12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)

Key Takeaways

  • Chapter 9, Table 1 limits conductor fill to 53% for one conductor, 31% for two conductors, and 40% for more than two conductors.

  • Conduit or tubing nipples not longer than 24 in. between boxes or enclosures may be filled to 60% of their cross-sectional area, and ampacity adjustment factors do not apply to them.

  • DLI's exam guide answers 32 conductors for 10 AWG THWN in trade size 1½ Schedule 80 PVC, read from Annex C Table C.10.

  • DLI's mixed-conductor example totals 1.1880 in² of conductor area and requires trade size 2 rigid metal conduit.

  • When calculating the number of same-size conductors, round up to the next whole number only if the decimal is 0.8 or more.

Last updated: October 2026

What DLI expects

DLI's exam guide includes a full section on conduit fill. It explains that Annex C has tables for each type of conduit and tubing, listing the maximum number of conductors of one size and insulation type, for raceways longer than 24 in. For mixed sizes or insulation types, it walks through a three-step calculation using Chapter 9, Tables 1, 4, and 5.

The Chapter 9 tables

TableWhat it gives
Table 1Percent of cross section allowed: 53% for 1 conductor, 31% for 2, 40% for over 2
Table 4Dimensions and allowable fill areas (in²) for each raceway type and trade size, including columns for 40%, 53%, 31%, and 60%
Table 5Approximate areas (in²) of insulated conductors by type and size, such as THHN, THW, XHHW, RHH
Table 5ACompact conductor areas
Table 8Conductor properties, including the area of bare conductors
Annex CMaximum number of same-size, same-type conductors for each raceway type and trade size

Key notes to Chapter 9 tables

  • Equipment grounding and bonding conductors are counted in fill, using their actual dimensions (Table 5 for insulated, Table 8 for bare).
  • Nipples not longer than 24 in. between boxes, cabinets, and similar enclosures may be filled to 60%, and the ampacity adjustment factors of Table 310.15(C)(1) do not apply to them.
  • A multiconductor cable or flexible cord counts as one conductor, using its overall area; for an elliptical cable, use a circle based on the major diameter.
  • When calculating the number of same-size conductors, use the next higher whole number only if the result has a decimal of 0.8 or more. DLI's guide calls this provision Note 8 and says it must be applied if you calculate instead of using Annex C.
  • The fill limits apply to complete raceway systems, not to short sections used only to protect cables from physical damage.

Method 1: same size and type (Annex C)

DLI example: how many 10 AWG THWN conductors may be installed in trade size 1½ Schedule 80 PVC?

  1. Use Table C.10 (Schedule 80 PVC).
  2. Find the THWN section and the 10 AWG row.
  3. Read the trade size 1½ column: 32 conductors.

If you calculate instead, divide the 40% area of the raceway (Table 4) by the area of one conductor (Table 5) and apply the 0.8 rounding rule.

Method 2: mixed conductors (Tables 1, 4, and 5)

DLI example: what minimum trade size of rigid metal conduit is needed for six 3 AWG THW, six 6 AWG THWN, one 8 AWG THWN, and twelve 14 AWG XHHW conductors?

  1. Percent fill: more than two conductors, so 40% (Table 1).
  2. Conductor areas (Table 5):
ConductorsArea each (in²)Total (in²)
6 × 3 AWG THW0.11340.6804
6 × 6 AWG THWN0.05070.3042
1 × 8 AWG THWN0.03660.0366
12 × 14 AWG XHHW0.01390.1668
Total1.1880
  1. Raceway (Table 4, RMC, 40% column): trade size 1½ allows 0.829 in² (too small), and trade size 2 allows 1.363 in². The answer is trade size 2.

Common Table 5 areas (in²)

SizeTHHN/THWNTHW, THHW, THW-2XHHW
14 AWG0.00970.01390.0139
12 AWG0.01330.01810.0181
10 AWG0.02110.02430.0243
8 AWG0.03660.04370.0437
6 AWG0.05070.07260.0590
4 AWG0.08240.09730.0814
3 AWG0.09730.11340.0962
2 AWG0.11580.13330.1146
1 AWG0.15620.19010.1534
1/0 AWG0.18550.22230.1825

Common Table 4 values, 40% fill (in²)

Trade sizeEMTRMCSchedule 40 PVCSchedule 80 PVC
½0.1220.1250.1140.087
¾0.2130.2200.2030.164
10.3460.3550.3330.275
1¼0.5980.6100.5810.495
1½0.8140.8290.7940.684
21.3421.3631.3161.150

Always use the table for the actual raceway type: Schedule 80 PVC has a thicker wall and much less area than EMT of the same trade size.

Worked example: EMT with an equipment grounding conductor

Size EMT for three 4 AWG THHN conductors and one 8 AWG insulated THHN EGC.

  1. Four conductors, so 40%.
  2. Areas: 3×0.0824=0.24723 \times 0.0824 = 0.2472 and 1×0.0366=0.03661 \times 0.0366 = 0.0366; total 0.2838 in².
  3. EMT 40% column: ¾ = 0.213 (too small); 1 = 0.346 (enough). Use trade size 1 EMT.
Test Your Knowledge

What maximum percentage of a conduit's cross-sectional area may be filled with three or more conductors under Chapter 9, Table 1?

A

31%

B

53%

C

40%

D

60%

Test Your Knowledge

A raceway calculation shows that 9.81 conductors of the same size would fit. How many conductors may be installed?

A

9

B

11

C

8

D

10

Test Your Knowledge

What is the smallest trade size of EMT for six 6 AWG THHN conductors and one 10 AWG THHN equipment grounding conductor?

A

¾

B

1

C

1¼

D

1½

Sections you finish are checked off in the contents.