3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor
Key Takeaways
- Room Sensible Heat Ratio ($\text{RSHR} = \frac{q_{s,room}}{q_{s,room} + q_{l,room}}$) determines the slope of the Room Condition Line connecting the room state to the required supply air state.
- Grand Sensible Heat Ratio ($\text{GSHR} = \frac{q_{s,total}}{q_{t,total}}$) includes ventilation loads and determines the slope of the process line connecting the mixed air state to the Apparatus Dew Point ($ADP$).
- The Apparatus Dew Point ($ADP$) is the effective surface temperature of the cooling coil where the condition line intersects the $100\%\text{ RH}$ saturation curve.
- Coil Bypass Factor ($BF$) represents the fraction of air passing through the coil unaffected: $BF = \frac{T_{leaving} - T_{adp}}{T_{entering} - T_{adp}} = \frac{W_{leaving} - W_{adp}}{W_{entering} - W_{adp}}$; Contact Factor is $CF = 1 - BF$.
- Required supply airflow accounting for coil bypass is: $\text{CFM}_{sa} = \frac{q_{s,room}}{1.08 \times (T_{room} - T_{adp}) \times (1 - BF)}$.
3.5 Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP) & Coil Bypass Factor
Designing a cooling coil requires satisfying both the sensible cooling load (temperature reduction) and the latent cooling load (moisture removal) simultaneously. The Sensible Heat Ratio (SHR), Apparatus Dew Point (ADP), and Coil Bypass Factor (BF) are the engineering parameters that link space cooling loads to physical coil construction and required airflow.
1. Sensible Heat Ratio (SHR) Definitions
Sensible Heat Ratio (also called Sensible Heat Factor, SHF) is the ratio of sensible heat to total heat:
1. Room Sensible Heat Ratio (RSHR)
Governs the slope of the Room Condition Line (RCL) on the psychrometric chart connecting the room design state ($R$) and the supply air state ($S$):
Where $q_{s,room}$ and $q_{l,room}$ include internal loads (people, lighting, equipment, envelope conduction, solar gain) but exclude outdoor ventilation air loads.
2. Grand Sensible Heat Ratio (GSHR)
Governs the slope of the Grand Condition Line (GCL) connecting the mixed air state ($M$) to the apparatus dew point ($ADP$):
Where:
- $q_{s,vent} = 1.08 \times \text{CFM}{oa} \times (T{oa} - T_{room})$
- $q_{l,vent} = 4840 \times \text{CFM}{oa} \times (W{oa} - W_{room})$
3. Effective Sensible Heat Ratio (ESHR)
Used when coil bypass factor $BF > 0$. It accounts for the fraction of outdoor ventilation air that bypasses the coil fins and enters the conditioned space directly:
2. Apparatus Dew Point (ADP) & Coil Bypass Factor (BF)
Apparatus Dew Point (ADP)
The Apparatus Dew Point is the effective average surface temperature of the cooling coil fins and tubes. Geometrically on the psychrometric chart, the $ADP$ is the point where the condition line intersects the $100%\text{ RH}$ saturation curve ($T_{db} = T_{wb} = T_{dp} = T_{adp}$).
Coil Bypass Factor ($BF$)
In a physical cooling coil, not all air molecules make direct thermal contact with the cold fin surfaces. A fraction of the air ($BF$) passes through between fins unaffected, while the remaining fraction ($1 - BF$) comes into complete thermal equilibrium at the $ADP$.
Rearranging to find leaving coil air temperature ($T_{leaving}$):
Parameters Governing Coil Bypass Factor ($BF$)
| Parameter | Change | Effect on Bypass Factor ($BF$) | Physical Reason |
|---|---|---|---|
| Number of Tube Rows | Increase (e.g., 4 to 8 rows) | Decreases $BF$ (improves contact) | Longer air residence time and more fin surface contact |
| Fin Density (FPI) | Increase (e.g., 8 to 14 fins/in) | Decreases $BF$ | Narrower air passages between fins maximize boundary layer contact |
| Coil Face Velocity | Increase (e.g., 400 to 600 FPM) | Increases $BF$ | Higher air velocity reduces residence time across coil |
| Typical DX Coils | Commercial Rooftop Units | $BF \approx 0.10 - 0.20$ | 3 to 4 rows, lower fin density |
| Typical CW Coils | Built-up Central AHUs | $BF \approx 0.03 - 0.08$ | 6 to 8 rows, higher fin density |
3. Supply Airflow (CFM) Calculation with Coil Bypass
To satisfy the room sensible cooling load ($q_{s,room}$), the supply airflow must be sized based on the temperature difference between the room design temperature ($T_{room}$) and the actual supply air temperature ($T_{supply}$):
Expressing $T_{supply}$ (leaving coil) in terms of $ADP$ and $BF$:
4. Step-by-Step Worked Example: Full SHR, ADP, and Airflow Sizing
Problem Statement
A conditioned space has a design sensible cooling load of $q_{s,room} = 194,400\text{ Btu/hr}$ and a latent cooling load of $q_{l,room} = 64,800\text{ Btu/hr}$.
- Indoor Room Design Condition: $T_{room} = 75.0^\circ\text{F}$ DB, $50%\text{ RH}$ ($W_{room} = 0.00925\text{ lb/lb}$)
- Outdoor Ventilation Air: $2,000\text{ CFM}$ at $95.0^\circ\text{F}$ DB, $78.0^\circ\text{F}$ WB ($W_{oa} = 0.0168\text{ lb/lb}$)
- Selected Chilled Water Coil: Bypass Factor $BF = 0.10$
Calculate:
- Room Sensible Heat Ratio (RSHR)
- Grand Sensible Heat Ratio (GSHR)
- Apparatus Dew Point ($ADP$) temperature from psychrometric alignment (RCL intersection with saturation curve yields $T_{adp} = 51.0^\circ\text{F}$)
- Leaving coil air temperature ($T_{leaving}$)
- Required supply airflow rate ($\text{CFM}_{sa}$)
Solution Steps
Step 1: Calculate Room Sensible Heat Ratio (RSHR)
Step 2: Calculate Ventilation Loads and GSHR
Step 3: Determine Apparatus Dew Point ($ADP$) Plotting the RSHR line ($0.75$) through the room state ($75.0^\circ\text{F}$ DB, $50%\text{ RH}$) to the saturation curve yields:
Step 4: Calculate Leaving Coil Air Temperature ($T_{leaving}$)
Step 5: Calculate Required Supply Airflow ($\text{CFM}_{sa}$) (Verification via direct formula: $\text{CFM} = \frac{194,400}{1.08 \times (1 - 0.10) \times (75 - 51)} = \frac{194,400}{1.08 \times 0.90 \times 24} = \frac{194,400}{23.328} = 8,333\text{ CFM}$).
A space has a design room sensible heat gain of 144,000 Btu/hr and a room latent heat gain of 36,000 Btu/hr. What is the Room Sensible Heat Ratio (RSHR)?
A cooling coil has an apparatus dew point (ADP) of 48.0°F and a bypass factor of 0.08. If mixed air enters the cooling coil at 80.0°F dry-bulb, what is the dry-bulb temperature of the air leaving the coil?
A room is maintained at 74.0°F dry-bulb. The cooling coil selected has an apparatus dew point (ADP) of 50.0°F and a bypass factor (BF) of 0.15. If the room sensible cooling load is 116,640 Btu/hr, what supply airflow (in CFM) is required?
Which of the following physical coil modifications will DECREASE the coil bypass factor (BF), thereby increasing the coil contact efficiency?