Exit Access: Counts, Common Paths and Travel Distance
Key Takeaways
Mark the start of the exit before measuring.
Use the space table for room doorways.
Check story exit count separately.
Common path, total travel and dead ends use different limits.
Verify the installed route is available.
Identify the egress boundary
The means of egress has three parts: exit access leads to an exit; the exit leads to exit discharge or the public way; exit discharge continues to the public way. A room door is not necessarily the entrance to an exit. On a plan, mark the point where a path enters a protected exit or reaches an exterior exit door. Use that boundary to measure exit access travel distance.
Use Table 1006.2.1 for the number of exits or exit access doorways from an individual room or space. Check both the allowable occupant load and common path length. Use §1006.3 and its tables for a story or occupiable roof. A room can qualify for one doorway while the story still needs two separate exits.
Compare three lengths separately
- Common path is the initial shared route before two distinct egress paths are available.
- Exit access travel distance is the total route to the nearest exit under §1017.
- Dead-end corridor length has separate limits in §1020.5.
For an unsprinklered Group B space with 45 occupants, Table 1006.2.1 allows a 75-foot common path. The 200-foot Group B travel distance in Table 1017.2 does not override that 75-foot limit. If the measured common path is 80 feet, the single-doorway design fails on common path even though the space has fewer than 50 occupants.
Confirm the as-built path follows the approved layout. Furniture, new partitions or locked access can change the route or remove the point where paths diverge.
What is the common path cap for an unsprinklered Group B space serving 45 occupants?
75 feet
50 feet
100 feet
200 feet
Which table gives the base exit access travel distance?
Table 1017.2
Table 1006.2.1
Table 1006.3.3
Table 1020.3
Does compliance for a single doorway from one room establish the number of exits from its story?
No; check the story under §1006.3
Yes, when the room has under 50 occupants
Yes, when the space is sprinklered
No; use the corridor width table instead