6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods

Key Takeaways

  • Steady-state envelope heat transmission obeys Fourier's conduction law: q = U * A * Delta_T, where overall thermal resistance R_total equals the summation of internal/external air film resistances and all intermediate material layers.

  • Thermal bridging through steel or wood framing significantly increases overall wall U-factors, requiring parallel-path thermal calculations or ASHRAE 90.1 framing correction factors (modified zone method).

  • Below-grade slab-on-grade heat loss is proportional to exposed perimeter length rather than floor area: q = F_p * P * (T_in - T_out), where F_p is the perimeter heat loss coefficient in Btu/(hr·ft·°F).

  • Infiltration airflow is calculated via the Air Change Method (CFM = ACH * Volume (ft^3) / 60) or the Crack Method, driven by wind pressure, stack effect (buoyancy), and mechanical ventilation imbalance.

  • Infiltration introduces direct sensible (q_s = 1.08 * CFM * Delta_T), latent (q_l = 4840 * CFM * Delta_W), and total (q_t = 4.5 * CFM * Delta_h) loads directly into the conditioned zone.

Last updated: August 2026

6.2 Envelope Heat Transmission & Infiltration/Exfiltration Load Methods

Building envelope heat transmission and unconditioned air infiltration represent the primary heating loads during winter design conditions and substantial components of summer sensible cooling loads. Calculating envelope loads requires evaluating the steady-state thermal resistance (RR-value) and overall heat transfer coefficient (UU-factor) of multi-layer assemblies, accounting for two-dimensional thermal bridging across structural framing members, sizing below-grade and slab-on-grade boundary losses, and quantifying infiltration air volume driven by stack effect, wind velocity, and mechanical room pressurization.


1. Steady-State Conduction & Multilayer Thermal Resistance

Under steady-state conditions with one-dimensional heat flow, the thermal transmission rate (qq) through an opaque building component of surface area AA is expressed by Fourier's law:

q=U⋅A⋅(Toutdoor−Tindoor)=A⋅ΔTRtotalq = U \cdot A \cdot (T_{\text{outdoor}} - T_{\text{indoor}}) = \frac{A \cdot \Delta T}{R_{\text{total}}}

Where:

  • q=Heat transfer rate (Btu/hr)q = \text{Heat transfer rate } (\text{Btu/hr})
  • U=Overall heat transfer coefficient (Btu/(hr⋅ft2⋅∘F))U = \text{Overall heat transfer coefficient } (\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)})
  • A=Net surface area of assembly (ft2)A = \text{Net surface area of assembly } (\text{ft}^2)
  • ΔT=Temperature difference between ambient outdoor air and indoor air (∘F)\Delta T = \text{Temperature difference between ambient outdoor air and indoor air } ({}^\circ\text{F})
  • Rtotal=Total thermal resistance of the composite assembly (hr⋅ft2⋅∘F/Btu)R_{\text{total}} = \text{Total thermal resistance of the composite assembly } (\text{hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu})
+-----------------------------------------------------------------------------------------+
| COMPOSITE MULTI-LAYER WALL THERMAL CIRCUIT                                              |
+-----------------------------------------------------------------------------------------+
| Outdoor Air (To)                                                        Indoor Air (Ti) |
|      |                                                                         |        |
|     [R_o]  ---  [R_ext_finish]  ---  [R_sheathing]  ---  [R_insul]  ---  [R_gyp] --- [R_i]  |
|  (Film Out)       (Brick/Siding)       (Plywood/OSB)     (Cavity)      (Drywall) (Film In)
+-----------------------------------------------------------------------------------------+

Overall Thermal Resistance (RtotalR_{\text{total}}) & Series Layer Summation

The total thermal resistance of an unbridged, homogeneous multi-layer assembly is the direct series sum of the individual layer resistances, including the interior (RiR_i) and exterior (RoR_o) surface air film resistances:

Rtotal=Ri+∑k=1nRk+Ro=1hi+∑k=1nxkkk+1hoR_{\text{total}} = R_i + \sum_{k=1}^n R_k + R_o = \frac{1}{h_i} + \sum_{k=1}^n \frac{x_k}{k_k} + \frac{1}{h_o} U=1RtotalU = \frac{1}{R_{\text{total}}}

Where:

  • xk=Thickness of material layer k (inches or feet)x_k = \text{Thickness of material layer } k\text{ (inches or feet)}
  • kk=Thermal conductivity of material layer k (Btu⋅in./(hr⋅ft2⋅∘F) or Btu/(hr⋅ft⋅∘F))k_k = \text{Thermal conductivity of material layer } k\text{ (Btu}\cdot\text{in./(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F) or Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)})
  • hi,ho=Inside and outside convective/radiative surface film heat transfer coefficients (Btu/(hr⋅ft2⋅∘F))h_i, h_o = \text{Inside and outside convective/radiative surface film heat transfer coefficients } (\text{Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)})

Standard Surface Air Film Resistances (RiR_i and RoR_o)

Surface Orientation & Heat Flow DirectionSurface Emittance (ε\varepsilon)Winter Condition (15 mph wind15\text{ mph wind})Summer Condition (7.5 mph wind7.5\text{ mph wind})Still Air (Indoor)
Exterior Surface (Any Orientation)ε=0.90\varepsilon = 0.90Ro=0.17 hr⋅ft2⋅∘F/BtuR_o = 0.17\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}Ro=0.25 hr⋅ft2⋅∘F/BtuR_o = 0.25\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}—
Interior Wall (Vertical, Horizontal Flow)ε=0.90\varepsilon = 0.90——Ri=0.68 hr⋅ft2⋅∘F/BtuR_i = 0.68\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}
Interior Ceiling (Horizontal, Upward Flow)ε=0.90\varepsilon = 0.90——Ri=0.61 hr⋅ft2⋅∘F/BtuR_i = 0.61\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}
Interior Floor (Horizontal, Downward Flow)ε=0.90\varepsilon = 0.90——Ri=0.92 hr⋅ft2⋅∘F/BtuR_i = 0.92\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}

2. Thermal Bridging & Parallel Heat Flow in Framed Assemblies

Framed envelope assemblies (wood studs, light-gauge steel studs, metal curtain wall mullions) contain high-conductivity structural framing that bridges the low-conductivity cavity insulation. This requires calculating an area-weighted parallel heat flow path.

+-----------------------------------------------------------------------------------------+
| PARALLEL HEAT PATHS THROUGH FRAMED WALL CAVITY                                         |
+-----------------------------------------------------------------------------------------+
| Path 1 (Through Stud / Framing):      R_path1 = R_i + R_gyp + R_stud + R_sheath + R_o   |
| Path 2 (Through Insulated Cavity):    R_path2 = R_i + R_gyp + R_cavity + R_sheath + R_o |
| Area-Weighted Overall U-factor:       U_overall = (f_frame * U_path1) + (f_cav * U_path2)|
+-----------------------------------------------------------------------------------------+

Area-Weighted Parallel Path Equation

Uoverall=fframing⋅Uframing+(1−fframing)⋅Ucavity=fframingRframing+1−fframingRcavityU_{\text{overall}} = f_{\text{framing}} \cdot U_{\text{framing}} + (1 - f_{\text{framing}}) \cdot U_{\text{cavity}} = \frac{f_{\text{framing}}}{R_{\text{framing}}} + \frac{1 - f_{\text{framing}}}{R_{\text{cavity}}}

Where fframingf_{\text{framing}} is the framing fraction (typically 0.15 to 0.250.15\text{ to }0.25 for wood framing at 16 in.16\text{ in.} or 24 in.24\text{ in.} on center, and 0.10 to 0.180.10\text{ to }0.18 for steel stud construction).

Steel Stud Thermal Derating (Modified Zone Method / ASHRAE 90.1)

Steel has a thermal conductivity (k≈314 Btu⋅in./(hr⋅ft2⋅∘F)k \approx 314\text{ Btu}\cdot\text{in./(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)}) over 300 times greater than fiberglass batt insulation (k≈0.27k \approx 0.27). Steel studs act as massive thermal shorts, derating cavity insulation effectiveness by 40% to 60%. ASHRAE Standard 90.1 provides effective cavity RR-values (ReffectiveR_{\text{effective}}):

Nominal Cavity Batt RatingSteel Stud Size & SpacingEffective Cavity RR-Value (ReffectiveR_{\text{effective}})Framing Derating Factor
R-112×4 (3.5 in.) @ 16 in. OC2\times 4\text{ (3.5 in.) @ 16 in. OC}R-5.5R\text{-}5.550%50\%
R-132×4 (3.5 in.) @ 16 in. OC2\times 4\text{ (3.5 in.) @ 16 in. OC}R-6.0R\text{-}6.046%46\%
R-192×6 (5.5 in.) @ 16 in. OC2\times 6\text{ (5.5 in.) @ 16 in. OC}R-7.1R\text{-}7.137%37\%
R-212×6 (5.5 in.) @ 16 in. OC2\times 6\text{ (5.5 in.) @ 16 in. OC}R-7.4R\text{-}7.435%35\%
R-192×6 (5.5 in.) @ 24 in. OC2\times 6\text{ (5.5 in.) @ 24 in. OC}R-8.6R\text{-}8.645%45\%

Design Rule: To meet modern energy codes (ASHRAE Standard 90.1 / IECC), steel-framed walls require continuous exterior insulation (ci) (such as rigid polyisocyanurate or extruded polystyrene) to break the framing thermal bridge.


3. Below-Grade Envelopes & Slab-on-Grade Heat Losses

Heat transfer from basements and on-grade concrete slabs does not follow simple 1D one-layer equations because ground temperature varies with depth and thermal path length through the earth increases radially.

+-----------------------------------------------------------------------------------------+
| SLAB-ON-GRADE PERIMETER HEAT FLOW DYNAMICS                                              |
+-----------------------------------------------------------------------------------------+
|                 Indoor Space (Ti)                                                       |
|                 =============================                                           |
|                 | Concrete Slab Floor       |                                           |
|     Outside     |                           | Perimeter Length P (ft)                   |
|     Air (To)    +---------------------------+                                           |
|     ~~~~~~~~~   | Perimeter Insulation (R)  |                                           |
|        |        +---------------------------+ ===> q = F_p * P * (T_in - T_out)         |
|        |              | Ground Heat Paths                                               |
|        +--------------+ (Curvilinear Earth Flow)                                        |
+-----------------------------------------------------------------------------------------+

1. Slab-on-Grade Perimeter Heat Loss Formulation

Concrete slab-on-grade heat loss occurs almost entirely around the exposed perimeter. Sizing is based on the perimeter heat loss coefficient (FpF_p) and slab perimeter length (PP):

qslab=Fp⋅P⋅(Tindoor−Toutdoor)q_{\text{slab}} = F_p \cdot P \cdot (T_{\text{indoor}} - T_{\text{outdoor}})

Where:

  • qslab=Slab heating transmission rate (Btu/hr)q_{\text{slab}} = \text{Slab heating transmission rate } (\text{Btu/hr})
  • Fp=Perimeter heat loss coefficient (Btu/(hr⋅ft⋅∘F))F_p = \text{Perimeter heat loss coefficient } (\text{Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)})
  • P=Exposed perimeter length of the slab floor (ft)P = \text{Exposed perimeter length of the slab floor } (\text{ft})
  • Tindoor−Toutdoor=Design dry-bulb temperature difference (∘F)T_{\text{indoor}} - T_{\text{outdoor}} = \text{Design dry-bulb temperature difference } ({}^\circ\text{F})

Standard FpF_p Perimeter Loss Coefficients (ASHRAE 90.1)

Slab Edge Insulation ConfigurationUnheated Slab Fp [Btu/(hr⋅ft⋅∘F)]F_p\text{ [Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)]}Heated Slab Fp [Btu/(hr⋅ft⋅∘F)]F_p\text{ [Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)]}
Uninsulated Slab0.730.731.351.35
R-5 Perimeter Insulation (12 in.12\text{ in.} depth)0.570.570.850.85
R-10 Perimeter Insulation (24 in.24\text{ in.} depth)0.540.540.780.78
R-15 Perimeter Insulation (24 in.24\text{ in.} depth)0.520.520.740.74
R-20 Fully Insulated Under Slab & Edge0.460.460.620.62

2. Below-Grade Basement Walls & Floors

Below-grade heat transfer is evaluated using depth-averaged UU-factors (UavgU_{\text{avg}}) applied to below-grade wall area (AbgA_{\text{bg}}) against ground temperature (TgroundT_{\text{ground}}):

qbasement, wall=Ubg, wall⋅Abg, wall⋅(Tindoor−Tground)q_{\text{basement, wall}} = U_{\text{bg, wall}} \cdot A_{\text{bg, wall}} \cdot (T_{\text{indoor}} - T_{\text{ground}}) qbasement, floor=Ubg, floor⋅Afloor⋅(Tindoor−Tground)q_{\text{basement, floor}} = U_{\text{bg, floor}} \cdot A_{\text{floor}} \cdot (T_{\text{indoor}} - T_{\text{ground}})

4. Infiltration & Exfiltration Load Methodologies

Infiltration is the uncontrolled ingress of outdoor air through cracks, gaps, building envelope joints, and door openings. Exfiltration is the corresponding egress of conditioned air.

Driving Physical Forces for Infiltration

  1. Wind Pressure (Velocity Head): ΔPwind=Cp⋅ρair⋅Vwind22gc\Delta P_{\text{wind}} = C_p \cdot \frac{\rho_{\text{air}} \cdot V_{\text{wind}}^2}{2 g_c} Wind creates positive pressure on the windward facade (causing infiltration) and negative suction pressure on the leeward and sidewall facades (causing exfiltration).
  2. Stack Effect (Thermal Buoyancy): ΔPstack=ρ0(ggc)h(Tindoor−ToutdoorToutdoor)\Delta P_{\text{stack}} = \rho_0 \left(\frac{g}{g_c}\right) h \left(\frac{T_{\text{indoor}} - T_{\text{outdoor}}}{T_{\text{outdoor}}}\right) During winter (Tindoor>ToutdoorT_{\text{indoor}} > T_{\text{outdoor}}), warm air rises inside the building, creating negative pressure and infiltration at the ground level, and positive pressure and exfiltration at upper levels. The height where internal and external pressures equalize is the Neutral Pressure Level (NPL).
  3. Mechanical Imbalance: Exhaust air flow in excess of supply/ventilation air creates net negative building pressure, accelerating infiltration.
+-----------------------------------------------------------------------------------------+
| WINTER STACK EFFECT & INFILTRATION PRESSURE PROFILE                                     |
+-----------------------------------------------------------------------------------------+
| Top of Building (Z = H):      P_in > P_out  -->  EXFILTRATION (Positive Pressure)       |
|                                     |                                                   |
| Neutral Pressure Level (NPL): P_in = P_out  -->  ZERO FLOW                              |
|                                     |                                                   |
| Base of Building (Z = 0):     P_in < P_out  -->  INFILTRATION (Negative Suction)        |
+-----------------------------------------------------------------------------------------+

Infiltration Volumetric Airflow Calculation Methods

1. Air Change Method

Used widely for general commercial and residential room load estimation:

CFMinf=ACH×Volume (ft3)60 min/hr\text{CFM}_{\text{inf}} = \frac{\text{ACH} \times \text{Volume }(\text{ft}^3)}{60\text{ min/hr}}

Where ACH\text{ACH} is Air Changes per Hour (0.1 to 0.3 ACH0.1\text{ to }0.3\text{ ACH} for tight commercial construction; 0.5 to 1.0 ACH0.5\text{ to }1.0\text{ ACH} for loose/older construction).

2. Crack Length Method

Based on fluid flow through window and door perimeter gaps:

CFMinf=K⋅L⋅(ΔP)n\text{CFM}_{\text{inf}} = K \cdot L \cdot (\Delta P)^n

Where LL is total crack length in feet, KK is crack flow coefficient, and nn is flow exponent (0.5≤n≤0.70.5 \le n \le 0.7).


5. Infiltration Heating & Cooling Load Synthesis

Infiltration air enters directly into the occupied space without passing through the central cooling/heating coil. It must be treated as a direct room sensible and latent load.

+-----------------------------------------------------------------------------------------+
| INFILTRATION PSYCHROMETRIC LOAD EQUATIONS (STANDARD SEA-LEVEL AIR)                      |
+-----------------------------------------------------------------------------------------+
| Sensible Load:   q_s = 1.08 * CFM_inf * (T_outdoor - T_indoor)                          |
| Latent Load:     q_l = 4840 * CFM_inf * (W_outdoor - W_indoor)                          |
| Total Load:      q_t = 4.5  * CFM_inf * (h_outdoor - h_indoor)                          |
+-----------------------------------------------------------------------------------------+
  • Winter Heating Infiltration: Both ΔT=(To−Ti)\Delta T = (T_o - T_i) and ΔW=(Wo−Wi)\Delta W = (W_o - W_i) are negative, imposing direct sensible and humidification (latent) heating loads on the zone terminal units.
  • Summer Cooling Infiltration: Hot, humid air entering the room adds to the zone Sensible Heat Ratio (RSHR) and requires coil dehumidification.

6. NCEES Reference Handbook Navigation Tactics

  • Envelope Transmission Formulas: Search "Thermal Resistance" or "Heat Transmission" to find steady-state conduction formulas (U=1/RtotalU = 1/R_{\text{total}}) and typical material thermal conductivity (kk) tables.
  • Slab-on-Grade Coefficients: Search "Slab-on-Grade" or "F_p" to locate the perimeter heat loss formula and coefficient table.
  • Air Change Method: Search "Infiltration" or "Air Changes" to locate air change rate tables and conversion formulas.

7. Worked Computational Examples

Example 1: Multilayer Steel-Stud Wall U-Factor with Thermal Bridging

An exterior wall assembly consists of the following series layers from outside to inside:

  1. Exterior air film (Ro=0.17 hr⋅ft2⋅∘F/BtuR_o = 0.17\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu})
  2. 4-inch face brick (k=9.0 Btu⋅in./(hr⋅ft2⋅∘F)k = 9.0\text{ Btu}\cdot\text{in./(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)}, R1=4/9.0=0.44 hr⋅ft2⋅∘F/BtuR_1 = 4 / 9.0 = 0.44\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu})
  3. 1-inch continuous extruded polystyrene (XPS) rigid board (R2=5.00 hr⋅ft2⋅∘F/BtuR_2 = 5.00\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu})
  4. 5/8-inch exterior gypsum sheathing (R3=0.56 hr⋅ft2⋅∘F/BtuR_3 = 0.56\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu})
  5. 2×62\times 6 light-gauge steel studs at 16 in.16\text{ in.} on center with nominal R-19 fiberglass batt cavity insulation. Per ASHRAE Standard 90.1, the effective cavity resistance is Reffective=7.10 hr⋅ft2⋅∘F/BtuR_{\text{effective}} = 7.10\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}.
  6. 5/8-inch interior gypsum wallboard (R4=0.56 hr⋅ft2⋅∘F/BtuR_4 = 0.56\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu})
  7. Interior air film (Ri=0.68 hr⋅ft2⋅∘F/BtuR_i = 0.68\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu})

Calculate: (a) The overall assembly UU-factor with thermal bridging, and (b) The total winter heat loss through a 3,000 ft23,000\text{ ft}^2 wall if Tindoor=70∘FT_{\text{indoor}} = 70^\circ\text{F} and Toutdoor=10∘FT_{\text{outdoor}} = 10^\circ\text{F}.

Solution:

  1. Sum all series resistances using the derated effective cavity resistance: Rtotal=Ro+R1+R2+R3+Reffective+R4+RiR_{\text{total}} = R_o + R_1 + R_2 + R_3 + R_{\text{effective}} + R_4 + R_i Rtotal=0.17+0.44+5.00+0.56+7.10+0.56+0.68=14.51 hr⋅ft2⋅∘F/BtuR_{\text{total}} = 0.17 + 0.44 + 5.00 + 0.56 + 7.10 + 0.56 + 0.68 = 14.51\text{ hr}\cdot\text{ft}^2\cdot{}^\circ\text{F/Btu}
  2. Calculate overall UU-factor: U=1Rtotal=114.51=0.0689 Btu/(hr⋅ft2⋅∘F)U = \frac{1}{R_{\text{total}}} = \frac{1}{14.51} = 0.0689\text{ Btu/(hr}\cdot\text{ft}^2\cdot{}^\circ\text{F)}
  3. Calculate total winter steady-state transmission heat loss: ΔT=70−10=60∘F\Delta T = 70 - 10 = 60^\circ\text{F} q=U⋅A⋅ΔT=0.0689×3,000 ft2×60∘F=12,402 Btu/hrq = U \cdot A \cdot \Delta T = 0.0689 \times 3,000\text{ ft}^2 \times 60^\circ\text{F} = 12,402\text{ Btu/hr}

(Note: If thermal bridging were ignored and nominal R-19 were used without derating, Rtotal=26.41R_{\text{total}} = 26.41, giving q=6,815 Btu/hrq = 6,815\text{ Btu/hr}—an underestimation of 45%!)


Example 2: Infiltration & Slab-on-Grade Combined Heating Load

A standalone commercial building in Columbus, OH has the following characteristics:

  • Building floor plan: 100 ft×60 ft100\text{ ft} \times 60\text{ ft} rectangle (Afloor=6,000 ft2A_{\text{floor}} = 6,000\text{ ft}^2, ceiling height 12 ft12\text{ ft}).
  • Unheated concrete slab-on-grade floor with R-10 perimeter insulation (Fp=0.54 Btu/(hr⋅ft⋅∘F)F_p = 0.54\text{ Btu/(hr}\cdot\text{ft}\cdot{}^\circ\text{F)}).
  • Infiltration rate: 0.35 ACH0.35\text{ ACH}.
  • Indoor winter design conditions: 70∘F70^\circ\text{F} DB, 30% RH30\%\text{ RH} (Wi=0.00470 lbw/lbdaW_i = 0.00470\text{ lb}_w/\text{lb}_{da}).
  • Outdoor winter design conditions (99.6%): 2∘F2^\circ\text{F} DB, 80% RH80\%\text{ RH} (Wo=0.00085 lbw/lbdaW_o = 0.00085\text{ lb}_w/\text{lb}_{da}).

Calculate: (a) The perimeter slab-on-grade heat loss, (b) Infiltration volumetric airflow, (c) Infiltration sensible heating load, and (d) Infiltration humidification (latent) heating load.

Solution:

  1. Slab-on-grade perimeter heat loss: P=2×(100+60)=320 ftP = 2 \times (100 + 60) = 320\text{ ft} ΔT=70−2=68∘F\Delta T = 70 - 2 = 68^\circ\text{F} qslab=Fp⋅P⋅ΔT=0.54×320×68=11,750.4 Btu/hrq_{\text{slab}} = F_p \cdot P \cdot \Delta T = 0.54 \times 320 \times 68 = 11,750.4\text{ Btu/hr}
  2. Infiltration volumetric airflow: Volume =6,000 ft2×12 ft=72,000 ft3\text{Volume } = 6,000\text{ ft}^2 \times 12\text{ ft} = 72,000\text{ ft}^3 CFMinf=0.35×72,000 ft360 min/hr=420 CFM\text{CFM}_{\text{inf}} = \frac{0.35 \times 72,000\text{ ft}^3}{60\text{ min/hr}} = 420\text{ CFM}
  3. Infiltration sensible heating load: qs,inf=1.08×CFMinf×(Ti−To)=1.08×420×68=30,844.8 Btu/hrq_{s,\text{inf}} = 1.08 \times \text{CFM}_{\text{inf}} \times (T_i - T_o) = 1.08 \times 420 \times 68 = 30,844.8\text{ Btu/hr}
  4. Infiltration latent (humidification) heating load: ΔW=0.00470−0.00085=0.00385 lbw/lbda\Delta W = 0.00470 - 0.00085 = 0.00385\text{ lb}_w/\text{lb}_{da} ql,inf=4840×CFMinf×ΔW=4840×420×0.00385=7,826.3 Btu/hrq_{l,\text{inf}} = 4840 \times \text{CFM}_{\text{inf}} \times \Delta W = 4840 \times 420 \times 0.00385 = 7,826.3\text{ Btu/hr}
  5. Total combined zone heating load from slab edge and infiltration: qtotal=11,750.4+30,844.8+7,826.3=50,421.5 Btu/hr=50.42 MBHq_{\text{total}} = 11,750.4 + 30,844.8 + 7,826.3 = 50,421.5\text{ Btu/hr} = 50.42\text{ MBH}
Test Your Knowledge

A framed exterior wall is constructed of 2x6 steel studs spaced at 16 inches on center with nominal R-19 fiberglass batt insulation in the cavity. According to ASHRAE Standard 90.1 thermal bridging data, the effective cavity resistance is derated to R-7.10 hr·ft2·°F/Btu. The assembly includes exterior air film (R-0.17), 1-inch continuous exterior insulation (R-5.00), 5/8-inch gypsum sheathing (R-0.56), 5/8-inch interior gypsum wallboard (R-0.56), and interior air film (R-0.68). What is the overall U-factor of the wall assembly?

A

0.0711 Btu/(hr·ft2·°F)

B

0.0374 Btu/(hr·ft2·°F)

C

0.0950 Btu/(hr·ft2·°F)

D

0.1408 Btu/(hr·ft2·°F)

Test Your Knowledge

An unheated commercial warehouse has a 150 ft by 80 ft rectangular slab-on-grade concrete floor. The perimeter of the slab is insulated with R-10 vertical edge insulation having a perimeter heat loss coefficient F_p = 0.54 Btu/(hr·ft·°F). What is the total slab heat loss when the indoor temperature is 68°F and the outdoor design temperature is -2°F?

A

18,878 Btu/hr

B

17,424 Btu/hr

C

28,224 Btu/hr

D

453,600 Btu/hr

Test Your Knowledge

A retail store with an internal volume of 90,000 ft3 has an estimated infiltration rate of 0.40 air changes per hour (ACH). If the indoor space is maintained at 72°F DB and the outdoor winter design temperature is 12°F DB, what is the sensible heating load imposed by infiltration?

A

23,328 Btu/hr

B

58,320 Btu/hr

C

38,880 Btu/hr

D

19,440 Btu/hr

Test Your Knowledge

During cold winter weather, stack effect creates a vertical pressure gradient across a high-rise building envelope. Which statement accurately describes the pressure distribution and air movement across the building facade?

A

Positive pressure exists at the ground floor causing exfiltration, while negative pressure exists at the top floor causing infiltration.

B

Uniform positive pressure exists across the entire height of the building facade regardless of temperature difference.

C

Stack effect pressure depends solely on wind velocity and is independent of indoor-to-outdoor temperature difference.

D

Negative pressure exists at the base of the building causing infiltration, and positive pressure exists at upper floors causing exfiltration, separated by the Neutral Pressure Level.

Sections you finish are checked off in the contents.