6.1 Resistance, Resistivity & Conductor Dimensions

Key Takeaways

  • Electrical resistance (RR), measured in Ohms (Ω\Omega), represents the opposition encountered by electric charge drifting through a material under an applied electric field.

  • Four physical factors dictate conductor resistance: conductor length (directly proportional), cross-sectional area (inversely proportional), material resistivity (in Ω⋅m\Omega\cdot\text{m}), and operating temperature.

  • The fundamental conductor resistance formula is R=(ρ×L)/AR = (\rho \times L) / A; cross-sectional area in mm2\text{mm}^2 must always be converted to base SI square metres (m2\text{m}^2) by multiplying by 10−610^{-6}.

  • Standard annealed copper conductor resistivity at 20∘C20^\circ\text{C} is taken as 1.72×10−8 Ω⋅m1.72 \times 10^{-8}\ \Omega\cdot\text{m} (0.0172 μΩ⋅m0.0172\ \mu\Omega\cdot\text{m}), whereas aluminium exhibits higher resistivity at 2.82×10−8 Ω⋅m2.82 \times 10^{-8}\ \Omega\cdot\text{m}.

  • Geometric scaling exhibits non-linear relationships: doubling conductor length doubles resistance (2×2\times), whereas doubling conductor diameter quadruples cross-sectional area and reduces resistance to one-quarter (0.25×0.25\times).

Last updated: October 2026

Resistance, Resistivity & Conductor Dimensions

In electrotechnical engineering, electrical resistance (RR) is defined as the property of a material or circuit element that opposes the flow of electric charge (current). When a potential difference (voltage) is established across a conductive path, an electric field accelerates mobile charge carriers—free electrons—through the material. As these electrons drift through the crystalline lattice of the conductor, they repeatedly collide with vibrating positive metal ions.

Each collision transfers kinetic energy from the drifting electrons to the lattice ions, increasing thermal kinetic energy and causing the conductor to warm up. This energy transformation, known as Joule heating (I2RI^2R), represents the physical manifestation of electrical resistance. Resistance is measured in the SI unit Ohm (symbol Ω\Omega), named in honour of German physicist Georg Simon Ohm. By definition, a conductor exhibits a resistance of one Ohm (1 Ω1\ \Omega) when a constant potential difference of one volt (1 V1\text{ V}) across its terminals produces a current of one ampere (1 A1\text{ A}).

Note

Resistance is not an intrinsic property of a chemical element alone; rather, it is an extrinsic property of a specific component, determined by both its physical dimensions (length and cross-sectional area) and its internal atomic material characteristics.


The Four Factors Determining Conductor Resistance

The electrical resistance of any conductor depends on four distinct physical variables:

  1. Length (LL): Resistance is directly proportional to conductor length (R∝LR \propto L). As an electric charge travels through a longer path, it encounters a proportionally greater number of lattice ions, leading to more frequent collisions and higher cumulative opposition. Doubling the length doubles the electrical resistance.
  2. Cross-Sectional Area (AA): Resistance is inversely proportional to cross-sectional area (R∝1AR \propto \frac{1}{A}). A larger cross-sectional area provides a broader conductive pathway with more parallel routes through which mobile electrons can drift simultaneously. Doubling the cross-sectional area halves the electrical resistance.
  3. Material Type (Resistivity, ρ\rho): Different elements and alloys possess differing atomic structures, valence electron densities, and lattice configurations. The intrinsic property quantifying how strongly a given material opposes charge movement is called its resistivity (symbolized by the Greek letter rho, ρ\rho).
  4. Temperature (θ\theta): The kinetic energy and vibration amplitude of the conductor's lattice ions vary directly with temperature. In metallic conductors, rising temperature causes the lattice ions to vibrate more violently across larger amplitudes, significantly increasing collision cross-sections and raising electrical resistance.

Material Resistivity (ρ\rho)

Resistivity is the intrinsic electrical resistance of a uniform sample of a material having unit length and unit cross-sectional area—specifically, a solid cube measuring one metre on each side (1 m×1 m×1 m1\text{ m} \times 1\text{ m} \times 1\text{ m}). Resistivity is expressed in Ohm-metres (Ω⋅m\Omega\cdot\text{m}), or in micro-Ohm metres (μΩ⋅m\mu\Omega\cdot\text{m}).

ρ=R×AL=Ω×m2m=Ω⋅m\rho = \frac{R \times A}{L} = \frac{\Omega \times \text{m}^2}{\text{m}} = \Omega\cdot\text{m}

Materials with very low resistivity are excellent electrical conductors, whereas materials with very high resistivity serve as insulators. Below are standard resistivity values for common engineering materials evaluated at a reference ambient temperature of 20∘C20^\circ\text{C}:

MaterialTypical Resistivity at 20∘C20^\circ\text{C} (Ω⋅m\Omega\cdot\text{m})Electrical Classification & Practical Application
Silver1.59×10−81.59 \times 10^{-8} (0.0159 μΩ⋅m0.0159\ \mu\Omega\cdot\text{m})Highest electrical conductivity of all metals; used for switchgear contacts and high-rupture-capacity (HRC) fuse elements.
Copper (Annealed)1.72×10−81.72 \times 10^{-8} (0.0172 μΩ⋅m0.0172\ \mu\Omega\cdot\text{m})Industry standard for building wiring, flexible cords, busbars, and electric motor windings due to superior conductivity and ductility.
Gold2.44×10−82.44 \times 10^{-8} (0.0244 μΩ⋅m0.0244\ \mu\Omega\cdot\text{m})Excellent conductivity with total resistance to surface oxidation; widely applied in low-voltage data terminals and edge connectors.
Aluminium2.82×10−82.82 \times 10^{-8} (0.0282 μΩ⋅m0.0282\ \mu\Omega\cdot\text{m})Lightweight conductor used in overhead transmission lines (ACSR) and large commercial subterranean distribution cables.
Tungsten5.60×10−85.60 \times 10^{-8} (0.0560 μΩ⋅m0.0560\ \mu\Omega\cdot\text{m})High melting point (3,422∘C3,422^\circ\text{C}); used in incandescent lamp filaments and specialised arc contacts.
Constantan (Eureka)49.0×10−849.0 \times 10^{-8} (0.490 μΩ⋅m0.490\ \mu\Omega\cdot\text{m})Copper-nickel alloy (55% Cu, 45% Ni) with near-zero temperature coefficient; used for precision laboratory standard resistors and instrument shunts.
Nichrome100.0×10−8100.0 \times 10^{-8} (1.00 μΩ⋅m1.00\ \mu\Omega\cdot\text{m})Nickel-chromium alloy exhibiting high resistivity and oxidation resistance at high heat; standard element for domestic heaters and showers.
Carbon (Graphite)3,500×10−83,500 \times 10^{-8} (35.0 μΩ⋅m35.0\ \mu\Omega\cdot\text{m})Non-metal conductor with negative temperature coefficient; used for DC motor commutator brushes and arc electrodes.

Copper versus Aluminium in Installation Practice

Comparing the resistivities of copper and aluminium reveals an important engineering relationship:

ρAlρCu=2.82×10−81.72×10−8≈1.64\frac{\rho_{\text{Al}}}{\rho_{\text{Cu}}} = \frac{2.82 \times 10^{-8}}{1.72 \times 10^{-8}} \approx 1.64

Because aluminium's resistivity is approximately 1.64 times that of copper, an aluminium cable requires roughly a 64% larger cross-sectional area than a copper cable of identical length to achieve the same electrical resistance. However, aluminium's mass density is only one-third that of copper. As a result, for equivalent current-carrying capacity, an aluminium conductor weighs roughly half as much as a copper conductor, making aluminium the economical choice for long-span high-voltage overhead grid lines.


The Conductor Resistance Formula: R=ρLAR = \frac{\rho L}{A}

Combining the physical relationships yields the fundamental resistance formula:

R=ρ×LAR = \frac{\rho \times L}{A}

Where:

  • RR = Conductor resistance in Ohms (Ω\Omega)
  • ρ\rho = Material resistivity in Ohm-metres (Ω⋅m\Omega\cdot\text{m})
  • LL = Conductor length in metres (m\text{m})
  • AA = Conductor cross-sectional area in square metres (m2\text{m}^2)

Formula Transpositions

Depending on the unknown quantity required in examination questions, the formula transposes as follows:

ρ=R×AL,L=R×Aρ,A=ρ×LR\rho = \frac{R \times A}{L}, \qquad L = \frac{R \times A}{\rho}, \qquad A = \frac{\rho \times L}{R}

Warning

In electrical contracting, cable cross-sectional area is universally quoted in square millimetres (mm2\text{mm}^2), such as 1.5 mm21.5\text{ mm}^2 or 2.5 mm22.5\text{ mm}^2. However, the resistivity formula strictly requires cross-sectional area in base SI square metres (m2\text{m}^2). Failing to execute this metric conversion is the single most common cause of calculation failure on examination papers.

Converting Square Millimetres (mm2\text{mm}^2) to Square Metres (m2\text{m}^2)

Because one linear metre contains 1,0001,000 millimetres (103 mm10^3\text{ mm}), one square metre consists of a square 1,000 mm1,000\text{ mm} wide by 1,000 mm1,000\text{ mm} high:

1 m2=1,000 mm×1,000 mm=1,000,000 mm2=106 mm21\text{ m}^2 = 1,000\text{ mm} \times 1,000\text{ mm} = 1,000,000\text{ mm}^2 = 10^6\text{ mm}^2

To convert an area from mm2\text{mm}^2 to m2\text{m}^2, you must divide by 1,000,0001,000,000 or multiply by 10−610^{-6}:

A(m2)=A(mm2)×10−6A(\text{m}^2) = A(\text{mm}^2) \times 10^{-6}

Standard UK metric cable sizes convert to base units as follows:

  • 1.0 mm2=1.0×10−6 m21.0\text{ mm}^2 = 1.0 \times 10^{-6}\text{ m}^2
  • 1.5 mm2=1.5×10−6 m21.5\text{ mm}^2 = 1.5 \times 10^{-6}\text{ m}^2
  • 2.5 mm2=2.5×10−6 m22.5\text{ mm}^2 = 2.5 \times 10^{-6}\text{ m}^2
  • 4.0 mm2=4.0×10−6 m24.0\text{ mm}^2 = 4.0 \times 10^{-6}\text{ m}^2
  • 6.0 mm2=6.0×10−6 m26.0\text{ mm}^2 = 6.0 \times 10^{-6}\text{ m}^2
  • 10.0 mm2=10.0×10−6 m2=1.0×10−5 m210.0\text{ mm}^2 = 10.0 \times 10^{-6}\text{ m}^2 = 1.0 \times 10^{-5}\text{ m}^2
  • 16.0 mm2=16.0×10−6 m2=1.6×10−5 m216.0\text{ mm}^2 = 16.0 \times 10^{-6}\text{ m}^2 = 1.6 \times 10^{-5}\text{ m}^2
  • 25.0 mm2=25.0×10−6 m2=2.5×10−5 m225.0\text{ mm}^2 = 25.0 \times 10^{-6}\text{ m}^2 = 2.5 \times 10^{-5}\text{ m}^2

Cross-Sectional Area of Circular Conductor Cores

Where an examination problem specifies the diameter (dd) or radius (rr) of a solid circular conductor core rather than stating the area directly, apply standard circular geometry:

A=πr2=πd24A = \pi r^2 = \frac{\pi d^2}{4}

If measuring a conductor core with a digital micrometer reveals a diameter of 1.78 mm1.78\text{ mm}: r=1.782=0.89 mmr = \frac{1.78}{2} = 0.89\text{ mm} A=π×(0.89)2≈2.488 mm2≈2.5 mm2A = \pi \times (0.89)^2 \approx 2.488\text{ mm}^2 \approx 2.5\text{ mm}^2


Step-by-Step Worked Calculations

Worked Example 1: Resistance of a 2.5 mm22.5\text{ mm}^2 Radial Run

Problem: Calculate the resistance of a single copper conductor 50 metres50\text{ metres} long having a cross-sectional area of 2.5 mm22.5\text{ mm}^2 at an ambient temperature of 20∘C20^\circ\text{C}. Take copper resistivity as ρ=1.72×10−8 Ω⋅m\rho = 1.72 \times 10^{-8}\ \Omega\cdot\text{m}.

Solution:

  1. State given values in base SI units:
    • ρ=1.72×10−8 Ω⋅m\rho = 1.72 \times 10^{-8}\ \Omega\cdot\text{m}
    • L=50 mL = 50\text{ m}
    • A=2.5 mm2=2.5×10−6 m2A = 2.5\text{ mm}^2 = 2.5 \times 10^{-6}\text{ m}^2
  2. Apply the resistivity equation: R=ρLA=1.72×10−8×502.5×10−6R = \frac{\rho L}{A} = \frac{1.72 \times 10^{-8} \times 50}{2.5 \times 10^{-6}}
  3. Calculate the numerator: 1.72×10−8×50=8.60×10−71.72 \times 10^{-8} \times 50 = 8.60 \times 10^{-7}
  4. Divide by the cross-sectional area: R=8.60×10−72.5×10−6=0.344 ΩR = \frac{8.60 \times 10^{-7}}{2.5 \times 10^{-6}} = 0.344\ \Omega

Tip

In practical circuit verification, a single radial circuit consists of both an outgoing line conductor and a returning neutral or protective conductor. If evaluating the total loop resistance (R1+R2R_1 + R_2) of a 50 m50\text{ m} run where both line and return are 2.5 mm22.5\text{ mm}^2, the total conductor length is 100 m100\text{ m}, yielding 0.344×2=0.688 Ω0.344 \times 2 = 0.688\ \Omega.

Worked Example 2: Resistance of an Aluminium Sub-Main

Problem: A commercial sub-main feeder uses a 120 metre120\text{ metre} single-core aluminium conductor with a cross-sectional area of 16 mm216\text{ mm}^2. Calculate its resistance at 20∘C20^\circ\text{C} given aluminium resistivity is 2.82×10−8 Ω⋅m2.82 \times 10^{-8}\ \Omega\cdot\text{m}.

Solution:

  1. Identify quantities:
    • ρ=2.82×10−8 Ω⋅m\rho = 2.82 \times 10^{-8}\ \Omega\cdot\text{m}
    • L=120 mL = 120\text{ m}
    • A=16 mm2=16×10−6 m2A = 16\text{ mm}^2 = 16 \times 10^{-6}\text{ m}^2
  2. Substitute into formula: R=2.82×10−8×12016×10−6=3.384×10−616×10−6=0.2115 ΩR = \frac{2.82 \times 10^{-8} \times 120}{16 \times 10^{-6}} = \frac{3.384 \times 10^{-6}}{16 \times 10^{-6}} = 0.2115\ \Omega

Worked Example 3: Transposition to Determine Required Area

Problem: A lighting sub-circuit requires an 80 metre80\text{ metre} run of single-core copper conductor. Design criteria dictate that the conductor resistance must not exceed 0.55 Ω0.55\ \Omega at 20∘C20^\circ\text{C}. Calculate the minimum required cross-sectional area in mm2\text{mm}^2 and select the appropriate standard metric size.

Solution:

  1. Transpose the resistance formula for area AA: A=ρLRA = \frac{\rho L}{R}
  2. Substitute values (ρ=1.72×10−8 Ω⋅m\rho = 1.72 \times 10^{-8}\ \Omega\cdot\text{m}): A=1.72×10−8×800.55=1.376×10−60.55≈2.502×10−6 m2A = \frac{1.72 \times 10^{-8} \times 80}{0.55} = \frac{1.376 \times 10^{-6}}{0.55} \approx 2.502 \times 10^{-6}\text{ m}^2
  3. Convert back to mm2\text{mm}^2 by multiplying by 10610^6: A=2.502×10−6×106=2.502 mm2A = 2.502 \times 10^{-6} \times 10^6 = 2.502\text{ mm}^2
  4. Select the standard cable size: A 2.5 mm22.5\text{ mm}^2 conductor would yield a resistance slightly over the 0.55 Ω0.55\ \Omega limit (R=0.5504 ΩR = 0.5504\ \Omega). Therefore, to guarantee compliance, the next standard size of 4.0 mm24.0\text{ mm}^2 must be selected.

Geometric Proportionality and Scaling Effects

Examiners regularly test candidate understanding of proportional relationships without providing full numerical values:

  • Doubling Conductor Length (L→2LL \rightarrow 2L): Rnew=ρ(2L)A=2×(ρLA)=2RR_{\text{new}} = \frac{\rho (2L)}{A} = 2 \times \left(\frac{\rho L}{A}\right) = 2R Doubling length doubles resistance (2×2\times).
  • Halving Conductor Length (L→0.5LL \rightarrow 0.5L): Halving length halves resistance (0.5×0.5\times).
  • Doubling Conductor Cross-Sectional Area (A→2AA \rightarrow 2A): Rnew=ρL2A=12×(ρLA)=0.5RR_{\text{new}} = \frac{\rho L}{2A} = \frac{1}{2} \times \left(\frac{\rho L}{A}\right) = 0.5R Doubling area halves resistance (0.5×0.5\times).
  • Doubling Conductor Diameter (d→2dd \rightarrow 2d): Because area depends on the square of the diameter (A=πd24A = \frac{\pi d^2}{4}): Anew=π(2d)24=π×4d24=4AA_{\text{new}} = \frac{\pi (2d)^2}{4} = \frac{\pi \times 4d^2}{4} = 4A Substituting 4A4A into the resistance equation: Rnew=ρL4A=14×(ρLA)=0.25RR_{\text{new}} = \frac{\rho L}{4A} = \frac{1}{4} \times \left(\frac{\rho L}{A}\right) = 0.25R Doubling diameter quadruples area and reduces resistance to one-quarter (0.25×0.25\times).
  • Doubling Length AND Doubling Diameter: Rnew=ρ(2L)4A=24R=0.5RR_{\text{new}} = \frac{\rho (2L)}{4A} = \frac{2}{4} R = 0.5R Doubling both length and diameter halves the original resistance.
Loading diagram...
Factors Dictating Conductor Resistance and Geometric Scaling Relationships
Test Your Knowledge

What happens to the electrical resistance of a solid cylindrical copper conductor if its diameter is doubled while its length remains unchanged?

A

It is halved, because resistance is inversely proportional to the diameter (0.5 times)

B

It falls to one-quarter of its original value (0.25 times)

C

It doubles (2 times the original value)

D

It remains completely unchanged

Test Your Knowledge

Calculate the resistance of a 50-metre run of single-core 2.5 mm² annealed copper conductor at 20°C, taking copper resistivity as 1.72 x 10^-8 Ω·m.

A

0.0344 Ω

B

3.44 Ω

C

0.086 Ω

D

0.344 Ω

Test Your Knowledge

When applying the conductor resistivity formula R = (ρ × L) / A, what mathematical operation must be performed to convert a conductor's cross-sectional area from square millimetres (mm²) to square metres (m²)?

A

Multiply by 10^-6 (or divide by 1,000,000)

B

Multiply by 10^-3 (or divide by 1,000)

C

Multiply by 10^3 (or multiply by 1,000)

D

Multiply by 10^6 (or multiply by 1,000,000)

Test Your Knowledge

Why does an aluminium conductor require a significantly larger cross-sectional area than an annealed copper conductor of equal length to achieve the exact same electrical resistance?

A

Aluminium possesses a substantially lower mechanical tensile strength than copper

B

Aluminium has a lower atomic mass and density than copper

C

Aluminium exhibits a higher intrinsic material resistivity than copper

D

Aluminium develops an insulating aluminium oxide surface film in air