21.1 Remote-Control, Signaling & Power-Limited Circuits: Class 1, 2 & 3 (2026 Articles 206, 720–725)
Key Takeaways
In the 2026 NEC, general rules for limited-energy wiring methods are in Article 720, power sources in 721, cables in 722, and raceways and cable trays in 723, while Class 2 and 3 circuit rules are in Article 725.
Class 2 and Class 3 circuits must be supplied by a listed power source, such as a Class 2 transformer or power supply marked for the class.
Class 2 and 3 conductors may not share a raceway, cable, enclosure, or cable tray with electric light, power, Class 1, or nonpower-limited fire alarm conductors unless separated by a barrier or a permitted exception applies.
Accessible portions of abandoned Class 2 and Class 3 cables must be removed, unless tagged for future use.
Remote-control circuits for safety-control equipment are classified as Class 1 when their failure would introduce a direct fire or life hazard; room thermostats for household heating and cooling are not safety-control equipment.
The 2026 reorganization
DLI's knowledge areas list Class 1, 2, and 3 remote-control, signaling, and power-limited circuits and the general requirements for limited-energy system wiring methods. The 2026 NEC moved these rules into a new structure so the same requirements are not repeated in every article:
| Article | Covers |
|---|---|
| 206 | Non-power-limited remote-control and signaling circuits (formerly Class 1 non-power-limited) |
| 720 | General requirements for limited-energy system wiring methods and materials |
| 721 | Power sources for limited-energy systems |
| 722 | Limited-energy cables: listing, marking, and permitted uses and substitutions |
| 723 | Raceways, cable routing assemblies, and cable trays for limited-energy systems |
| 724 | Class 1 power-limited circuits |
| 725 | Class 2 and Class 3 power-limited circuits |
| 742 | Overvoltage protection of limited-energy systems |
| 750 | Grounding and bonding of limited-energy systems |
Chapter 8 now covers only communications circuits outside and entering buildings; inside the building, communications wiring follows the Chapter 7 limited-energy rules.
Circuit classes
| Class | What limits it | Typical uses |
|---|---|---|
| Class 1 non-power-limited (Article 206) | Ordinary OCPDs; up to 600 V | Motor control circuits, relay coils, interlocks |
| Class 1 power-limited (Article 724) | Source limited to 30 V and 1000 VA | Some control circuits |
| Class 2 (Article 725) | Listed power source limits voltage and power, so the circuit is safe from fire and, at lower voltages, from shock | Thermostats, doorbells, security, low-voltage lighting controls, PoE |
| Class 3 (Article 725) | Listed source with higher voltage limits than Class 2; safe from fire but may present a shock hazard | Some sound systems, nurse call, certain controls |
Class 1 rules
- Conductors: 18 AWG and 16 AWG Class 1 conductors are permitted where protected at 7 A and 10 A; larger conductors follow Table 310.16 and 240.4.
- Same raceway with power: Class 1 circuit conductors may share a raceway or enclosure with power-supply conductors only where functionally associated with the equipment they supply.
- Safety-control circuits: remote-control circuits for safety-control equipment are Class 1 where failure of the equipment to operate would introduce a direct fire or life hazard. Where physical damage to such circuits would create a hazard, all their conductors must be in RMC, IMC, PVC, EMT, Type MI or MC cable, or otherwise protected. Room thermostats, water temperature regulators, and similar household heating and air-conditioning controls are not safety-control equipment.
Class 2 and Class 3 circuits
Power sources (Article 721)
A Class 2 or Class 3 circuit must be supplied by a listed power source: a Class 2 or 3 transformer, a Class 2 or 3 power supply, other listed equipment marked to identify the Class 2 or 3 power source, listed ITE equipment, or a dry-cell battery for Class 2. The outputs of Class 2 and 3 power sources may not be paralleled or otherwise interconnected unless listed for that use, because combining them can exceed the class limits.
Power source limits (Chapter 9, Tables 11(A) and 11(B))
Chapter 9 Table 11(A) (ac) and Table 11(B) (dc) set the maximum voltage, current, and power for Class 2 and Class 3 power sources. Each table has two halves: inherently limited sources, which need no overcurrent protection, and sources not inherently limited, which require overcurrent protection. Two values are worth remembering: an inherently limited Class 2 ac source over 20 V and up to 30 V has a maximum nameplate rating of 100 VA, and an inherently limited Class 3 ac source over 30 V and up to 100 V is also limited to 100 VA. Equipment listed and marked as Class 2 or Class 3 already meets these limits, so in the field you verify the marking rather than calculating.
Separation from other systems
- Class 2 and 3 conductors may not be placed in any raceway, cable, compartment, outlet box, junction box, or cable tray with conductors of electric light, power, Class 1, nonpower-limited fire alarm, or medium-power network-powered broadband circuits, unless separated by a barrier or the Code specifically permits it.
- In enclosures where power conductors enter only to connect to the same equipment, Class 2 and 3 conductors must keep at least ¼ in. of separation or be routed to avoid the power conductors.
- In other installations, such as open wiring in a building, Class 2 and 3 conductors must be kept at least 2 in. from power, Class 1, and NPLFA conductors, unless the power conductors are in raceway or in metal-sheathed, metal-clad, nonmetallic-sheathed, Type TC, or Type UF cable, or the Class 2 and 3 conductors are in raceway.
- Class 2 and Class 3 circuits may share a cable or raceway with each other where the Class 2 conductors are insulated for Class 3 use, and with communications and power-limited fire alarm circuits where permitted.
Cable types and substitutions (Article 722)
| Space | Class 2 / Class 3 cable | May substitute |
|---|---|---|
| Plenums and other spaces for environmental air | CL2P / CL3P | CMP (and CL3P for CL2P) |
| Risers | CL2R / CL3R | Plenum types above, CMR, and CL3R for CL2R |
| General use | CL2 / CL3 | Any of the above, CM (CMG), PLTC, and CL3 for CL2 |
| Limited use (dwellings, raceways, and short exposed lengths) | CL2X / CL3X | Any of the above, and CMX |
Class 3 cable may substitute for Class 2 cable, and a higher-rated cable (plenum over riser over general purpose) may always substitute for a lower-rated one, never the reverse.
Power over Ethernet and other power on data cable
Class 2 and Class 3 circuits that carry power over communications cables, such as PoE to cameras, access points, and LED luminaires, have ampacity limits that depend on conductor size, temperature rating, and bundle size. For larger bundles and higher power levels, use cables marked "-LP" (limited power) with the marked current rating, or the ampacity table for the bundle size.
Installation rules (Article 720 and Article 300)
- Access to equipment (formerly 725.21): cables and equipment may not be installed in a way that prevents removal of panels, including suspended ceiling panels, needed to reach electrical equipment.
- Workmanship and support (formerly 725.24): cables must be installed in a neat and workmanlike manner, supported by the building structure with straps, staples, hangers, or cable ties listed and identified for securement and support, and not damaged. They may not be supported by ceiling grids or ceiling-support wires, or strapped to the outside of raceways (except Class 2 cables supported by a raceway that supplies power to the equipment they control).
- Penetrations: openings through fire-resistant-rated walls, floors, and ceilings must be firestopped.
- Abandoned cables (formerly 725.25): the accessible portion of abandoned Class 2, Class 3, and PLTC cables must be removed. Cables identified for future use with a tag of sufficient durability are not considered abandoned.
Worked example: a commercial ceiling
A security contractor runs CL2 cable above a suspended ceiling used as a return-air plenum.
- Cable type: the space is a plenum, so the cable must be CL2P (or a permitted substitute such as CMP or CL3P).
- Support: fasten the cable to the structure with listed supports or J-hooks; do not lay it on the ceiling tiles or tie it to grid wires.
- Separation: do not pull the CL2P cable into the same raceway or box as 120 V lighting conductors.
- Old cable: remove the accessible portions of the abandoned alarm cable that the new system replaced, or tag any cable kept for future use.
In the 2026 NEC, where are the general requirements for limited-energy system wiring methods and materials located?
Article 300
Article 760
Article 805
Article 720
A low-voltage contractor wants to install CL2 cable in an air-handling plenum above a suspended ceiling. What does the Code require?
A plenum-rated cable such as CL2P, CL3P, or CMP
CL2 cable is acceptable if bundled neatly
CL2X cable in any length
Any cable, if it is supported by the ceiling grid
What must be done with the accessible portions of abandoned Class 2 cables in a building?
They may remain if cut back at both ends
They must be grounded at one end
They must be removed, unless tagged for future use
They may remain if spliced into a junction box
Sections you finish are checked off in the contents.