6.4 Commercial Lighting, Receptacle, Sign & Show-Window Loads (Table 120.42(A) & 120.44)
Key Takeaways
Table 120.42(A) lists general lighting unit loads such as 1.3 VA/ft² for offices, 1.9 for retail, 1.5 for schools and restaurants, 1.2 for warehouses, and 2.2 for manufacturing facilities.
Nondwelling receptacle outlets are calculated at 180 VA per single or multiple receptacle on one yoke.
Table 120.44 permits nondwelling receptacle loads to be taken at 100% of the first 10 kVA and 50% of the remainder.
In banks and office buildings, the receptacle load is the larger of the calculated 180 VA per outlet load after demand or 1 VA/ft² (120.14(K)).
Each required sign outlet adds at least 1,200 VA (120.14(F)), and show-window lighting adds 200 VA per linear foot of show window.
Commercial calculations on the exam
DLI's knowledge areas include commercial load calculations. Expect a building area, an occupancy type, and a list of receptacles, signs, show windows, and equipment. Build the load line by line, apply only the demand factors the Code allows, and convert to amperes with the correct voltage formula.
General lighting (120.42 and Table 120.42(A))
Multiply the floor area (outside dimensions, 120.5(C)) by the unit load for the occupancy:
| Occupancy | VA/ft² | Occupancy | VA/ft² |
|---|---|---|---|
| Automotive facility | 1.5 | Manufacturing facility | 2.2 |
| Convention center | 1.4 | Motion picture theater | 1.6 |
| Courthouse | 1.4 | Museum | 1.6 |
| Dormitory | 1.5 | Office | 1.3 |
| Exercise center | 1.4 | Parking garage | 0.3 |
| Fire station | 1.3 | Penitentiary | 1.2 |
| Gymnasium | 1.7 | Performing arts theater | 1.5 |
| Health care clinic | 1.6 | Police station | 1.3 |
| Hospital | 1.6 | Post office | 1.6 |
| Hotel and motel, including apartment houses without cooking provisions | 1.7 | Religious facility | 2.2 |
| Library | 1.5 | Restaurant | 1.5 |
| Retail | 1.9 | School or university | 1.5 |
| Sports arena | 1.1 | Town hall | 1.4 |
| Transportation | 1.2 | Warehouse | 1.2 |
| Workshop | 1.7 |
Table 120.45 demand factors then apply: 100% for most occupancies, with reductions only for dwellings, hotels and motels, and warehouses (first 12,500 VA at 100%, remainder at 50%). Section 120.42(B) allows a building designed to an adopted energy code to use the energy code's lighting power values under specific conditions, such as a power monitoring system.
Note
The 2023 edition had a note stating that the Table 220.42(A) unit loads already included the 125% continuous-load multiplier. The 2026 edition deleted that note without changing the values, and 120.5(E) states that load calculations do not apply the 125% factor. The 125% factor appears when sizing conductors and OCPDs for continuous loads (215.2, 215.3, 230.42). Read each exam question carefully for whether it asks for the calculated load or the minimum conductor ampacity.
Receptacles and outlets (120.14)
| Load | Value |
|---|---|
| General receptacle outlet (120.14(I)) | 180 VA for each single or multiple receptacle on one yoke; a single piece of equipment with four or more receptacles counts at least 90 VA per receptacle |
| Multioutlet assembly (120.14(H)) | 180 VA per 5 ft, or 180 VA per 1 ft where appliances are likely to be used at the same time |
| Banks and offices (120.14(K)) | The larger of the 180 VA per outlet load after demand factors or 1 VA/ft² |
| Sign outlet (120.14(F)) | At least 1,200 VA for each required sign or outline lighting outlet |
| Show windows (120.14(G), 120.43(A)) | 200 VA per linear foot, measured horizontally along the base |
| Track lighting (120.43(B)) | 150 VA per 2 ft of track, unless otherwise limited |
| Other outlets | Nameplate rating of the equipment, or 180 VA for other outlets |
Section 600.5(A) requires at least one sign outlet at each entrance to each tenant space of commercial buildings accessible to pedestrians, supplied by a branch circuit rated at least 20 A that supplies no other load.
Receptacle demand (Table 120.44)
Receptacle loads calculated at not more than 180 VA per outlet may be reduced:
| Portion of receptacle load | Demand factor |
|---|---|
| First 10 kVA or less | 100% |
| Remainder over 10 kVA | 50% |
Converting to amperes
- Single-phase 120/240 V:
- Three-phase: , such as at 208 V or at 480 V
Worked example: retail store
A 20,000 ft² retail store has 100 general-purpose receptacles, 60 linear feet of show window, and one sign outlet, supplied at 208Y/120 V, three-phase.
| Line | Calculation | VA |
|---|---|---|
| General lighting | 38,000 | |
| Show windows | 12,000 | |
| Sign outlet | minimum | 1,200 |
| Receptacles | ; | 14,000 |
| Total | 65,200 |
Feeder current: A. Conductor and OCPD sizing then apply 215.2 and 215.3 (or 230.42 for a service) to the continuous loads, together with any HVAC, motor, and equipment loads that a full calculation would add.
Worked example: office receptacles
A 15,000 ft² office has 60 general-purpose receptacles.
- Calculated: VA; with Table 120.44: VA.
- Minimum: VA.
- Use the larger value: 15,000 VA.
What is the general lighting load for a 12,000 ft² office building using Table 120.42(A)?
12,000 VA
22,800 VA
15,600 VA
36,000 VA
A commercial building has 150 general-purpose receptacles. What is the receptacle load after applying Table 120.44?
27,000 VA
13,500 VA
10,000 VA
18,500 VA
A store has 40 linear feet of show window. What load does the NEC require for the show-window lighting?
4,000 VA
8,000 VA
7,200 VA
1,200 VA
Sections you finish are checked off in the contents.