calculate the number of turns required on the primary winding.
Solution:
- Transpose the turns ratio formula for :
- Substitute values:
Transformer Construction: Cores and Windings
Practical transformers are engineered to maximize mutual magnetic coupling while minimizing energy losses and mechanical hum.
Core-Type versus Shell-Type Construction
- Core-Type Transformer: Windings are arranged in concentric cylindrical layers surrounding two vertical limbs of a rectangular magnetic core. The low-voltage winding is placed closest to the iron core to ease insulation requirements, with the high-voltage winding wound over it. Core-type units are common in high-voltage transmission equipment.
- Shell-Type Transformer: The magnetic iron core completely encloses and surrounds the copper windings like an external shell. The core provides two parallel return paths for magnetic flux, yielding superior magnetic confinement and reduced flux leakage. Shell-type designs are common in commercial low-voltage distribution transformers and power supply units.
Core Material and Lamination Geometry
Transformer cores are constructed from thin stampings of high-permeability silicon alloy steel (cold-rolled grain-oriented, CRGO), coated with insulating varnish to minimize eddy current and hysteresis losses. Stampings are produced in standardized shapes:
- 'E' and 'I' Laminations: The central limb of the 'E' stamping carries twice the magnetic flux of the outer limbs. The 'I' strip bridges the top.
- Interleaved Assembly: Successive layers of laminations are reversed and alternated during core stacking to eliminate continuous air gaps at butt joints, significantly reducing magnetic reluctance.
Transformer Losses and Efficiency
Because transformers have no rotating parts, they experience zero mechanical friction or windage losses. Total internal energy losses consist purely of electrical and magnetic losses:
1. Copper Losses () — Variable Losses
Caused by the electrical resistance of the primary and secondary copper windings carrying current ( Joule heating).
- Dependent entirely on load current: At zero load (), copper loss is negligible. At full load, copper loss reaches maximum ().
- At half-load (), copper loss drops to (25%) of its full-load value.
2. Iron / Core Losses () — Constant Losses
Caused by magnetic hysteresis and eddy currents within the steel core laminations.
- Independent of load: Because applied voltage and frequency remain constant, core flux density remains virtually identical from zero load to full load. Iron losses remain constant 24 hours a day whenever the transformer is energized.
Efficiency Formula ()
Because there are no rotating mechanical parts, modern power transformers achieve extraordinary efficiencies ranging between and .
Autotransformers: Construction, Advantages & Critical Safety Hazards
An autotransformer differs fundamentally from a double-wound transformer: it consists of only one continuous winding on a laminated iron core, which acts as both primary and secondary.
Primary Supply (230 V)
L ------------------------------.
|
[ Winding ]
|-------> Tapped Secondary Output (110 V)
[ Winding ]
|
N ------------------------------+-------> Secondary Common Neutral
Operational Advantages
- Reduced Copper and Size: Because part of the winding carries the difference between primary and secondary currents (), lighter copper conductors and smaller cores can be used.
- Higher Efficiency & Lower Cost: Lower internal resistance minimizes copper losses, yielding lower purchase and running costs.
- Used commonly in motor soft-starters (Korndorfer starters) and laboratory variable AC power supplies (Variacs).
Critical Safety Hazard: Lack of Galvanic Isolation
Warning
An autotransformer provides ZERO galvanic isolation (no electrical separation). The primary and secondary share a direct, continuous conductive copper connection.
- Broken Common Neutral Risk: If the shared neutral connection becomes loose, high-resistance, or severed, the full primary phase voltage (e.g. ) appears directly on the low-voltage secondary terminals, creating an immediate, lethal electric shock risk to operators expecting extra-low or reduced voltage.
- Prohibitions in BS 7671: Because the source for these measures must be a safety isolating (double-wound) transformer or equivalent, an autotransformer cannot be used where electrical separation is required for protection:
- Separated Extra-Low Voltage (SELV) circuits (e.g. bathroom lighting, pool equipment).
- Protective Extra-Low Voltage (PELV) circuits.
- Bathroom shaver supply units conforming to BS EN 61558-2-5 (which mandate a double-wound isolating transformer with an earthed metal screen).
- Construction site temporary supplies to BS 7375 / BS 7671 Section 704.
Practical Electrotechnical Applications in UK Installations
| Transformer Application | Specification & Construction | Operational Function & Safety Purpose |
|---|---|---|
| 110 V Site Transformers | Double-wound, or to Centre-Tapped-to-Earth (CTE) | Strongly preferred on UK construction sites for portable tools and hand lamps (BS 7375; BS 7671 Section 704). Center tap of secondary is earthed, limiting shock voltage to earth to a safe maximum of AC. |
| Bell / Chime Transformers | Double-wound step-down, to or SELV | Provides safe extra-low voltage for domestic doorbells, with double insulation preventing mains voltages reaching external push buttons. |
| Current Transformers (CT) | Toroidal core surrounding main busbar, stepping down current (e.g. ) | Instrument transformer used in commercial switchboards to safely step down high line currents for standard ammeters and protective trip relays. |
| Voltage Transformers (VT) | High-accuracy step-down (e.g. ) | Instrument transformer stepping down high distribution voltages for voltmeters and tariff energy meters without exposing instrumentation to high voltage. |
| Grid Distribution Transformers | Heavy 3-phase oil-filled double-wound units ( to ) | Mounted on street-level substations or poles, stepping regional distribution down to standard 3-phase 4-wire TN-C-S / TN-S supplies for consumer premises. |
A single-phase double-wound step-down transformer has 800 turns on its primary winding and 40 turns on its secondary winding. If the primary is connected to a 230 V AC supply, what is the output secondary voltage?
46.0 V
23.0 V
5.75 V
11.5 V
Why are electrical power and distribution transformers rated in Volt-Amperes (VA or kVA) rather than in Watts (kW)?
Because transformers cannot supply real power to resistive loads
Because internal thermal heating and magnetic saturation depend solely on voltage and current, irrespective of the load power factor
Because the secondary voltage fluctuates continuously with alternating grid frequency
Because statutory regulations prohibit rating static electromagnetic machines in metric units
What is the primary safety hazard associated with an autotransformer that strictly prohibits its use for SELV, PELV, and bathroom shaver circuits?
The absence of galvanic isolation means that an open-circuit in the common winding can expose secondary equipment to full primary mains voltage
Autotransformers produce excessive harmonic distortion that overheats protective conductors
The magnetic core of an autotransformer operates at elevated temperatures that melt standard PVC cable insulation
Autotransformers cannot step down alternating voltages below 110 V
In an operational electrical transformer, how do copper losses and iron (core) losses behave when the electrical load connected to the secondary winding increases?
Both copper losses and iron losses increase in direct proportion to the secondary current drawn by the connected load
Copper losses remain constant at all loads, whereas iron losses increase with the square of the current
Iron losses stay constant at all loads, while copper losses rise with the square of the load current (I²R)
Both copper losses and iron losses remain completely constant regardless of the load connected