7.2 Outside Feeders & Separate Buildings (Article 225 & 250.32)

Key Takeaways

  • A building or structure supplied by a feeder may have only one feeder or branch circuit supplying it, unless 225.30 permits more, such as for fire pumps, emergency or standby systems, or different voltage characteristics.

  • Each building must have a disconnecting means for all ungrounded supply conductors, either inside nearest the point of entrance or outside on or within sight of the building (225.31).

  • At a separate building supplied by a feeder, the equipment grounding conductor run with the feeder is connected to the building's grounding electrode system, and the neutral is not bonded to the enclosure (250.32(B)).

  • Overhead feeder conductors must be at least 10 AWG copper for spans up to 50 ft and 8 AWG copper for longer spans, unless supported by a messenger (225.6(A)).

  • Overhead feeder conductors need 12 ft of clearance over residential driveways at 300 V or less to ground and 18 ft over public streets and roads subject to truck traffic (225.18).

Last updated: October 2026

Why separate buildings are tested

Minnesota homes have detached garages and shops, and farms have many outbuildings. DLI's knowledge areas include outside branch circuits and feeders and grounding of separate buildings. Most errors come from treating a feeder-supplied building like a service: bonding the neutral at the second panel, or running only three wires.

Number of supplies (225.30)

A building or structure supplied by a feeder or branch circuit may have only one feeder or branch circuit supplying it, unless 225.30 permits additional supplies for:

  • special conditions: fire pumps, emergency systems, legally required and optional standby systems, parallel power production, and systems designed for multiple sources for enhanced reliability;
  • special occupancies: by special permission, for multiple-occupancy buildings without space for supply equipment accessible to all occupants, or very large buildings;
  • capacity requirements: where the load exceeds what one supply can provide; and
  • different characteristics: different voltages, frequencies, or phases, or different uses.

Where a building has more than one supply, 225.37 requires a permanent plaque or directory at each disconnect location identifying all other supplies and the area served by each.

Disconnecting means (225.31 to 225.41)

RuleRequirement
Required disconnect (225.31(A))A means to disconnect all ungrounded conductors that supply or pass through the building
Location (225.31(B))Readily accessible, either inside nearest the point of entrance of the conductors or outside; the 2026 NEC states that an outside disconnect must be on or within sight of the building (110.29)
Number (225.33)Not more than six switches or sets of circuit breakers for each supply, grouped at one location (225.34)
Rating and type (225.36)Suitable for use as service equipment; for garages and outbuildings on residential property, a snap switch or a set of 3-way or 4-way snap switches is permitted
Emergency disconnect (225.41)One- and two-family dwellings supplied by a feeder need an emergency disconnecting means in a readily accessible outdoor location on or within sight of the dwelling; the 2026 NEC clarifies that one disconnect can satisfy both 225.31 and 225.41

"Within sight" means visible and not more than 50 ft away (110.29).

Outdoor lighting (225.7)

Part I of Article 225 also covers outdoor lighting supplied by outside branch circuits and feeders:

  • Common neutral (225.7(B)): where outdoor lighting circuits share a neutral, its ampacity may not be less than the maximum net computed load current between the neutral and all ungrounded conductors connected to any one phase.
  • 277 V to ground (225.7(C)): circuits over 120 V between conductors and not over 277 V to ground may supply luminaires lighting outdoor areas of industrial establishments, office buildings, schools, stores, and other commercial or public buildings. This is how 480Y/277 V parking-lot lighting is fed.
  • Up to 1000 V between conductors (225.7(D)): circuits over 277 V to ground and not over 1000 V between conductors may supply the auxiliary equipment of electric-discharge lamps where 210.6 allows it, such as luminaires on poles at least 22 ft high for parking lots, roads, and athletic fields, or at least 18 ft high on other structures such as tunnels.

Overhead feeder spans

RuleRequirement
Conductor size (225.6(A))At least 10 AWG copper (8 AWG aluminum) for spans up to 50 ft; 8 AWG copper (6 AWG aluminum) for longer spans, unless supported by a messenger wire
Clearance from ground (225.18)10 ft over areas accessible to pedestrians only, at the electric service entrance, for cables at 150 V to ground or less; 12 ft over residential property and driveways and commercial areas not subject to truck traffic, at 300 V to ground or less; 15 ft for those areas above 300 V to ground; 18 ft over public streets, alleys, roads, parking areas subject to truck traffic, and nonresidential driveways; 24.5 ft over railroad tracks
Clearance from buildings (225.19)Generally 8 ft 6 in. above roofs, with exceptions similar to services; 3 ft from windows that open, doors, porches, balconies, ladders, stairs, and fire escapes
Vegetation (225.26)Trees and other vegetation may not be used to support overhead conductor spans

Underground feeders

An underground feeder to a detached building follows the Article 300 burial depths, which the 2026 NEC moved from 300.5 to 300.7. Conductors in underground raceways are in a wet location and need wet-rated insulation such as THWN-2 or XHHW-2. Raceways entering a building from underground must be sealed or plugged where moisture could contact live parts.

Grounding and bonding at the separate building (250.32)

250.32(A) Grounding electrode: each building supplied by a feeder or branch circuit needs a grounding electrode system per Part III of Article 250, connected to the building disconnecting means. A building supplied by a single branch circuit (including a multiwire branch circuit) with an equipment grounding conductor does not need an electrode.

250.32(B)(1) Equipment grounding conductor: the supply must include an equipment grounding conductor sized from Table 250.122. It connects to the building disconnecting means and to the grounding electrode system. The grounded (neutral) conductor may not be connected to the equipment grounding conductor or to the grounding electrodes at the second building. In practice:

  • run four wires for a 120/240 V feeder: two ungrounded conductors, a neutral, and an EGC;
  • use a panelboard with an isolated neutral bar, and remove or do not install the bonding screw or strap;
  • land the EGC and the grounding electrode conductor on the equipment grounding bar.

An exception allows existing installations, made under earlier Code editions that permitted it, to keep using the grounded conductor for grounding where no EGC was run, there are no continuous metallic paths between buildings, and no ground-fault protection of equipment is installed at the supply. New work never uses this method.

250.32(E) Grounding electrode conductor: sized from 250.66 based on the largest ungrounded supply conductor.

Bonding the neutral at the second building creates parallel paths, so normal neutral current flows on the EGC, metal raceways, water pipes, and the earth. This creates shock hazards and stray voltage, a serious problem around livestock.

Worked example: detached garage

A 60 A, 120/240 V feeder supplies a detached garage from the house panel, underground in PVC.

  1. Conductors: 6 AWG copper THWN-2 for the two ungrounded conductors and the neutral (65 A at 75°C), protected at 60 A.
  2. EGC: Table 250.122 for a 60 A OCPD is 10 AWG copper.
  3. Disconnect: a main breaker or switch at the garage, suitable as service equipment, or a snap switch if the garage is on residential property and the load permits.
  4. Electrode: install a grounding electrode system, such as a ground rod supplemented by a second rod at least 6 ft away, unless one rod measures 25 Ω or less.
  5. GEC: for 6 AWG copper supply conductors, Table 250.66 gives 8 AWG copper; a GEC connected only to rods need not be larger than 6 AWG copper.
  6. Neutral: isolated from the enclosure at the garage panel.
Test Your Knowledge

A new 100 A feeder supplies a detached shop on the same property. Which installation meets 250.32(B)?

A

Four wires, with the neutral isolated and the EGC tied to the shop's electrode system

B

Three wires (two ungrounded and a neutral), with the neutral bonded to the shop panel and a ground rod

C

Four wires, with the neutral and EGC both bonded to the shop panel enclosure

D

Two ungrounded conductors and a ground rod only, with no neutral or EGC

Test Your Knowledge

What is the minimum size of copper overhead feeder conductors for a 75 ft span between a house and a barn, with no messenger wire?

A

12 AWG

B

10 AWG

C

6 AWG

D

8 AWG

Test Your Knowledge

An overhead 120/240 V feeder crosses a residential driveway to reach a detached garage. What is the minimum clearance above the driveway under 225.18?

A

10 ft

B

12 ft

C

15 ft

D

18 ft

Sections you finish are checked off in the contents.