21.4 Optical Fiber Cables & Communications Systems Entering Buildings (2026 Articles 720–723, 800, 810, 820)

Key Takeaways

  • Optical fiber cables are nonconductive (OFN types, no metallic members), conductive (OFC types, with non-current-carrying metallic members), or composite (fibers plus current-carrying conductors).

  • Nonconductive optical fiber cables may share a raceway or cable tray with power, Class 1, or nonpower-limited fire alarm conductors of 1000 V or less, but conductive optical fiber cables may not.

  • Unlisted outside plant communications or optical fiber cable may extend no more than 50 ft inside a building from its point of entrance before terminating in an enclosure or listed protector.

  • The bonding conductor for a communications primary protector must be copper, insulated, at least 14 AWG, and, at one- and two-family dwellings, not longer than 20 ft unless a separate electrode is used and bonded to the power electrode system with 6 AWG copper.

  • In the 2026 NEC, Article 800 covers only communications wiring outside and entering buildings; inside buildings, communications cabling follows the Chapter 7 limited-energy rules.

Last updated: October 2026

What changed in 2026

The 2026 NEC removed the independence of Chapter 8 and consolidated limited-energy wiring:

  • Articles 770 (Optical Fiber Cables) and 805 (Communications Circuits) were deleted. Their inside-the-building requirements moved into Articles 720 (general wiring methods), 722 (cables, including listing, marking, and substitutions), and 723 (raceways, cable routing assemblies, and cable trays).
  • Article 800 now covers communications systems outside and entering buildings: entrance cables, primary protection, and bonding at the entrance.
  • Article 742 covers overvoltage protection and Article 750 covers grounding and bonding for limited-energy systems.
  • Articles 810 (radio and television equipment), 820 (community antenna television and radio distribution), 830 (network-powered broadband), and 840 (premises-powered broadband) continue for their specific systems.

Optical fiber cable types

TypeConstructionMarkings
NonconductiveNo metallic members; strength members are nonmetallic, such as aramid yarnOFNP (plenum), OFNR (riser), OFNG or OFN (general purpose)
ConductiveNon-current-carrying conductive members, such as metallic strength members, armor, or vapor barriersOFCP, OFCR, OFCG or OFC
CompositeOptical fibers plus current-carrying electrical conductorsListed and marked under the article for the electrical conductors, such as power or Class 2

Cable substitutions

A cable with a higher fire rating may replace a lower one in the same space: plenum cable may be used where riser or general-purpose cable is required, and riser cable where general-purpose cable is required. Nonconductive cable may substitute for conductive cable of the same or lower rating (for example, OFNP for OFCP or OFCR), but conductive cable may not substitute for nonconductive cable. Plenum spaces need plenum-rated cable or cable in a raceway suitable for the plenum.

Optical fiber with electrical conductors

SituationRule
Nonconductive fiber in the same raceway or cable tray with conductors of electric light, power, Class 1, NPLFA, or medium-power broadband circuits of 1000 V or lessPermitted
Conductive fiber in the same raceway or cable tray with those conductorsNot permitted
Composite fiber cables containing only power or Class 1 conductors of 1000 V or lessMay share enclosures and raceways with power and Class 1 conductors of 1000 V or less
Nonconductive fiber in the same cabinet, box, panel, or enclosure that houses the terminations of power, Class 1, or NPLFA circuitsNot permitted, unless the fiber is functionally associated with that equipment, in factory- or field-assembled control centers, or in industrial establishments with qualified maintenance
Fiber with Class 2, Class 3, communications, and PLFA cablesPermitted in the same raceway, enclosure, or cable tray

Installation inside buildings (Articles 720 to 723)

  • Cables must be supported by the building structure, not by ceiling grids or ceiling-support wires, and installed so they do not block access to equipment above suspended ceilings.
  • Penetrations of fire-resistant-rated walls, floors, and ceilings must be firestopped.
  • Abandoned optical fiber and communications cables: the accessible portion must be removed, unless tagged for future use.
  • Cables in plenums must be plenum rated; cables in vertical risers between floors must be riser rated or in a raceway or fireproof shaft as permitted.
  • Raceways and cable routing assemblies used for these cables must have the same fire rating as the space (plenum, riser, or general purpose).

Communications entering buildings (Article 800)

Entrance cables

  • Unlisted outside plant cable: unlisted communications or optical fiber cable may be installed in building spaces other than risers and plenums where the length within the building, measured from the point of entrance, does not exceed 50 ft, and the cable terminates in an enclosure or on a listed primary protector. The point of entrance may be extended by enclosing the entrance cable in RMC or IMC to the point of emergence.
  • Conductive members: the metallic members of conductive optical fiber cable and the metallic sheath of communications cable entering a building must be bonded or grounded as close as practicable to the point of entrance.

Primary protectors and bonding

  • A listed primary protector is required on each communications circuit that is exposed to lightning or accidental contact with power conductors, located as close as practicable to the point of entrance.
  • Bonding conductor: copper or other corrosion-resistant conductive material, insulated, at least 14 AWG, with a current-carrying capacity at least equal to the outer sheath or protected conductors, run as straight as practicable, and protected where exposed to physical damage.
  • Connection point: to the building's intersystem bonding termination (250.94), or to the grounding electrode system, the power service equipment enclosure, the grounding electrode conductor, or another permitted point.
  • Length at one- and two-family dwellings: the bonding conductor or grounding electrode conductor must be as short as practicable and not longer than 20 ft. If 20 ft cannot be achieved, a separate electrode (such as a ground rod) may be installed for the protector and bonded to the power grounding electrode system with at least 6 AWG copper.

Antennas and CATV

  • Radio and television antennas (Article 810): masts and metal structures supporting antennas, and the antenna discharge unit, must be bonded to the building's grounding means with a copper bonding conductor of at least 10 AWG for receiving stations; outdoor antennas and lead-ins must be kept away from power conductors and may not be attached to poles carrying power circuits over 250 V.
  • CATV (Article 820): the outer conductive shield of coaxial cable entering a building must be bonded as close as practicable to the point of entrance, with the same 14 AWG minimum and 20 ft dwelling limit for the bonding conductor; unlisted outside coaxial cable may extend no more than 50 ft inside.

Worked example: fiber in a commercial building

A contractor brings a single-mode fiber cable with a steel armor (conductive, OFC-type outside plant cable) into a building and runs it to a telecom room 120 ft away.

  1. Entrance: the unlisted outside plant cable may extend only 50 ft inside unless enclosed in RMC or IMC from the point of entrance; at the 50 ft limit, splice it in an enclosure to a listed indoor cable.
  2. Bonding: bond the steel armor as close as practicable to the point of entrance, to the intersystem bonding termination.
  3. Indoor cable: the route passes through a return-air plenum, so the indoor cable must be OFNP or OFCP, or be in a plenum-rated raceway.
  4. Shared raceway: if it must share a raceway with 277 V lighting conductors, only a nonconductive (OFN-type) cable is permitted.
Test Your Knowledge

Which optical fiber cable may share a raceway with 480 V power conductors?

A

OFCP conductive plenum cable

B

OFCR conductive riser cable

C

OFNR nonconductive riser cable

D

No optical fiber cable may ever share a raceway with power conductors

Test Your Knowledge

How far may unlisted outside plant communications cable extend inside a building from its point of entrance?

A

20 ft

B

25 ft

C

100 ft

D

50 ft

Test Your Knowledge

At a one-family dwelling, the communications primary protector bonding conductor would need to be 30 ft long to reach the intersystem bonding termination. What does the Code permit?

A

A 30 ft insulated bonding conductor of 14 AWG copper to the IBT

B

A separate protector electrode bonded to the power electrodes with 6 AWG copper

C

No bonding of the protector, if it is listed for ungrounded use

D

Bonding to a nearby outdoor water faucet or hose bib

Sections you finish are checked off in the contents.

Congratulations!

You've completed this section

Continue exploring other exams