Fire Walls, Fire Barriers and Fire Partitions
Key Takeaways
Identify the rated wall function.
Check continuity to the required boundary.
Use the wall-specific door rating row.
Check width and area limits for openings.
Verify firestop details against their listing.
Start with the wall function
A fire wall under §706 must resist collapse of construction on either side in fire conditions without collapsing itself. Fire barriers under §707 serve functions such as shaft enclosure and occupancy separation. Fire partitions under §708 serve functions such as certain corridor walls and unit separations. Do not infer the assembly type from its hourly rating: a one-hour corridor partition and a one-hour fire barrier can require different continuity and openings.
For a fire barrier, §707.6 generally limits aggregate openings to 25% of wall length and each opening to 156 square feet, subject to listed exceptions. Read the additional rules for stair and shaft enclosures and passageways. For a 60-foot wall, the base aggregate limit is 15 feet. A 12-foot-wide opening plus a 5-foot-wide opening exceeds that cap even if each individual opening is under 156 square feet.
Match the installed assembly to its listing
Check the approved assembly identification, board layers or masonry, framing, attachments, and continuity at intersecting construction. For a door, use Table 716.1(2) and the row for the wall's function. A 45-minute door may be appropriate in the Other fire barriers row for a one-hour wall; it is not the universal rule for one-hour walls.
Before concealment, compare each pipe, conduit or duct opening with the applicable code provision and approved protection. Check the listed material and annular space rather than accepting any sealant of the right color. Ducts may require protection under §717 instead of an ordinary penetration detail.
A 60-foot fire barrier has 17 feet of aggregate openings. What is the general §707.6 width cap without an exception?
15 feet
12 feet
20 feet
30 feet
What determines which row of Table 716.1(2) to use?
The wall’s function and required rating
The door’s nominal width and color
The contractor’s hardware supplier
The number of stories by itself
What is the general minimum fire-partition rating under §708.3 before exceptions?
1 hour
½ hour
1½ hours
2 hours