Free MI Journeyman Electrician Exam Flashcards

Memorize 50 essential terms and definitions for the Michigan Electrical Journeyman License Examination (LARA Bureau of Construction Codes, delivered by PSI). See the term, recall the definition, then flip to check yourself.

50 Flashcards
13 Topics
100% Free
TermClick to flip

Minimum age and experience for a Michigan electrical journeyman's license

Tap to reveal definition
Card 1 of 50Michigan Law & Code Rules

Filter by Topic

Jump to Card

About These MI Journeyman Electrician Flashcards

These 50 flashcards are designed to help you memorize key terms and definitions for the Michigan Electrical Journeyman License Examination (LARA Bureau of Construction Codes, delivered by PSI). Each card shows a term on the front and its definition on the back—the classic flashcard format for vocabulary memorization. Use these alongside our practice questions to build both recall and comprehension.

Topics Covered

Michigan Law & Code Rules4 cards
Grounding & Bonding3 cards
Overcurrent Protection3 cards
Wiring Methods & Installations4 cards
Boxes, Cabinets & Fill6 cards
Services & Feeders6 cards
Motors & Motor Controls3 cards
Special Occupancies3 cards
Load Calculations3 cards
Lighting & Appliances6 cards
Power-Limited Circuits3 cards
General Trade Knowledge3 cards
Electrical Theory3 cards

Complete Flashcard Reference

Review every term in this set. Open any term to reveal its definition.

Minimum age and experience for a Michigan electrical journeyman's license

MCL 339.5715 requires you to be at least 20 years old with at least 8,000 hours of experience obtained over a period of at least 4 years, performed under the direct supervision of someone licensed under Article 7. Hours alone are not enough - crowding 8,000 hours into three years does not satisfy the 4-year clock.

What happens after two journeyman exam failures in Michigan?

Under MCL 339.5715(3), failing the electrical journeyman exam twice within 2 years makes you ineligible to sit again for at least 1 year from the date of the second failure. After that year you must also give the board proof that you completed an approved course on Michigan electrical code, electrical fundamentals, or electrical theory.

Michigan apprentice electrician registration and jobsite ratio

An apprentice must register with the board within 30 days after employment (MCL 339.5717(1)), and the ratio is 1 journeyman or master electrician to no more than 3 registered apprentices, enforced on a jobsite basis. Counting apprentices company-wide instead of per jobsite is the classic violation.

How long is a Michigan electrical permit valid (Part 8, R 408.30818)?

Permits expire 180 days after issuance and are extended 180 days from the last inspection date, and the AHJ may grant one additional 180-day extension for a satisfactory reason. Permits are not transferable, and a copy must be posted or otherwise readily accessible at each work site.

Grounding electrode conductor vs. equipment grounding conductor

The grounding electrode conductor connects the system and enclosures to the earth electrodes and is sized from Table 250.66, while the equipment grounding conductor provides the low-impedance fault-clearing path back to the source and is sized from Table 250.122 by overcurrent-device rating. Sizing an EGC off Table 250.66 (or vice versa) is a common exam trap; note that 250.66(A) never requires more than 6 AWG copper where that conductor is the sole connection to a rod, pipe, or plate electrode.

Ground rod length, spacing, and the supplemental electrode rule

A rod electrode must be at least 8 ft long and in contact with the soil (250.52(A)(5)), and where rods are used together they must be at least 6 ft apart (250.53(A)(3)). A single rod must be supplemented by an additional electrode unless it is tested and shows 25 ohms or less to ground (250.53(A)(2), Exception).

Michigan CSST gas-piping bonding rule (R 408.30871)

Michigan amends 250.104(B): a listed CSST gas piping system must be bonded to the electrical service grounding electrode system with a jumper not smaller than 6 AWG copper, landed on metallic pipe or a fitting between the point of delivery and the first downstream CSST fitting. That 6 AWG minimum is a Michigan requirement, not a plain NEC number, and once bonded this way the system is considered effectively bonded regardless of how much CSST is installed.

Small-conductor overcurrent limits (240.4(D))

Regardless of the ampacity you calculate from Table 310.16, copper conductors are limited to 15 A for 14 AWG, 20 A for 12 AWG, and 30 A for 10 AWG unless a specific exception applies. This is why a 12 AWG THHN conductor rated 30 A at 90 degrees C still cannot be protected at 30 A on a general branch circuit.

When may you round up to the next standard overcurrent device (240.4(B))?

You may use the next higher standard rating from 240.6(A) when the conductor ampacity does not match a standard size, the device is rated 800 A or less, and the circuit does not supply receptacles for cord-and-plug-connected loads on a multi-outlet branch circuit. Above 800 A the rule flips: 240.4(C) requires the device rating to not exceed the conductor ampacity.

Where overcurrent devices may not be located (240.24)

The 2023 NEC's 240.24(E) prohibits overcurrent devices other than supplementary devices in bathrooms, showering facilities, and locker rooms that contain showering facilities. Panelboards must also stay readily accessible, out of clothes closets and bathrooms, and away from easily ignitible material.

Michigan's amended NM cable use rules (R 408.30873)

Michigan rewrites 334.10 and 334.12(A): NM and NMC are permitted in one- and two-family dwellings with their garages and storage buildings, in multifamily dwellings and their detached garages, and in other structures over one floor above grade only where concealed behind assemblies with at least a 15-minute finish rating. It may never be used as service-entrance cable, in commercial garage classified locations, in hoistways, or embedded in concrete.

Securing and supporting NM cable (334.30)

NM cable must be secured within 12 in. of every box, cabinet, or fitting and at intervals not exceeding 4.5 ft. The relief is single-gang nonmetallic boxes without internal clamps, where the cable may instead be fastened within 8 in. of the box measured along the sheath.

EMT support spacing (358.30)

EMT must be securely fastened within 3 ft of each outlet box, junction box, cabinet, or termination and supported at intervals not exceeding 10 ft. Rigid metal conduit and IMC use the same 3-ft rule at boxes but allow longer intervals based on conduit trade size in Table 344.30(B)(2) - up to 20 ft for trade size 3 and larger.

Minimum burial cover depths (Table 300.5(A))

Typical minimums are 24 in. for direct-buried cable, 18 in. for nonmetallic raceway listed for direct burial, and 6 in. for rigid metal conduit or IMC. A residential branch circuit rated 120 V or less that is GFCI-protected and protected at 20 A or less may be buried at 12 in.

Conductor volume allowances for box fill (Table 314.16(B))

Each conductor counts as 2.00 cubic in. for 14 AWG, 2.25 for 12 AWG, 2.50 for 10 AWG, 3.00 for 8 AWG, and 5.00 for 6 AWG. Conductors that pass through the box without splice count once, and conductors that both enter and leave through a cable or raceway are still one count each.

How a switch or receptacle counts in box fill (314.16(B)(4))

Each yoke or strap holding one or more devices counts as a double volume allowance, based on the largest conductor connected to that yoke - not the largest conductor in the box. A switch fed with 12 AWG therefore adds 4.5 cubic in., which is what pushes many two-device boxes over the limit.

Clamp and equipment grounding conductor allowances in a box

One or more internal cable clamps together add a single allowance based on the largest conductor in the box (314.16(B)(2)). Up to four equipment grounding conductors also count as one allowance based on the largest EGC, with a 1/4 allowance for each additional EGC beyond four (314.16(B)(5)).

Maximum raceway fill percentages (Chapter 9, Table 1)

One conductor may fill 53% of the raceway cross section, two conductors 31%, and more than two 40%. Note 4 to the table allows 60% fill in a nipple no longer than 24 in., and that nipple also escapes the ampacity adjustment factors.

Free conductor length required at a box (300.14)

At least 6 in. of free conductor must be left at each outlet, junction, and switch point, measured from where it emerges from the raceway or cable sheath. Where the opening is less than 8 in. in any dimension, each conductor must also extend at least 3 in. outside that opening.

Sizing a pull box for 4 AWG and larger conductors (314.28(A))

For a straight pull, the box length must be at least 8 times the trade size of the largest raceway. For angle or U pulls, the distance from the raceway entry to the opposite wall must be at least 6 times the largest raceway trade size, plus the trade sizes of the other raceways in the same row on that wall.

Minimum service disconnect rating for a one-family dwelling (230.79)

The service disconnecting means for a one-family dwelling must be rated not less than 100 amperes, 3-wire. Smaller minimums apply elsewhere - 15 A for a one-circuit installation, 30 A for a two-circuit installation, and 60 A for all other installations under 230.79(D) - so read the occupancy before you answer.

The two-to-six service disconnect rule after the 2020 NEC (230.71(B))

Two to six service disconnects are still permitted per service, but each must now be in its own enclosure, in a panelboard with a main, in a separate barriered vertical switchboard section, or in a separate switchgear compartment. Six breakers stacked in one panel as the service disconnecting means is no longer acceptable.

Michigan's emergency disconnect requirement for dwellings (R 408.30870)

Part 8 adds 230.85: one- and two-family dwellings need an emergency disconnecting means in a readily accessible outdoor location on or within sight of the dwelling, with a short-circuit current rating at least equal to the available fault current. Each disconnect must be a service disconnect and must be marked EMERGENCY DISCONNECT, SERVICE DISCONNECT; multiple disconnects must be grouped.

Where surge protection is required in the 2023 NEC

A surge-protective device is required where a service (230.67), feeder (215.18), or outside feeder/branch circuit (225.42) supplies dwelling units, dormitory units, hotel and motel guest rooms and suites, or nursing home and limited-care areas used exclusively as patient sleeping rooms. Replacing that service equipment triggers the SPD requirement too.

Where must the service disconnecting means be located (230.70)?

It must be installed at a readily accessible location either outside the building or inside nearest the point of entrance of the service conductors, and it may not be in a bathroom. Running unprotected service-entrance conductors deep into a building past the nearest practical point is the violation this rule exists to prevent.

Why the neutral is bonded to ground only at the service

The main bonding jumper ties the grounded (neutral) conductor to the equipment grounding system at the service disconnect, and 250.142 prohibits using the grounded conductor for equipment grounding on the load side. Bonding neutral to ground in a downstream panel puts normal neutral current on metal enclosures and the equipment grounding conductors.

Sizing conductors for a single continuous-duty motor (430.22)

Branch-circuit conductors must have an ampacity of at least 125% of the motor full-load current taken from Table 430.248 or Table 430.250 - the code table value, not the nameplate. Using nameplate amps here is the single most common motor-calculation error on licensing exams.

Sizing motor overload protection (430.32(A)(1))

For continuous-duty motors over 1 hp, the separate overload device is set at no more than 125% of the motor nameplate full-load amperes when the marked service factor is 1.15 or greater or the temperature rise is 40 degrees C or less; all other motors use 115%. Overloads are the one place you must use the nameplate rather than the code table.

Maximum motor branch-circuit short-circuit and ground-fault protection (Table 430.52(C)(1))

Using the table full-load current, the maximum is 300% for a non-time-delay fuse, 175% for a dual-element time-delay fuse, and 250% for an inverse-time circuit breaker. If the calculated value does not match a standard rating, 430.52(C)(1)(a) permits the next higher standard size; the 2023 NEC renumbered old Table 430.52 as Table 430.52(C)(1) and turned its exceptions into list items.

Receptacle placement near a permanently installed pool (680.22(A)(1))

At a dwelling unit, at least one 125-volt, 15- or 20-ampere receptacle must be located not less than 6 ft and not more than 20 ft from the inside wall of the pool, and no more than 6 ft 6 in. above the floor or grade. The 6-ft minimum keeps cords out of the water while the 20-ft maximum discourages extension cords.

Pool equipotential bonding conductor and perimeter distance (680.26)

Equipotential bonding uses a minimum 8 AWG solid bare copper conductor, and the perimeter surface to be bonded extends 3 ft horizontally beyond the inside walls of the pool. This bonding grid only equalizes voltage in the pool area - it is not required to be run to a panelboard, service equipment, or grounding electrode.

Classes and divisions in hazardous locations (Article 500)

Class I covers flammable gases and vapors, Class II combustible dust, and Class III ignitible fibers and flyings. Division 1 means the hazard is present in normal operation, while Division 2 means it appears only under abnormal conditions, which is why Division 2 permits less costly wiring methods.

Dwelling unit general lighting load in the 2023 NEC

Section 220.41 sets the dwelling minimum unit load at 3 volt-amperes per square foot, and 220.5(C) says the floor area is computed from outside dimensions, excluding open porches and unfinished areas not adaptable for future use. This value moved from 220.12 in the 2020 NEC, and the 2023 edition also removed garages from the exclusion list - garage floor area now counts.

How small-appliance and laundry circuits enter a dwelling load calculation

Each required 20-ampere small-appliance branch circuit and each laundry branch circuit is computed at 1,500 volt-amperes (220.52), and a dwelling must have at least two small-appliance circuits, one laundry circuit, and one 20-ampere bathroom circuit under 210.11(C). Those VA values are added to the general lighting load before demand factors are applied.

Demand values for a household dryer and range

A household electric clothes dryer is calculated at 5,000 volt-amperes or the nameplate rating, whichever is larger (220.54). Household ranges use the demand table in 220.55, where a single range rated not over 12 kW is calculated as an 8 kW demand rather than at nameplate.

Required lighting outlets in a dwelling (210.70(A))

At least one wall-switch-controlled lighting outlet is required in every habitable room, kitchen, and bathroom, plus hallways, stairways, attached garages, and outdoor entrances or exits with grade-level access. Storage or equipment spaces such as attics and basements need a lighting outlet controlled at the point of entry.

Which dwelling receptacles need GFCI protection in the 2023 NEC (210.8(A))

Protection applies to 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground in the listed locations, and the 2023 edition expanded 210.8(A)(6) to all dwelling kitchen receptacles - not just those serving countertops. The old shorthand of 15- and 20-ampere, 125-volt receptacles is outdated.

GFCI protection for specific appliances (210.8(D))

The branch circuit or outlet supplying certain appliances rated 150 volts or less to ground and 60 amperes or less, single- or three-phase, must be GFCI protected. The 2023 additions are electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and microwave ovens, joining items such as dishwashers, sump pumps, and vending machines on the 12-item list.

Where arc-fault protection is required (210.12)

AFCI protection is required for 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices in dwelling-unit kitchens, bedrooms, living areas, hallways, laundry areas, and similar rooms. The 2023 NEC also extended it under 210.12(D) to areas used exclusively as sleeping quarters in fire, police, ambulance, rescue, and ranger stations and similar locations.

2023 changes to kitchen countertop and island receptacles (210.52(C))

Receptacle outlets serving countertops or work surfaces must be located on or above the surface but not more than 20 in. above it, or in listed countertop or work-surface assemblies. For islands and peninsulas the 2023 NEC no longer mandates a receptacle, but provisions for adding one later must be built in.

Tamper-resistant receptacle requirement (406.12)

All 15- and 20-ampere, 125-volt and 250-volt non-locking receptacles in the listed areas must be listed tamper-resistant. The 2023 edition added residential care and assisted-living facilities, rehabilitation facilities, group homes, foster care facilities, nursing homes, psychiatric hospitals, and public or common areas of agricultural buildings.

How the 2023 NEC reorganized Class 1, 2, and 3 circuits

Article 725 now covers only Class 2 and Class 3 power-limited circuits, Class 1 power-limited circuits moved to new Article 724, and cable requirements for power-limited, fault-managed, and optical fiber installations moved to new Article 722; Article 720 was deleted. Citing 725 for a Class 1 rule is a wrong answer under the code Michigan now enforces.

What makes a circuit Class 2 versus Class 3?

Both are supplied from listed power sources whose voltage, current, and volt-ampere limits come from Chapter 9, Tables 11(A) for alternating current and 11(B) for direct current. Class 2 is limited enough to be considered safe from shock and fire ignition, while Class 3 permits higher voltage and therefore requires additional protection against electric shock.

Separating power-limited conductors from power conductors (725.136)

Class 2 and Class 3 conductors may not occupy the same cable, raceway, enclosure, or cable tray as electric light, power, Class 1, or non-power-limited fire alarm conductors unless a barrier or one of the specific permissions in 725.136(B) through (I) applies. Dropping a thermostat cable into a box with a 120-volt branch circuit is the everyday version of this violation.

Which documents the Michigan electrical exams are written from

LARA states that all Michigan electrical examinations are currently based on the 2023 NEC, the 2023 Michigan Electrical Code Part 8 rules, 1972 PA 230 (Stille-DeRossett-Hale), 2016 PA 407 (Skilled Trades Regulation Act), and their promulgated rules. Where Part 8 amends, adds, or rescinds an NEC section, the Michigan text is the enforceable answer.

Working space around electrical equipment (110.26(A))

For equipment operating at 0-150 volts to ground under Condition 1, the working space is at least 3 ft deep, at least 30 in. wide or the width of the equipment if greater, and 6.5 ft high. The 2023 NEC added 110.26(A)(6), requiring the grade, floor, or working platform to be kept clear and as level and flat as practical for the full depth and width.

Termination temperature limits (110.14(C))

Unless the equipment or terminals are listed for higher, circuits rated 100 amperes or less and conductors 14 AWG through 1 AWG must be sized from the 60 degree C column, while larger circuits default to the 75 degree C column. A 90 degree C conductor may still be used, but only its higher rating is used for derating - the final ampacity may not exceed the terminal rating.

Ohm's law and the power formula

E = I x R and P = I x E, which combine to P = I squared x R for a resistive load. Because heat rises with the square of current, doubling the current through a fixed resistance quadruples the heat; halving the resistance at a fixed voltage doubles the current and therefore doubles the power (P = E squared / R).

Voltage and current relationships in three-phase systems

In a wye system, line voltage equals 1.732 times phase voltage (120 V phase gives 208 V line) while line and phase current are equal; in a delta system, line and phase voltage are equal while line current equals 1.732 times phase current. Three-phase power is P = 1.732 x line volts x line amps x power factor.

Voltage-drop formula and the NEC's recommended limits

For a single-phase circuit, VD = (2 x K x I x L) / circular mils, with K about 12.9 for copper and 21.2 for aluminum; substitute 1.732 for the 2 on a three-phase circuit. NEC informational notes recommend holding branch-circuit drop to 3% and total drop to 5%, but those are recommendations, not enforceable requirements.

Frequently Asked Questions

How many questions are on the Michigan journeyman electrician exam and what score do I need?

The PSI Candidate Information Bulletin for the Michigan Bureau of Construction Codes lists the Electrical Journeyman exam as 80 questions with 150 minutes allowed and a minimum passing score of 75%. The examination fee is $100 under MCL 339.5707 and is valid for one year from the date of payment.

Which code edition does the Michigan electrician exam use?

LARA states that all Michigan electrical examinations are currently based on the 2023 National Electrical Code, the 2023 Michigan Electrical Code Part 8 rules, 1972 PA 230, 2016 PA 407, and their promulgated rules. Part 8 (R 408.30801) adopts the 2023 NEC second printing with Michigan amendments, effective March 12, 2024.

Is the Michigan journeyman electrician exam open book?

Yes. The exam is open book, and candidates may bring a bound NEC (factory markings and factory tabs only), 2016 PA 407, 1972 PA 230, and the Michigan Electrical Code Part 8 rules. Documents printed from the BCC website must be bound with 3 staples on the left edge, no highlighting or tabs, and the NEC Handbook is not allowed.

What happens if I fail the Michigan journeyman electrician exam?

PSI limits journeyman candidates to 2 attempts within the 1-year application period, after which you must reapply with the state. Under MCL 339.5715(3), failing the journeyman exam twice within 2 years makes you ineligible for at least 1 year from the second failure, and you must then show proof of a board-approved course on Michigan electrical code, electrical fundamentals, or electrical theory.

What experience does Michigan require before I can take the journeyman exam?

MCL 339.5715 requires an applicant to be at least 20 years old with at least 8,000 hours of experience obtained over a period of at least 4 years, performed under the direct supervision of an individual licensed under Article 7. A military route also exists for honorably discharged interior electricians who apply within one year of discharge.

Same family resources

Explore More Electrician License

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.