8.3 OCPD Location, Breaker Voltage Ratings, Handle Ties & Arc Energy Reduction

Key Takeaways

  • OCPDs must be readily accessible and installed so the center of the grip of the operating handle in its highest position is not more than 6 ft 7 in. above the floor or working platform (240.24(A)).

  • Overcurrent devices may not be located in the bathrooms of dwelling units, dormitory units, or guest rooms, near easily ignitible material such as clothes closets, or over the steps of a stairway (240.24(D) to (F)).

  • A slash-rated breaker (such as 120/240 V) may be used only where no conductor exceeds the lower value to ground and no two conductors exceed the higher value, so it cannot be used on a corner-grounded or ungrounded delta system (240.85).

  • Circuit breakers rated or adjustable to 1200 A or more must use an arc energy reduction method such as zone-selective interlocking or an energy-reducing maintenance switch, and the method must be performance tested when installed (240.87).

  • An OCPD may not be placed in a grounded conductor unless it opens all conductors of the circuit at the same time (240.22).

Last updated: October 2026

Where overcurrent devices may be installed (240.24)

RuleRequirement
Accessibility (A)Readily accessible, with the center of the operating handle grip in its highest position not more than 6 ft 7 in. above the floor or working platform; exceptions include busway plug-in devices, supplementary OCPDs, devices next to the motors or equipment they supply, and certain service and feeder devices
Occupancy (B)Each occupant must have ready access to all OCPDs protecting the conductors supplying that occupancy, unless electrical maintenance is under continuous building management supervision; guest rooms of hotels and motels follow similar rules
Physical damage (C)Not exposed to physical damage
Ignitible material (D)Not in the vicinity of easily ignitible material, such as in clothes closets
Bathrooms (E)Not in bathrooms of dwelling units, dormitory units, or guest rooms and guest suites of hotels and motels; a 2026 exception allows adding OCPDs to an existing panelboard in a bathroom that was installed in compliance with an earlier Code edition
Stairways (F)Not located over the steps of a stairway

240.22 Grounded conductor: an OCPD may not be connected in series with a grounded conductor unless it opens all conductors of the circuit simultaneously, or unless it is a motor overload device permitted by Article 430.

Circuit breakers as overcurrent protection

Handle ties and common trip (240.15(B))

Single-pole breakers with identified handle ties may protect each ungrounded conductor in these cases:

  • multiwire branch circuits that serve only line-to-neutral loads;
  • line-to-line loads on single-phase circuits; and
  • line-to-line loads on 3-phase, 4-wire systems or 5-wire, 2-phase systems, where the system has a grounded neutral and the voltage to ground does not exceed the breakers' rating.

Handle ties make the breakers open together manually. Where a load requires all ungrounded conductors to trip together on a fault, use a multipole common-trip breaker.

Marking (240.83)

Breakers must be durably marked with their ampere rating, and with their interrupting rating where it is other than 5000 A. A breaker used as a switch for 120 V or 277 V fluorescent lighting must be marked SWD or HID; a breaker used to switch high-intensity discharge lighting must be marked HID.

Voltage ratings (240.85)

Breaker markingWhere it may be used
Straight rating, such as 240 V or 480 VAny circuit where the nominal voltage between any two conductors does not exceed the rating
Slash rating, such as 120/240 V or 480Y/277 VOnly solidly grounded circuits where the voltage from any conductor to ground does not exceed the lower value and the voltage between any two conductors does not exceed the higher value

A 480Y/277 V slash-rated breaker is correct on a 480Y/277 V wye system. It may not be used on a 480 V ungrounded or corner-grounded delta system, because a conductor can be 480 V to ground. A 120/240 V slash-rated breaker on the high leg of a 120/240 V, 4-wire delta system would see about 208 V to ground, which exceeds 120 V, so a straight-rated 240 V breaker is required there.

Other circuit breaker rules

  • 240.8 Parallel devices: fuses and circuit breakers may be connected in parallel only where factory assembled in parallel and listed as a unit.
  • 240.86 Series ratings: a tested combination may be used where a downstream breaker's interrupting rating is lower than the available fault current, with the 110.22(C) field marking.
  • 240.13 and 215.10 GFPE for buildings and feeders: like 230.95, a building or feeder disconnect rated 1000 A or more on a solidly grounded wye system over 150 V to ground needs GFPE, unless it is provided on the supply side.

Arc energy reduction (240.87 and 240.67)

Where the highest continuous current trip setting that a circuit breaker is rated for, or can be adjusted to, is 1200 A or higher, the documentation must show the breaker's location and the arc energy reduction method used. Methods include:

  1. zone-selective interlocking;
  2. differential relaying;
  3. an energy-reducing maintenance switch with a local status indicator;
  4. an energy-reducing active arc-flash mitigation system;
  5. an instantaneous trip setting below the available arcing current;
  6. an instantaneous override set below the available arcing current; or
  7. an approved equivalent means.

The arc energy reduction system must be performance tested by primary current injection or another approved method when first installed, and a written record kept. Section 240.67 sets a parallel rule for fuses rated 1200 A or more: the fuse must clear the available arcing current in 0.07 second or less, or another listed method must be used.

Selective coordination

Certain systems require that only the OCPD closest to a fault opens, so critical loads stay energized. Selective coordination is required for emergency systems (700.32), legally required standby systems (701.32), critical operations power systems (708.54), elevator circuits with more than one driving machine disconnect on a feeder (620.62). Health care essential electrical systems have their own coordination rules in Article 517, which the 2026 NEC extended to Type 2 systems. The 2026 NEC also adds rules requiring elevator coordination to be re-evaluated when overcurrent devices are replaced or the system is modified. An engineer usually selects the devices, but the electrician must install the specified fuse classes, breaker frames, and trip settings exactly.

Worked example: choosing the right breaker

A plant has three systems: a 480Y/277 V wye feeding lighting panels, a 480 V corner-grounded delta feeding a press line, and a 120/240 V high-leg delta in an old shop.

  1. 480Y/277 V lighting panel: 480Y/277 V slash-rated breakers are permitted: 277 V to ground, 480 V between conductors.
  2. 480 V corner-grounded delta: two ungrounded conductors are 480 V to ground, so straight 480 V-rated breakers are required.
  3. 120/240 V high-leg delta: the B phase (high leg) is about 208 V to ground. A 120/240 V slash-rated breaker on that phase violates 240.85; use breakers with a straight 240 V rating for circuits that include the high leg.
Test Your Knowledge

A homeowner wants a new panelboard installed in the master bathroom of a single-family home. What does 240.24(E) require?

A

It is permitted if the panelboard is at least 6 ft from the tub or shower

B

It is permitted if all breakers are GFCI type

C

It is permitted if the bathroom has a ducted exhaust fan

D

It is not permitted in a dwelling unit bathroom

Test Your Knowledge

Which system may use circuit breakers with a 480Y/277 V slash rating?

A

A 480 V ungrounded delta system

B

A solidly grounded 480Y/277 V wye system

C

A 480 V corner-grounded delta system

D

Any 480 V system, regardless of grounding

Test Your Knowledge

At what circuit breaker trip rating does 240.87 require an arc energy reduction method?

A

400 A or higher, based on the breaker frame rating

B

800 A or higher, based on the service rating

C

1200 A or higher, based on its highest possible trip setting

D

2000 A or higher, based on the available fault current