14.2 Pipe Sizing, Longest-Length Method & Pressure Drop

Key Takeaways

  • 2024 IFGC 402.2 sizes from the sum of maximum appliance inputs, assuming simultaneous full-capacity operation unless a diversity of load is established, and adjusts volume for altitude above 2,000 feet.
  • IFGC Appendix A A102.1 converts Btu/h to cubic feet per hour by dividing by the serving supplier’s heating value per cubic foot; the Appendix A worked examples use 1,000 Btu/ft³ for natural gas.
  • 2024 IFGC 402.4.1 (longest-length method) measures from the point of delivery to the most remote outlet and uses that one length, and the load of each section, to size every section of the system.
  • 2024 IFGC Table 402.4(2) is the common low-pressure natural-gas table: Schedule 40 metallic pipe, inlet less than 2 psi, 0.5-inch w.c. drop, specific gravity 0.60, capacities in cfh.
  • Undiluted-propane Tables 402.4(25) through 402.4(37) are already in thousands of Btu per hour; a 199,000 Btu/h tankless on an 80-foot 1/2-inch natural-gas run has only 56 cfh of Table 402.4(2) capacity against 199 cfh of demand.
Last updated: August 2026

402.1 requires the piping system to supply the maximum demand and to deliver not less than the minimum inlet pressure each appliance needs. 402.2 sets the volumetric flow as the sum of the maximum inputs of the appliances served. Use the total connected hourly load and assume every appliance can run at full capacity at once. Diversity is allowed only where a diversity of load can be established. Adjust the volume for altitude above 2,000 feet. 401.4 is the existing-system twin: adding an appliance means you re-check the old pipe; if it is inadequate, enlarge it or run a separate pipe of adequate capacity. 401.3 says modifications still keep sizes in accordance with Chapter 4. 401.8 forbids a pipe that cannot supply the full number of outlets.

Convert Btu/h to the table’s units

IFGC Appendix A A102.1 (informative, but it is the conversion the tables assume): obtain cubic feet per hour by dividing total Btu/h input by the average Btu heating value per cubic foot from the serving gas supplier. The Appendix A sample calculations use 0.60 specific gravity and 1,000 Btu/ft³. On the exam, unless a stem gives a different heating value, convert natural gas as:

cfh = Btu/h ÷ 1,000

A 199,000 Btu/h tankless is 199 cfh. A 100,000 Btu/h furnace is 100 cfh. A 40,000 Btu/h water heater is 40 cfh.

Do not convert propane into cfh to use the propane tables. Appendix A A103.1 Step 2 is explicit: Tables 402.4(25) through 402.4(37) are selected with demand in thousands of Btu per hour. The same 199,000 Btu/h tankless is 199 on a propane table. Those tables already use specific gravity 1.50. Mixing a natural-gas cfh table with an LP nameplate, or dividing LP Btu/h by 1,000 and then reading a propane MBH column, is how candidates undersize a second-stage line.

402.3 allows three sizing paths: the Section 402.4 / 402.5 tables or equations; the sizing tables in a listed piping system’s manufacturer’s instructions (the CSST path); or engineering methods. 402.6 is the pressure-drop governor: from the point of delivery to every appliance inlet, remaining pressure shall be greater than or equal to the appliance’s minimum. Indoor systems are generally capped at 5 psig unless a 402.7 exception applies (welded or brazed joints, LC-4 fittings, flanged-and-welded joints, a ventilated chase, certain industrial/research/warehouse/boiler-room occupancies, temporary construction piping, agricultural use, or an LP-gas system over 20 psi that complies with NFPA 58).

Longest-length method — 402.4.1

402.4.1 is one sentence you should be able to write from memory:

The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section.

Measure meter (or other point of delivery) to the farthest appliance. That footage is the only length you take into the table. Every section — the trunk that carries everything and the 8-foot stub that carries one water heater — is read on that same row. You do not size the stub on 8 feet. Appendix A A103.1 adds the exam technique: if the measured length is not printed, use the next longer row; then, starting at the most remote outlet, find a capacity equal to or greater than that section’s load and read the size at the top of the column.

402.4.2 Branch Length Method is the allowed alternate. Size the longest run with the longest length, then size each remaining branch using the length from the point of delivery to the most remote outlet on that branch. 402.4.3 Hybrid Pressure sizes the high-pressure portion on the longest length from the point of delivery to the most remote line pressure regulator, then sizes each low-pressure zone on the length from that regulator to its most remote outlet.

Table 402.4(2) — the table to tab

Table 402.4(2): Schedule 40 metallic pipe, natural gas, inlet less than 2 psi, pressure drop 0.5 in. w.c., specific gravity 0.60, capacity in cfh. These are fetched 2024 values, not folklore:

Length (ft)1/2 in.3/4 in.1 in.1-1/4 in.1-1/2 in.2 in.
101723606781,3902,0904,020
201182474669571,4302,760
30951993747681,1502,220
40811703206579851,900
50721512845838731,680
60651372575287911,520
80561172204526771,300
100501041954006001,160

Table 402.4(1) is the same pipe and gas at a 0.3 in. w.c. drop. Its 10-foot, 1/2-inch cell is 131 cfh — that 131 is real, but it is not the 0.5-inch-drop number. If the stem does not name the drop, the common low-pressure commercial table is 402.4(2).

Worked examples with those cells

Example 1 — longest length 60 feet, natural gas, Table 402.4(2). A mechanical room has a 100,000 Btu/h furnace (100 cfh), a 40,000 Btu/h water heater (40 cfh), and a 250,000 Btu/h rooftop (250 cfh). The most remote outlet is 60 feet from the meter. Stay on the 60-foot row: 1/2 = 65, 3/4 = 137, 1 = 257, 1-1/4 = 528.

  • Water-heater branch at 40 cfh: 1/2 inch (65 ≥ 40).
  • Furnace branch at 100 cfh: 3/4 inch (137 ≥ 100; 65 is short).
  • Rooftop branch at 250 cfh: 1 inch (257 ≥ 250). That cell is tight; 249 cfh would still be 1 inch, 258 cfh would jump to 1-1/4.
  • Trunk that serves all three (390 cfh): 1-1/4 inch (528 ≥ 390; 257 is short).

Example 2 — the 199k tankless field fail. A 199,000 Btu/h natural-gas tankless sits 80 feet from the meter on a lone 1/2-inch run. Demand is 199 cfh. Table 402.4(2) at 80 feet gives 1/2-inch only 56 cfh, 3/4-inch 117 cfh, 1-inch 220 cfh. The 1/2-inch pipe carries about 28 percent of the load. 1 inch is the first size that works (220 ≥ 199). A 3/4-inch “upgrade” still fails. This is the 401.4 addition problem dressed as a new house: the installer copied a 40-foot water-heater size onto an 80-foot tankless.

Example 3 — adding load to an existing 1-inch, 80-foot main. The same 80-foot 1-inch main already serves 100 cfh of other appliances (Table capacity 220 cfh). Adding the 199 cfh tankless makes 299 cfh. 220 < 299, so the existing 1-inch main fails 401.4. The 80-foot row needs 1-1/4 inch (452 ≥ 299).

Example 4 — undiluted propane, Table 402.4(28). That table is Schedule 40 metallic, 11.0 in. w.c. inlet, 0.5 in. w.c. drop, SG 1.50, intended for pipe between a single- or second-stage low-pressure regulator and the appliance, capacity in thousands of Btu per hour. At 80 feet: 1/2-inch = 94, 3/4-inch = 197, 1-inch = 372. The same 199,000 Btu/h tankless is 199 on this table. 197 < 199, so 3/4-inch propane at 80 feet fails by 2 MBH. The legal size is 1 inch (372). That one-cell miss is an exam item waiting to happen.

Example 5 — 10 psi first-stage propane, Table 402.4(25). Between the first-stage and second-stage regulators, 10 psi inlet, 1.0 psi drop, an 80-foot 1/2-inch steel line carries 1,080 thousand Btu/h. That is why two-stage LP systems can use small pipe outdoors and still feed a large second-stage regulator. Do not read Table 402.4(25) on the low-pressure house line.

free M2 practice bankPractice questions with detailed explanations
Loading diagram...
2024 IFGC 402.4.1 longest-length method
Test Your Knowledge

Under 2024 IFGC 402.4.1, a natural-gas system has a 20-foot branch to a water heater and an 80-foot run to a rooftop unit. Which length is used to size the 20-foot water-heater branch by the longest-length method?

A
B
C
D
Test Your Knowledge

A 199,000 Btu/h natural-gas tankless is supplied by 80 feet of 1/2-inch Schedule 40 steel from the meter. Using 1,000 Btu/ft³ and 2024 IFGC Table 402.4(2), what is the correct result?

A
B
C
D
Test Your Knowledge

A 199,000 Btu/h undiluted-propane tankless is 80 feet from a second-stage regulator. Using 2024 IFGC Table 402.4(28), which size is the first Schedule 40 metallic size that works?

A
B
C
D