14.5 Appliances, Fixed Electric Space Heating & Deicing Equipment (Articles 422, 424 & 426)
Key Takeaways
A fixed storage-type water heater with a capacity of 120 gallons or less is a continuous load, so its branch-circuit rating must be at least 125% of the nameplate rating (422.13).
Appliances with resistance heating elements rated more than 48 A must have the elements subdivided, with each subdivided load not over 48 A and protected at not more than 60 A (422.11(F)).
Central heating equipment other than fixed electric space heating must be on an individual branch circuit; the 2026 NEC allows that circuit to also supply the required service receptacle and equipment lighting outlet (422.12).
A cord-and-plug connected waste disposer needs a cord 18 in. to 36 in. long, a built-in dishwasher 3 ft to 6.5 ft, a trash compactor 3 ft to 4 ft, and a range hood 18 in. to 4 ft (422.16(B)).
Fixed outdoor electric deicing and snow-melting equipment requires ground-fault protection of equipment, except mineral-insulated cable embedded in a noncombustible medium (426.28).
Appliances (Article 422)
Branch circuits and overcurrent protection
| Rule | Requirement |
|---|---|
| Branch-circuit rating (422.10) | Not less than the appliance's marked rating; motor-operated appliances follow Article 430 |
| Storage water heaters (422.13) | Fixed storage-type water heaters of 120 gallons or less are continuous loads: branch-circuit rating at least 125% of the nameplate |
| Single nonmotor appliance (422.11(E)) | OCPD not to exceed the rating marked on the appliance; if not marked, not over 20 A for an appliance rated 13.3 A or less, or not over 150% of its rated current for an appliance rated over 13.3 A, using the next higher standard size where needed |
| Resistance heating elements (422.11(F)) | Elements rated more than 48 A must be subdivided; each subdivided load may not exceed 48 A and must be protected at not more than 60 A |
| Water heater controls (422.47) | Each storage or instantaneous water heater needs a temperature-limiting means in addition to its control thermostat |
Example: a 4,500 W, 240 V storage water heater draws A. Its branch circuit must be rated at least A, so use a 25 A circuit with 10 AWG copper.
Central heating equipment (422.12)
Central heating equipment other than fixed electric space-heating equipment, such as a gas furnace, must be supplied by an individual branch circuit. Exceptions:
- auxiliary equipment directly associated with the heating equipment, such as a pump, valve, humidifier, or electrostatic air cleaner, may be on the same circuit; and
- new in the 2026 NEC: the circuit may also supply the HVAC service receptacle required by 210.63(A) and the lighting outlet for the service area required by 210.70(C).
DLI's 2026 review also describes the exception as broadened to cover similar associated equipment on the dedicated furnace circuit.
Cord-and-plug connection (422.16(B))
| Appliance | Cord length | Other conditions |
|---|---|---|
| In-sink waste disposer | 18 in. to 36 in. | Grounding-type attachment plug (unless double insulated); receptacle located to avoid cord damage and accessible |
| Built-in dishwasher | 3 ft to 6.5 ft, measured from the face of the plug to the plane of the rear of the appliance | Receptacle in the space adjacent to the space the dishwasher occupies, and accessible |
| Trash compactor | 3 ft to 4 ft, measured the same way | Receptacle in the space occupied by the appliance or adjacent to it, and accessible |
| Range hood, and microwave with integral range hood | 18 in. to 4 ft | Cord identified in the manufacturer's instructions; receptacle accessible and supplied by an individual branch circuit |
| Wall-mounted oven and counter-mounted cooking unit | As needed for servicing | Cord-and-plug or permanent connection |
Disconnecting means (422.31 to 422.34)
| Appliance | Disconnecting means |
|---|---|
| Rated not over 300 VA or ⅛ hp | The branch-circuit OCPD may serve |
| Rated over 300 VA | A switch or circuit breaker within sight of the appliance, or capable of being locked in the open position (110.25) |
| Motor-operated, over ⅛ hp | Within sight, or lockable where not within sight |
| Cord-and-plug connected | An accessible attachment plug and receptacle may serve |
| Unit switches with a marked "off" position | May serve where another means is provided, such as the service disconnect in a single-family dwelling |
Fixed electric space heating (Article 424)
| Rule | Requirement |
|---|---|
| Continuous load (424.4(B)) | Fixed electric space-heating equipment and its motors are a continuous load; branch circuits and conductors are sized at 125% |
| Branch circuits (424.4(A)) | Individual branch circuits may supply any size of fixed heating; branch circuits supplying two or more outlets are rated 15, 20, 25, or 30 A (in nonresidential occupancies, fixed infrared heating may be on circuits up to 50 A) |
| Disconnecting means (424.19) | A means to disconnect the heater, motor controller, and supplementary OCPDs from all ungrounded conductors, within sight or lockable |
| Overcurrent protection (424.22) | Resistance elements subdivided so each load does not exceed 48 A, protected at not more than 60 A |
| Baseboard heaters (424.9) | Listed baseboard heaters with factory-installed receptacles may serve as required receptacle outlets, but the receptacles may not be connected to the heater circuit; follow the listing, which often prohibits installing heaters below receptacle outlets |
| Thermostats (424.20) | Indicating thermostats with an off position must open all ungrounded conductors when off, and may serve as the required disconnecting means only if they can be locked in the open position |
Example: two 2,000 W, 240 V baseboard heaters on one circuit: A; A. A 20 A circuit is too small, so use a 25 A or 30 A circuit with conductors sized to match.
Heating cables in ceilings, floors, and walls (Article 424, Part V)
| Rule | Requirement |
|---|---|
| GFCI (424.44(E)) | GFCI protection for personnel is required for heating cables installed in electrically heated floors of bathrooms, kitchens, and hydromassage bathtub, spa, and hot tub locations |
| Wiring above heated ceilings (424.36) | Wiring contained in thermal insulation above a heated ceiling must be at least 2 in. above the ceiling and is treated as operating in a 50°C (122°F) ambient for ampacity correction; wiring above at least 2 in. of thermal insulation needs no correction |
| Wiring in walls (424.37) | Branch-circuit wiring in interior walls of rooms with heated ceilings is treated as operating at 40°C (104°F); wiring in exterior walls follows Article 300 and the 310.15 ampacity rules |
| Cable installation | Heating cables may not extend beyond the room or area they heat, may not be installed in closets or over walls or partitions that extend to the ceiling, and must keep specified clearances from boxes and luminaires |
Deicing, snow-melting, and pipeline heating (Articles 426 and 427)
Minnesota winters make heated sidewalks, ramps, roof and gutter deicing cable, and heat-traced pipes common:
- GFPE (426.28): ground-fault protection of equipment is required for fixed outdoor electric deicing and snow-melting equipment, except equipment using mineral-insulated, metal-sheathed cable embedded in a noncombustible medium. A 30 mA equipment protective device is typical.
- Pipeline and vessel heating (427.22): GFPE is required for electric heat tracing, with limited exceptions for industrial establishments with qualified maintenance.
- Branch circuits: deicing and snow-melting equipment is a continuous load, sized at 125%.
- Expansion and contraction (Article 426): embedded heating cables and their leads must be protected where they pass through expansion joints and where they leave the embedding material, so movement of the slab does not damage them.
- Disconnecting means (426.50): a means to disconnect all ungrounded conductors simultaneously; it must be of the indicating type and lockable in the open position, and the branch-circuit switch or breaker may serve where readily accessible to the user.
- Conductive pavement heating (new Part VI of Article 426, 2026): systems operating at not more than 30 V RMS or 60 V DC, used for snow and ice melting.
- Outdoor receptacles: a receptacle that is not readily accessible and supplies only a dedicated snow-melting, deicing, or pipeline heating circuit is exempt from the dwelling GFCI requirement for outdoor receptacles, because the equipment already has GFPE.
Worked example: a garage with a heated driveway
A new home has a 4,500 W water heater, a gas furnace, and a 9,600 W heated driveway at 240 V.
- Water heater: 25 A circuit as calculated above.
- Furnace: individual branch circuit, which may also feed the required service receptacle and the equipment-area light under the 2026 exception.
- Driveway: A; continuous load, so A. Provide a 50 A circuit with GFPE, unless it uses MI cable embedded in concrete, and a lockable disconnecting means.
A 5,500 W, 240 V storage water heater with a 50-gallon tank is installed. What is the minimum branch-circuit rating?
22.9 A
28.6 A
34.4 A
45.8 A
A built-in dishwasher is cord-and-plug connected. What cord length does 422.16(B)(2) require?
3 ft to 6.5 ft
18 in. to 36 in.
18 in. to 4 ft
3 ft to 4 ft
What protection does 426.28 require for fixed outdoor electric snow-melting cable embedded in a concrete driveway, when the cable is not MI cable?
A Class A GFCI receptacle
An AFCI circuit breaker at the panel
Ground-fault protection of equipment
No additional protection beyond the breaker