3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor

Key Takeaways

  • Room Sensible Heat Ratio ($\text{RSHR} = \frac{q_{s,room}}{q_{s,room} + q_{l,room}}$) determines the slope of the Room Condition Line connecting the room state to the required supply air state.
  • Grand Sensible Heat Ratio ($\text{GSHR} = \frac{q_{s,total}}{q_{t,total}}$) includes ventilation loads and determines the slope of the process line connecting the mixed air state to the Apparatus Dew Point ($ADP$).
  • The Apparatus Dew Point ($ADP$) is the effective surface temperature of the cooling coil where the condition line intersects the $100\%\text{ RH}$ saturation curve.
  • Coil Bypass Factor ($BF$) represents the fraction of air passing through the coil unaffected: $BF = \frac{T_{leaving} - T_{adp}}{T_{entering} - T_{adp}} = \frac{W_{leaving} - W_{adp}}{W_{entering} - W_{adp}}$; Contact Factor is $CF = 1 - BF$.
  • Required supply airflow accounting for coil bypass is: $\text{CFM}_{sa} = \frac{q_{s,room}}{1.08 \times (T_{room} - T_{adp}) \times (1 - BF)}$.
Last updated: August 2026

3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor

Designing a cooling coil requires satisfying both the sensible cooling load (temperature reduction) and the latent cooling load (moisture removal) simultaneously. The Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP), and Coil Bypass Factor (BF) are the engineering parameters that link space cooling loads to physical coil construction and required airflow.


1. Sensible Heat Ratio (SHR) Definitions

Sensible Heat Ratio (also called Sensible Heat Factor, SHF) is the ratio of sensible heat to total heat:

SHR=q˙sensibleq˙total=q˙sq˙s+q˙l\text{SHR} = \frac{\dot{q}_{sensible}}{\dot{q}_{total}} = \frac{\dot{q}_s}{\dot{q}_s + \dot{q}_l}

1. Room Sensible Heat Ratio (RSHR)

Governs the slope of the Room Condition Line (RCL) on the psychrometric chart connecting the room design state ($R$) and the supply air state ($S$):

RSHR=qs,roomqs,room+ql,room\text{RSHR} = \frac{q_{s,room}}{q_{s,room} + q_{l,room}}

Where $q_{s,room}$ and $q_{l,room}$ include internal loads (people, lighting, equipment, envelope conduction, solar gain) but exclude outdoor ventilation air loads.

2. Grand Sensible Heat Ratio (GSHR)

Governs the slope of the Grand Condition Line (GCL) connecting the mixed air state ($M$) to the apparatus dew point ($ADP$):

GSHR=qs,totalqt,total=qs,room+qs,ventqt,room+qt,vent\text{GSHR} = \frac{q_{s,total}}{q_{t,total}} = \frac{q_{s,room} + q_{s,vent}}{q_{t,room} + q_{t,vent}}

Where:

  • $q_{s,vent} = 1.08 \times \text{CFM}{oa} \times (T{oa} - T_{room})$
  • $q_{l,vent} = 4840 \times \text{CFM}{oa} \times (W{oa} - W_{room})$

3. Effective Sensible Heat Ratio (ESHR)

Used when coil bypass factor $BF > 0$. It accounts for the fraction of outdoor ventilation air that bypasses the coil fins and enters the conditioned space directly:

ESHR=qs,room+(1BF)qs,ventqt,room+(1BF)qt,vent\text{ESHR} = \frac{q_{s,room} + (1 - BF) q_{s,vent}}{q_{t,room} + (1 - BF) q_{t,vent}}

Loading diagram...
Psychrometric Construction of RSHR, GSHR, ADP, and Coil Bypass

2. Apparatus Dew Point (ADP) & Coil Bypass Factor (BF)

Apparatus Dew Point (ADP)

The Apparatus Dew Point is the effective average surface temperature of the cooling coil fins and tubes. Geometrically on the psychrometric chart, the $ADP$ is the point where the condition line intersects the $100%\text{ RH}$ saturation curve ($T_{db} = T_{wb} = T_{dp} = T_{adp}$).

Coil Bypass Factor ($BF$)

In a physical cooling coil, not all air molecules make direct thermal contact with the cold fin surfaces. A fraction of the air ($BF$) passes through between fins unaffected, while the remaining fraction ($1 - BF$) comes into complete thermal equilibrium at the $ADP$.

Bypass Factor: BF=TleavingTadpTenteringTadp=WleavingWadpWenteringWadp=hleavinghadphenteringhadp\text{Bypass Factor: } BF = \frac{T_{leaving} - T_{adp}}{T_{entering} - T_{adp}} = \frac{W_{leaving} - W_{adp}}{W_{entering} - W_{adp}} = \frac{h_{leaving} - h_{adp}}{h_{entering} - h_{adp}}

Contact Factor: CF=1BF=TenteringTleavingTenteringTadp\text{Contact Factor: } CF = 1 - BF = \frac{T_{entering} - T_{leaving}}{T_{entering} - T_{adp}}

Rearranging to find leaving coil air temperature ($T_{leaving}$):

Tleaving=Tadp+BF(TenteringTadp)=(1BF)Tadp+BFTenteringT_{leaving} = T_{adp} + BF \left( T_{entering} - T_{adp} \right) = (1 - BF) T_{adp} + BF \cdot T_{entering}

Parameters Governing Coil Bypass Factor ($BF$)

ParameterChangeEffect on Bypass Factor ($BF$)Physical Reason
Number of Tube RowsIncrease (e.g., 4 to 8 rows)Decreases $BF$ (improves contact)Longer air residence time and more fin surface contact
Fin Density (FPI)Increase (e.g., 8 to 14 fins/in)Decreases $BF$Narrower air passages between fins maximize boundary layer contact
Coil Face VelocityIncrease (e.g., 400 to 600 FPM)Increases $BF$Higher air velocity reduces residence time across coil
Typical DX CoilsCommercial Rooftop Units$BF \approx 0.10 - 0.20$3 to 4 rows, lower fin density
Typical CW CoilsBuilt-up Central AHUs$BF \approx 0.03 - 0.08$6 to 8 rows, higher fin density

3. Supply Airflow (CFM) Calculation with Coil Bypass

To satisfy the room sensible cooling load ($q_{s,room}$), the supply airflow must be sized based on the temperature difference between the room design temperature ($T_{room}$) and the actual supply air temperature ($T_{supply}$):

CFMsa=qs,room1.08×(TroomTsupply)\text{CFM}_{sa} = \frac{q_{s,room}}{1.08 \times (T_{room} - T_{supply})}

Expressing $T_{supply}$ (leaving coil) in terms of $ADP$ and $BF$: TroomTsupply=Troom[Tadp+BF(TroomTadp)]=(1BF)(TroomTadp)T_{room} - T_{supply} = T_{room} - \left[ T_{adp} + BF(T_{room} - T_{adp}) \right] = (1 - BF)(T_{room} - T_{adp})

CFMsa=qs,room1.08×(1BF)×(TroomTadp)\text{CFM}_{sa} = \frac{q_{s,room}}{1.08 \times (1 - BF) \times (T_{room} - T_{adp})}


4. Step-by-Step Worked Example: Full SHR, ADP, and Airflow Sizing

Problem Statement

A conditioned space has a design sensible cooling load of $q_{s,room} = 194,400\text{ Btu/hr}$ and a latent cooling load of $q_{l,room} = 64,800\text{ Btu/hr}$.

  • Indoor Room Design Condition: $T_{room} = 75.0^\circ\text{F}$ DB, $50%\text{ RH}$ ($W_{room} = 0.00925\text{ lb/lb}$)
  • Outdoor Ventilation Air: $2,000\text{ CFM}$ at $95.0^\circ\text{F}$ DB, $78.0^\circ\text{F}$ WB ($W_{oa} = 0.0168\text{ lb/lb}$)
  • Selected Chilled Water Coil: Bypass Factor $BF = 0.10$

Calculate:

  1. Room Sensible Heat Ratio (RSHR)
  2. Grand Sensible Heat Ratio (GSHR)
  3. Apparatus Dew Point ($ADP$) temperature from psychrometric alignment (RCL intersection with saturation curve yields $T_{adp} = 51.0^\circ\text{F}$)
  4. Leaving coil air temperature ($T_{leaving}$)
  5. Required supply airflow rate ($\text{CFM}_{sa}$)

Solution Steps

Step 1: Calculate Room Sensible Heat Ratio (RSHR) RSHR=qs,roomqs,room+ql,room=194,400194,400+64,800=194,400259,200=0.750\text{RSHR} = \frac{q_{s,room}}{q_{s,room} + q_{l,room}} = \frac{194,400}{194,400 + 64,800} = \frac{194,400}{259,200} = 0.750

Step 2: Calculate Ventilation Loads and GSHR qs,vent=1.08×CFMoa×(ToaTroom)=1.08×2,000×(95.075.0)=2,160×20.0=43,200 Btu/hrq_{s,vent} = 1.08 \times \text{CFM}_{oa} \times (T_{oa} - T_{room}) = 1.08 \times 2,000 \times (95.0 - 75.0) = 2,160 \times 20.0 = 43,200\text{ Btu/hr} ql,vent=4840×CFMoa×(WoaWroom)=4840×2,000×(0.01680.00925)=9,680,000×0.00755=73,084 Btu/hrq_{l,vent} = 4840 \times \text{CFM}_{oa} \times (W_{oa} - W_{room}) = 4840 \times 2,000 \times (0.0168 - 0.00925) = 9,680,000 \times 0.00755 = 73,084\text{ Btu/hr} qs,total=qs,room+qs,vent=194,400+43,200=237,600 Btu/hrq_{s,total} = q_{s,room} + q_{s,vent} = 194,400 + 43,200 = 237,600\text{ Btu/hr} qt,total=(qs,room+ql,room)+(qs,vent+ql,vent)=259,200+116,284=375,484 Btu/hrq_{t,total} = (q_{s,room} + q_{l,room}) + (q_{s,vent} + q_{l,vent}) = 259,200 + 116,284 = 375,484\text{ Btu/hr} GSHR=qs,totalqt,total=237,600375,484=0.633\text{GSHR} = \frac{q_{s,total}}{q_{t,total}} = \frac{237,600}{375,484} = 0.633

Step 3: Determine Apparatus Dew Point ($ADP$) Plotting the RSHR line ($0.75$) through the room state ($75.0^\circ\text{F}$ DB, $50%\text{ RH}$) to the saturation curve yields: Tadp=51.0FT_{adp} = 51.0^\circ\text{F}

Step 4: Calculate Leaving Coil Air Temperature ($T_{leaving}$) Tleaving=Tadp+BF×(TroomTadp)=51.0F+0.10×(75.0F51.0F)T_{leaving} = T_{adp} + BF \times (T_{room} - T_{adp}) = 51.0^\circ\text{F} + 0.10 \times (75.0^\circ\text{F} - 51.0^\circ\text{F}) Tleaving=51.0+0.10(24.0)=51.0+2.4=53.4FT_{leaving} = 51.0 + 0.10(24.0) = 51.0 + 2.4 = 53.4^\circ\text{F}

Step 5: Calculate Required Supply Airflow ($\text{CFM}_{sa}$) ΔT=TroomTleaving=75.0F53.4F=21.6F\Delta T = T_{room} - T_{leaving} = 75.0^\circ\text{F} - 53.4^\circ\text{F} = 21.6^\circ\text{F} CFMsa=qs,room1.08×ΔT=194,4001.08×21.6=194,40023.328=8,333 CFM\text{CFM}_{sa} = \frac{q_{s,room}}{1.08 \times \Delta T} = \frac{194,400}{1.08 \times 21.6} = \frac{194,400}{23.328} = 8,333\text{ CFM} (Verification via direct formula: $\text{CFM} = \frac{194,400}{1.08 \times (1 - 0.10) \times (75 - 51)} = \frac{194,400}{1.08 \times 0.90 \times 24} = \frac{194,400}{23.328} = 8,333\text{ CFM}$).

Test Your Knowledge

A space has a design room sensible heat gain of 144,000 Btu/hr and a room latent heat gain of 36,000 Btu/hr. What is the Room Sensible Heat Ratio (RSHR)?

A
B
C
D
Test Your Knowledge

A cooling coil has an apparatus dew point (ADP) of 48.0°F and a bypass factor of 0.08. If mixed air enters the cooling coil at 80.0°F dry-bulb, what is the dry-bulb temperature of the air leaving the coil?

A
B
C
D
Test Your Knowledge

A room is maintained at 74.0°F dry-bulb. The cooling coil selected has an apparatus dew point (ADP) of 50.0°F and a bypass factor (BF) of 0.15. If the room sensible cooling load is 116,640 Btu/hr, what supply airflow (in CFM) is required?

A
B
C
D
Test Your Knowledge

Which of the following physical coil modifications will DECREASE the coil bypass factor (BF), thereby increasing the coil contact efficiency?

A
B
C
D