16.3 Capacitors, Transformers Over 1000 V & Medium-Voltage Equipment (Articles 460, 450 & 495)

Key Takeaways

  • The ampacity of capacitor circuit conductors must be at least 135% of the capacitor's rated current (460.8(A)).

  • Conductors connecting a capacitor to a motor's terminals or motor circuit conductors must have at least one-third the ampacity of the motor circuit conductors, and never less than 135% of the capacitor rated current (460.8(A)).

  • Capacitors of 1000 V or less must have a means to drain the stored charge to 50 V or less within 1 minute after disconnection (460.6).

  • Where a power-factor capacitor is connected on the load side of a motor overload device, the overload device is sized from the reduced line current that results from the improved power factor (460.9).

  • The 2026 NEC 495.2 requires equipment rated up to 15 kV to be listed starting January 1, 2029, and equipment over 15 kV up to 52 kV starting January 1, 2032.

Last updated: October 2026

Capacitors (Article 460)

Power-factor correction capacitors reduce the reactive current a motor or facility draws, which lowers line current and voltage drop. DLI's knowledge areas include ampacity of capacitor circuit conductors and motor circuits including a capacitor.

Conductors (460.8(A))

  • Capacitor circuit conductors must have an ampacity of at least 135% of the capacitor's rated current.
  • Conductors connecting a capacitor to the terminals of a motor, or to motor circuit conductors, must have an ampacity of at least one-third of the ampacity of the motor circuit conductors, and in no case less than 135% of the capacitor's rated current.

The 135% factor allows for overvoltage, harmonic currents, and manufacturing tolerances that make a capacitor draw more than its nameplate current.

Overcurrent protection and disconnecting means (460.8(B) and (C))

  • An OCPD is required in each ungrounded conductor for each capacitor bank, rated or set as low as practicable. It is not required for a capacitor connected on the load side of a motor overload device.
  • A disconnecting means is required in each ungrounded conductor for each capacitor bank. It must open all ungrounded conductors simultaneously, have a continuous rating of at least 135% of the capacitor's rated current, and is permitted to disconnect the capacitor as a regular operating procedure. It is not required where the capacitor is connected on the load side of a motor controller.

Stored energy (460.6)

Capacitors operating at 1000 V or less must have a means to discharge the stored energy to 50 V or less within 1 minute after the capacitor is disconnected. The discharge circuit must be permanently connected to the capacitor terminals or arranged to connect automatically when the capacitor is disconnected; a manual means of switching or connecting the discharge circuit is not permitted. A capacitor connected directly to motor windings without a disconnecting means discharges through the windings.

Motor overload with a capacitor (460.9)

When a capacitor is connected on the load side of the motor overload device, the line current through the overload relay drops. The overload rating or setting must therefore be based on the improved power factor of the motor circuit, not the motor's full nameplate current. The 430.22 conductor sizing still uses the motor full-load current.

Example: a motor draws 40 A at 0.80 power factor. A capacitor on the load side of the overload raises the power factor of the circuit to 0.95. The current the overload sees becomes about 40×(0.80÷0.95)=33.740 \times (0.80 \div 0.95) = 33.7 A, so the overload must be selected for about 33.7 A, applying the 430.32 percentages to that value.

Grounding and marking

Capacitor cases must be connected to an EGC (460.10), and each capacitor must have a nameplate showing the manufacturer, rated voltage, frequency, kilovar or ampere rating, number of phases, and amount of liquid if filled with a combustible liquid (460.12).

Transformers over 1000 V (450.3(A))

Table 450.3(A) sets the maximum OCPD ratings for transformers over 1000 V, as a percentage of rated current:

Location and transformer impedancePrimary over 1000 V: circuit breakerPrimary over 1000 V: fuseSecondary over 1000 V: circuit breakerSecondary over 1000 V: fuseSecondary 1000 V or less: breaker or fuse
Any location, impedance 6% or less600%300%300%250%125%
Any location, impedance more than 6% and not more than 10%400%300%250%225%125%
Supervised location, primary protection only300%250%Not requiredNot requiredNot required

Where the required rating does not match a standard size, the next higher standard rating or setting is generally permitted under the table notes. The secondary 125% column for 1000 V or less matches the rule for low-voltage transformers in Table 450.3(B).

Indoor dry-type transformers rated over 35,000 V must be installed in a vault, and those over 112½ kVA generally need a transformer room of fire-resistant construction. Oil-insulated transformers installed indoors generally require a vault, with alternatives for less-flammable and nonflammable liquid-insulated units (450.21 to 450.27).

Medium-voltage wiring and equipment

Where the rules are in 2026

The 2026 NEC places over-1000-volt rules in Articles 245 (overcurrent protection), 265 to 268 (branch circuits, feeders, outside circuits, services), 270 (grounding and bonding), 305 (wiring methods), 315 (Type MV cable), and 495 (equipment). Article 495 replaced former Article 490.

Underground cover over 1000 V

The over-1000-volt cover table (Table 300.50 in the 2023 NEC, now in the Article 305 rules) requires, for circuits over 1000 V through 22 kV, 30 in. for direct-buried cables, 18 in. for nonmetallic raceways listed for direct burial, and 6 in. for RMC or IMC. Direct-buried cable over 22 kV through 40 kV needs 36 in. A warning ribbon at least 12 in. above direct-buried cables or nonmetallic raceways is required.

Type MV cable (Article 315)

Type MV cables are rated 2001 V to 35,000 V ac. Shielded MV cable has a semiconducting layer and a metallic shield that must be grounded, and terminations need stress-relief devices, such as stress cones or preformed terminations, to control the electric field where the shield ends. Splices and terminations must be made by qualified persons following the manufacturer's instructions.

Circuit-interrupting devices (Article 495)

DeviceKey requirements
Circuit breakersContinuous current rating at least the maximum continuous current; interrupting rating at least the maximum available fault current; closing rating at least the maximum asymmetrical fault current; voltage rating at least the maximum circuit voltage; indoor breakers in metal-enclosed units or fire-resistant cells
Power fuses and fuseholdersInterrupting rating at least the maximum fault current; voltage rating at least the maximum circuit voltage; expulsion fuses not used indoors, underground, or in metal enclosures unless identified for that use
Distribution cutoutsNot used indoors, underground, or in metal enclosures; located so the expelled gases do not endanger people
Load interrupter switchesInterrupter switches must be rated for the load they break; where used with fuses, they must be coordinated so the fuses clear faults the switch cannot interrupt

Listing (495.2, new in 2026): medium-voltage equipment rated up to 15,000 V must be listed beginning January 1, 2029, and equipment over 15,000 V up to 52,000 V beginning January 1, 2032. The delayed dates reflect the lack of testing laboratories for this equipment.

Worked example: a motor capacitor

A 50 hp, 460 V motor has a Table 430.250 full-load current of 65 A, so its branch-circuit conductors are rated at least 65×1.25=81.2565 \times 1.25 = 81.25 A (4 AWG copper, 85 A at 75°C). A capacitor rated 12 A is connected to the motor circuit conductors.

  1. 135% of the capacitor current: 12×1.35=16.212 \times 1.35 = 16.2 A.
  2. One-third of the motor circuit conductor ampacity: 85÷3=28.385 \div 3 = 28.3 A.
  3. The capacitor conductors must carry the larger value, 28.3 A, so 10 AWG copper (35 A at 75°C) is required.
Test Your Knowledge

A power-factor capacitor has a rated current of 30 A and is supplied by its own circuit. What is the minimum ampacity of its conductors?

A

40.5 A

B

30.0 A

C

37.5 A

D

52.5 A

Test Your Knowledge

How quickly must a 480 V capacitor's discharge means reduce the residual voltage to 50 V or less after it is disconnected?

A

Within 5 seconds

B

Within 1 minute

C

Within 5 minutes

D

Within 1 hour

Test Your Knowledge

A transformer over 1000 V with 5% impedance is protected on its primary by a circuit breaker, in any location. What is the maximum breaker rating as a percentage of rated primary current under Table 450.3(A)?

A

250%

B

300%

C

400%

D

600%

Sections you finish are checked off in the contents.