12.5 Conduit & Tubing Fill Calculations (Chapter 9 & Annex C)
Key Takeaways
Chapter 9, Table 1 limits conductor fill to 53% for one conductor, 31% for two conductors, and 40% for more than two conductors.
Conduit or tubing nipples not longer than 24 in. between boxes or enclosures may be filled to 60% of their cross-sectional area, and ampacity adjustment factors do not apply to them.
DLI's exam guide answers 32 conductors for 10 AWG THWN in trade size 1½ Schedule 80 PVC, read from Annex C Table C.10.
DLI's mixed-conductor example totals 1.1880 in² of conductor area and requires trade size 2 rigid metal conduit.
When calculating the number of same-size conductors, round up to the next whole number only if the decimal is 0.8 or more.
What DLI expects
DLI's exam guide includes a full section on conduit fill. It explains that Annex C has tables for each type of conduit and tubing, listing the maximum number of conductors of one size and insulation type, for raceways longer than 24 in. For mixed sizes or insulation types, it walks through a three-step calculation using Chapter 9, Tables 1, 4, and 5.
The Chapter 9 tables
| Table | What it gives |
|---|---|
| Table 1 | Percent of cross section allowed: 53% for 1 conductor, 31% for 2, 40% for over 2 |
| Table 4 | Dimensions and allowable fill areas (in²) for each raceway type and trade size, including columns for 40%, 53%, 31%, and 60% |
| Table 5 | Approximate areas (in²) of insulated conductors by type and size, such as THHN, THW, XHHW, RHH |
| Table 5A | Compact conductor areas |
| Table 8 | Conductor properties, including the area of bare conductors |
| Annex C | Maximum number of same-size, same-type conductors for each raceway type and trade size |
Key notes to Chapter 9 tables
- Equipment grounding and bonding conductors are counted in fill, using their actual dimensions (Table 5 for insulated, Table 8 for bare).
- Nipples not longer than 24 in. between boxes, cabinets, and similar enclosures may be filled to 60%, and the ampacity adjustment factors of Table 310.15(C)(1) do not apply to them.
- A multiconductor cable or flexible cord counts as one conductor, using its overall area; for an elliptical cable, use a circle based on the major diameter.
- When calculating the number of same-size conductors, use the next higher whole number only if the result has a decimal of 0.8 or more. DLI's guide calls this provision Note 8 and says it must be applied if you calculate instead of using Annex C.
- The fill limits apply to complete raceway systems, not to short sections used only to protect cables from physical damage.
Method 1: same size and type (Annex C)
DLI example: how many 10 AWG THWN conductors may be installed in trade size 1½ Schedule 80 PVC?
- Use Table C.10 (Schedule 80 PVC).
- Find the THWN section and the 10 AWG row.
- Read the trade size 1½ column: 32 conductors.
If you calculate instead, divide the 40% area of the raceway (Table 4) by the area of one conductor (Table 5) and apply the 0.8 rounding rule.
Method 2: mixed conductors (Tables 1, 4, and 5)
DLI example: what minimum trade size of rigid metal conduit is needed for six 3 AWG THW, six 6 AWG THWN, one 8 AWG THWN, and twelve 14 AWG XHHW conductors?
- Percent fill: more than two conductors, so 40% (Table 1).
- Conductor areas (Table 5):
| Conductors | Area each (in²) | Total (in²) |
|---|---|---|
| 6 × 3 AWG THW | 0.1134 | 0.6804 |
| 6 × 6 AWG THWN | 0.0507 | 0.3042 |
| 1 × 8 AWG THWN | 0.0366 | 0.0366 |
| 12 × 14 AWG XHHW | 0.0139 | 0.1668 |
| Total | 1.1880 |
- Raceway (Table 4, RMC, 40% column): trade size 1½ allows 0.829 in² (too small), and trade size 2 allows 1.363 in². The answer is trade size 2.
Common Table 5 areas (in²)
| Size | THHN/THWN | THW, THHW, THW-2 | XHHW |
|---|---|---|---|
| 14 AWG | 0.0097 | 0.0139 | 0.0139 |
| 12 AWG | 0.0133 | 0.0181 | 0.0181 |
| 10 AWG | 0.0211 | 0.0243 | 0.0243 |
| 8 AWG | 0.0366 | 0.0437 | 0.0437 |
| 6 AWG | 0.0507 | 0.0726 | 0.0590 |
| 4 AWG | 0.0824 | 0.0973 | 0.0814 |
| 3 AWG | 0.0973 | 0.1134 | 0.0962 |
| 2 AWG | 0.1158 | 0.1333 | 0.1146 |
| 1 AWG | 0.1562 | 0.1901 | 0.1534 |
| 1/0 AWG | 0.1855 | 0.2223 | 0.1825 |
Common Table 4 values, 40% fill (in²)
| Trade size | EMT | RMC | Schedule 40 PVC | Schedule 80 PVC |
|---|---|---|---|---|
| ½ | 0.122 | 0.125 | 0.114 | 0.087 |
| ¾ | 0.213 | 0.220 | 0.203 | 0.164 |
| 1 | 0.346 | 0.355 | 0.333 | 0.275 |
| 1¼ | 0.598 | 0.610 | 0.581 | 0.495 |
| 1½ | 0.814 | 0.829 | 0.794 | 0.684 |
| 2 | 1.342 | 1.363 | 1.316 | 1.150 |
Always use the table for the actual raceway type: Schedule 80 PVC has a thicker wall and much less area than EMT of the same trade size.
Worked example: EMT with an equipment grounding conductor
Size EMT for three 4 AWG THHN conductors and one 8 AWG insulated THHN EGC.
- Four conductors, so 40%.
- Areas: and ; total 0.2838 in².
- EMT 40% column: ¾ = 0.213 (too small); 1 = 0.346 (enough). Use trade size 1 EMT.
What maximum percentage of a conduit's cross-sectional area may be filled with three or more conductors under Chapter 9, Table 1?
31%
53%
40%
60%
A raceway calculation shows that 9.81 conductors of the same size would fit. How many conductors may be installed?
9
11
8
10
What is the smallest trade size of EMT for six 6 AWG THHN conductors and one 10 AWG THHN equipment grounding conductor?
¾
1
1¼
1½
Sections you finish are checked off in the contents.