Exit Discharge, Occupant Load and Capacity
Key Takeaways
Use the correct net or gross area.
Round a fractional required load up.
Multiply load by the component factor.
Check component minimums and exit count independently.
Follow discharge to the public way or permitted alternative.
Calculate occupant load before width
Identify the function of each area and use the correct net or gross factor in Table 1004.5. A business area of 7,600 gross square feet at 150 gross square feet per occupant gives 50.67, so use at least 51 occupants. A fixed-seat area follows the separate seat-count rule. Where areas have different functions, calculate them separately before combining the loads that use the same egress component.
Section 1005.3 gives baseline capacity factors of 0.3 inch per occupant for stairs and 0.2 inch per occupant for other egress components. For example, 180 occupants at the baseline stair factor require 54 inches of aggregate stair capacity. Check how that capacity is distributed, along with the individual component minimums. The usual reduced factors require qualifying sprinklers and emergency voice/alarm, and are not available to Groups H and I-2 under that exception.
Trace the exit discharge
Follow the route from the termination of each exit to a public way. Section 1028 addresses discharge at the exterior and specific exceptions, such as qualifying discharge through an interior area or a safe dispersal area where access to a public way cannot be provided. Do not stop the inspection at the exterior door. Verify continuity, obstructions and the final route with the approved site plan.
Calculate exit number separately under §1006. An area can have the required width in a single component and still lack enough separate exits. At reinspection, check both the width and the actual number and availability of routes.
What minimum whole-person load results from 7,600 gross square feet at 150 gross square feet per person?
51 occupants
50 occupants
52 occupants
57 occupants
At 0.3 inch per occupant, what aggregate stair capacity is needed for 180 occupants?
54 inches
36 inches
44 inches
60 inches
Where does a standard exit discharge lead?
From the exit termination toward the public way
From an occupied room to the exit access
From the corridor to the stair door
From the site arrival point to the accessible entrance