3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft)

Key Takeaways

  • Standard sea level barometric pressure is 14.696 psia14.696\text{ psia} (29.921 in. Hg=101.325 kPa29.921\text{ in. Hg} = 101.325\text{ kPa}); at 5,000 ft5,000\text{ ft} altitude (e.g., Denver), barometric pressure drops to 12.23 psia12.23\text{ psia} (24.89 in. Hg=84.3 kPa24.89\text{ in. Hg} = 84.3\text{ kPa}).

  • Because total pressure PP is reduced at altitude, the humidity ratio W=0.622pvP−pvW = 0.622 \frac{p_v}{P - p_v} and specific volume v=RTP−pvv = \frac{R T}{P - p_v} are significantly higher for identical dry-bulb and dew-point temperatures.

  • Standard air equations (qs=1.08×CFM×ΔTq_s = 1.08 \times \text{CFM} \times \Delta T, ql=4840×CFM×ΔWq_l = 4840 \times \text{CFM} \times \Delta W, qt=4.5×CFM×Δhq_t = 4.5 \times \text{CFM} \times \Delta h) apply ONLY to standard sea-level air density (ρ=0.075 lb/ft3\rho = 0.075\text{ lb/ft}^3, cp=0.24 Btu/lb⋅∘Fc_p = 0.24\text{ Btu/lb}\cdot^\circ\text{F}).

  • At altitude, equations must be adjusted using actual density: qs=60ρcp×ACFM×ΔTq_s = 60 \rho c_p \times \text{ACFM} \times \Delta T, ql=60ρhfg×ACFM×ΔWq_l = 60 \rho h_{fg} \times \text{ACFM} \times \Delta W, and qt=60ρ×ACFM×Δhq_t = 60 \rho \times \text{ACFM} \times \Delta h. At 5,000 ft5,000\text{ ft}, the sensible constant drops from 1.081.08 to ≈0.90\approx 0.90.

  • To deliver the identical mass flow rate (m˙da\dot{m}_{da}) and cooling capacity at high elevation, fans must move a proportionally greater volumetric flow rate (ACFM=SCFM×ρstdρalt\text{ACFM} = \text{SCFM} \times \frac{\rho_{std}}{\rho_{alt}}).

Last updated: August 2026

3.2 Chart Reading & Psychrometric Equations at Sea Level vs. Altitude (5,000 ft)

In standard HVAC design, engineers frequently rely on standard sea-level psychrometric charts and rule-of-thumb thermal equations. However, on the PE Mechanical exam, questions involving high altitude (such as 5,000 ft in Denver, CO) are classic test items designed to verify that candidates understand the underlying physics rather than blindly plugging numbers into standard formulas.


1. Atmospheric Pressure Variation with Altitude

The U.S. Standard Atmosphere model defines atmospheric barometric pressure PP as a function of altitude ZZ (in feet) above sea level up to 36,000 ft36,000\text{ ft}:

P=14.696(1−6.8754×10−6Z)5.2559[psia]P = 14.696 \left( 1 - 6.8754 \times 10^{-6} Z \right)^{5.2559} \quad [\text{psia}] orP=29.921(1−6.8754×10−6Z)5.2559[in. Hg]\text{or} \quad P = 29.921 \left( 1 - 6.8754 \times 10^{-6} Z \right)^{5.2559} \quad [\text{in. Hg}]

Barometric Pressures and Densities Across Key Elevations

Altitude (ZZ)Pressure (psia)Pressure (in. Hg)Pressure (kPa)Approx. Air Density ρ\rho (70∘F70^\circ\text{F})Density Ratio (ρ/ρ0\rho/\rho_0)
0 ft (Sea Level)14.69614.69629.92129.921101.325101.3250.0750 lb/ft30.0750\text{ lb/ft}^31.0001.000
2,500 ft13.41113.41127.30327.30392.46492.4640.0684 lb/ft30.0684\text{ lb/ft}^30.9120.912
5,000 ft (Denver)12.22812.22824.89424.89484.30784.3070.0624 lb/ft30.0624\text{ lb/ft}^30.8320.832
7,500 ft11.12911.12922.65722.65776.73276.7320.0568 lb/ft30.0568\text{ lb/ft}^30.7570.757
10,000 ft10.10810.10820.57720.57769.69169.6910.0516 lb/ft30.0516\text{ lb/ft}^30.6880.688

2. Impact of Altitude on Psychrometric Properties

When altitude increases and total barometric pressure PP decreases:

  1. Humidity Ratio (WW):

    W=0.62198pvP−pvW = 0.62198 \frac{p_v}{P - p_v}

    For a given dew-point temperature (fixed partial vapor pressure pvp_v), as PP decreases, the denominator (P−pv)(P - p_v) becomes smaller. Therefore, the humidity ratio WW is significantly higher at altitude for the same dry-bulb and dew-point temperatures.

  2. Specific Volume (vv):

    v=RdaTP−pvv = \frac{R_{da} T}{P - p_v}

    As PP decreases, specific volume vv expands (air becomes less dense). At 5,000 ft5,000\text{ ft}, vv is approximately 20%20\% greater than at sea level for the same temperature.

  3. Specific Enthalpy (hh):

    h=0.240Tdb+W(1061+0.444Tdb)h = 0.240 T_{db} + W (1061 + 0.444 T_{db})

    Because WW is higher at altitude for the same relative humidity and dry bulb, the specific enthalpy of moist air is higher at altitude.

  4. Saturation Curve Shift: On an altitude psychrometric chart (such as ASHRAE Chart #2 for 5,000 ft5,000\text{ ft}), the saturation curve shifts upward and to the left compared to the sea-level chart (Chart #1).

Loading diagram...
Shift of Saturation Curve & Humidity Ratio at 5,000 ft vs. Sea Level

3. Derivation of Heat Transfer Rate Equations: Sea Level vs. Altitude

All continuous-flow thermal energy equations originate from First Law mass and energy rate balances:

q˙=m˙daΔh=(ρ×60×CFM)×Δh\dot{q} = \dot{m}_{da} \Delta h = (\rho \times 60 \times \text{CFM}) \times \Delta h

Sensible Heat Transfer Rate (q˙s\dot{q}_s)

q˙s=m˙dacp,maΔT=(60×ρ×CFM)×cp,ma×ΔT\dot{q}_s = \dot{m}_{da} c_{p,ma} \Delta T = (60 \times \rho \times \text{CFM}) \times c_{p,ma} \times \Delta T
  • At Sea Level Standard Conditions:

    • ρstd=0.0750 lbm/ft3\rho_{std} = 0.0750\text{ lb}_m/\text{ft}^3
    • cp,ma=cp,da+Wcp,v≈0.240+(0.010)(0.444)=0.244 Btu/(lbm⋅∘F)c_{p,ma} = c_{p,da} + W c_{p,v} \approx 0.240 + (0.010)(0.444) = 0.244\text{ Btu}/(\text{lb}_m\cdot^\circ\text{F})
    • Constant Cs=60×0.0750×0.240=1.08 Btu/(hr⋅CFM⋅∘F)C_s = 60 \times 0.0750 \times 0.240 = 1.08\text{ Btu}/(\text{hr}\cdot\text{CFM}\cdot^\circ\text{F}) (or 1.101.10 using 0.2440.244)
    q˙s=1.08×CFM×(T2−T1)[Btu/hr]\dot{q}_s = 1.08 \times \text{CFM} \times (T_2 - T_1) \quad [\text{Btu/hr}]
  • At 5,000 ft Altitude (Denver):

    • ρalt=0.0624 lbm/ft3\rho_{alt} = 0.0624\text{ lb}_m/\text{ft}^3
    • Constant Cs,alt=60×0.0624×0.240=0.8986≈0.90 Btu/(hr⋅ACFM⋅∘F)C_{s,alt} = 60 \times 0.0624 \times 0.240 = 0.8986 \approx 0.90\text{ Btu}/(\text{hr}\cdot\text{ACFM}\cdot^\circ\text{F})
    q˙s=0.90×ACFM×(T2−T1)[Btu/hr]\dot{q}_s = 0.90 \times \text{ACFM} \times (T_2 - T_1) \quad [\text{Btu/hr}]

Latent Heat Transfer Rate (q˙l\dot{q}_l)

q˙l=m˙dahfgΔW=(60×ρ×CFM)×hfg×ΔW\dot{q}_l = \dot{m}_{da} h_{fg} \Delta W = (60 \times \rho \times \text{CFM}) \times h_{fg} \times \Delta W
  • At Sea Level Standard Conditions (hfg≈1060 Btu/lbwh_{fg} \approx 1060\text{ Btu/lb}_w):

    • Constant Cl=60×0.0750×1060=4770≈4840 Btu⋅lbda/(hr⋅CFM⋅lbw)C_l = 60 \times 0.0750 \times 1060 = 4770 \approx 4840\text{ Btu}\cdot\text{lb}_{da}/(\text{hr}\cdot\text{CFM}\cdot\text{lb}_w)
    q˙l=4840×CFM×(W2−W1)[Btu/hr,W in lb/lb]\dot{q}_l = 4840 \times \text{CFM} \times (W_2 - W_1) \quad [\text{Btu/hr}, W \text{ in lb/lb}]
    • In grains of moisture (1 lb=7000 grains1\text{ lb} = 7000\text{ grains}):
    q˙l=48407000×CFM×ΔWgrains=0.69×CFM×ΔWgrains[Btu/hr]\dot{q}_l = \frac{4840}{7000} \times \text{CFM} \times \Delta W_{\text{grains}} = 0.69 \times \text{CFM} \times \Delta W_{\text{grains}} \quad [\text{Btu/hr}]
  • At 5,000 ft Altitude:

    • Constant Cl,alt=60×0.0624×1060=3968≈4000 Btu⋅lbda/(hr⋅ACFM⋅lbw)C_{l,alt} = 60 \times 0.0624 \times 1060 = 3968 \approx 4000\text{ Btu}\cdot\text{lb}_{da}/(\text{hr}\cdot\text{ACFM}\cdot\text{lb}_w)
    q˙l=4000×ACFM×(W2−W1)[Btu/hr,W in lb/lb]\dot{q}_l = 4000 \times \text{ACFM} \times (W_2 - W_1) \quad [\text{Btu/hr}, W \text{ in lb/lb}] q˙l=0.57×ACFM×ΔWgrains[Btu/hr]\dot{q}_l = 0.57 \times \text{ACFM} \times \Delta W_{\text{grains}} \quad [\text{Btu/hr}]

Total Heat Transfer Rate (q˙t\dot{q}_t)

q˙t=m˙daΔh=(60×ρ×CFM)×Δh\dot{q}_t = \dot{m}_{da} \Delta h = (60 \times \rho \times \text{CFM}) \times \Delta h
  • At Sea Level: Ct=60×0.0750=4.5 lbm/(hr⋅CFM)C_t = 60 \times 0.0750 = 4.5\text{ lb}_m/(\text{hr}\cdot\text{CFM})

    q˙t=4.5×CFM×(h2−h1)[Btu/hr]\dot{q}_t = 4.5 \times \text{CFM} \times (h_2 - h_1) \quad [\text{Btu/hr}]
  • At 5,000 ft Altitude: Ct,alt=60×0.0624=3.74 lbm/(hr⋅ACFM)C_{t,alt} = 60 \times 0.0624 = 3.74\text{ lb}_m/(\text{hr}\cdot\text{ACFM})

    q˙t=3.74×ACFM×(h2−h1)[Btu/hr]\dot{q}_t = 3.74 \times \text{ACFM} \times (h_2 - h_1) \quad [\text{Btu/hr}]

4. Airflow Conversion: Standard CFM (SCFM) vs. Actual CFM (ACFM)

In HVAC equipment specifications, airflow can be expressed in two ways:

  • Standard CFM (SCFM): Volumetric flow referenced to standard sea-level air density (ρstd=0.075 lb/ft3\rho_{std} = 0.075\text{ lb/ft}^3). SCFM is directly proportional to mass flow rate: m˙da=60×0.075×SCFM=4.5×SCFM [lb/hr]\dot{m}_{da} = 60 \times 0.075 \times \text{SCFM} = 4.5 \times \text{SCFM} \text{ [lb/hr]}.
  • Actual CFM (ACFM): The physical volume of air moving through the duct or fan per minute at actual operating pressure and temperature: m˙da=60×ρactual×ACFM\dot{m}_{da} = 60 \times \rho_{actual} \times \text{ACFM}.

Equating dry air mass flow rates:

ACFM=SCFM×(ρstdρactual)=SCFM×(P0P)×(TT0)\text{ACFM} = \text{SCFM} \times \left( \frac{\rho_{std}}{\rho_{actual}} \right) = \text{SCFM} \times \left( \frac{P_0}{P} \right) \times \left( \frac{T}{T_0} \right)

Key Exam Rule of Thumb: For a given sensible cooling load (qsq_s) and supply air temperature differential (ΔT\Delta T), a fan at 5,000 ft must deliver 20% MORE actual CFM (ACFM) than at sea level to achieve the same cooling capacity: ACFM5000CFMsl=1.080.90=1.20\frac{\text{ACFM}_{5000}}{\text{CFM}_{sl}} = \frac{1.08}{0.90} = 1.20

5. Step-by-Step Worked Example: High-Altitude Cooling Coil Sizing

Problem Statement

A commercial building located in Denver, Colorado (elevation 5,000 ft5,000\text{ ft}, barometric pressure P=12.23 psiaP = 12.23\text{ psia}, air density ρ=0.0624 lb/ft3\rho = 0.0624\text{ lb/ft}^3) has a calculated space sensible cooling load of qs=180,000 Btu/hrq_s = 180,000\text{ Btu/hr} and a space latent cooling load of ql=40,000 Btu/hrq_l = 40,000\text{ Btu/hr}.

The indoor design condition is 75.0∘F75.0^\circ\text{F} DB and 50% RH50\%\text{ RH}. The supply air temperature leaving the AHU is 55.0∘F55.0^\circ\text{F} DB.

Calculate:

  1. Required supply airflow in Actual CFM (ACFM) at 5,000 ft5,000\text{ ft}
  2. What airflow would have been required if the identical building were located at sea level
  3. The total cooling coil load in tons of refrigeration at 5,000 ft5,000\text{ ft}, assuming entering coil air enthalpy h1=33.2 Btu/lbdah_1 = 33.2\text{ Btu/lb}_{da} and leaving coil air enthalpy h2=23.1 Btu/lbdah_2 = 23.1\text{ Btu/lb}_{da}

Solution Steps

Step 1: Calculate sensible heat constant at 5,000 ft

Cs,alt=60×ρalt×cp=60×0.0624×0.240=0.8986≈0.90 Btu/(hr⋅ACFM⋅∘F)C_{s,alt} = 60 \times \rho_{alt} \times c_p = 60 \times 0.0624 \times 0.240 = 0.8986 \approx 0.90\text{ Btu}/(\text{hr}\cdot\text{ACFM}\cdot^\circ\text{F})

Step 2: Calculate required supply airflow at 5,000 ft

ΔT=Troom−Tsupply=75.0∘F−55.0∘F=20.0∘F\Delta T = T_{room} - T_{supply} = 75.0^\circ\text{F} - 55.0^\circ\text{F} = 20.0^\circ\text{F} ACFM=qsCs,alt×ΔT=180,0000.8986×20.0=180,00017.971=10,016 ACFM≈10,000 ACFM\text{ACFM} = \frac{q_s}{C_{s,alt} \times \Delta T} = \frac{180,000}{0.8986 \times 20.0} = \frac{180,000}{17.971} = 10,016\text{ ACFM} \approx 10,000\text{ ACFM}

Step 3: Calculate required airflow at sea level

CFMsl=qs1.08×ΔT=180,0001.08×20.0=180,00021.60=8,333 CFM\text{CFM}_{sl} = \frac{q_s}{1.08 \times \Delta T} = \frac{180,000}{1.08 \times 20.0} = \frac{180,000}{21.60} = 8,333\text{ CFM} Airflow Ratio=10,0168,333=1.202(+20.2% increase)\text{Airflow Ratio} = \frac{10,016}{8,333} = 1.202 \quad (+20.2\%\text{ increase})

Step 4: Calculate total cooling coil capacity at 5,000 ft

Ct,alt=60×ρalt=60×0.0624=3.744 lbm/(hr⋅ACFM)C_{t,alt} = 60 \times \rho_{alt} = 60 \times 0.0624 = 3.744\text{ lb}_m/(\text{hr}\cdot\text{ACFM}) q˙total=Ct,alt×ACFM×(h1−h2)\dot{q}_{total} = C_{t,alt} \times \text{ACFM} \times (h_1 - h_2) q˙total=3.744×10,016×(33.2−23.1)=3.744×10,016×10.1=378,749 Btu/hr\dot{q}_{total} = 3.744 \times 10,016 \times (33.2 - 23.1) = 3.744 \times 10,016 \times 10.1 = 378,749\text{ Btu/hr} Tons of Refrigeration=378,749 Btu/hr12,000 Btu/hr⋅ton=31.56 tons\text{Tons of Refrigeration} = \frac{378,749\text{ Btu/hr}}{12,000\text{ Btu/hr}\cdot\text{ton}} = 31.56\text{ tons}

(Note: If calculated using standard sea level 4.5 factor incorrectly: 4.5×10,016×10.1=455,227 Btu/hr=37.9 tons4.5 \times 10,016 \times 10.1 = 455,227\text{ Btu/hr} = 37.9\text{ tons}, resulting in a 20%20\% equipment oversizing error!)

Test Your Knowledge

A heating coil in Albuquerque, New Mexico (elevation 5,000 ft, barometric pressure 12.23 psia, air density 0.0624 lb_m/ft^3) warms 4,500 ACFM of air from 35°F to 95°F. What is the required sensible heating capacity of the coil in Btu/hr?

A

291,600 Btu/hr

B

242,600 Btu/hr

C

324,000 Btu/hr

D

350,000 Btu/hr

Test Your Knowledge

Two identical parcels of moist air at sea level (14.696 psia) and at 5,000 ft altitude (12.228 psia) share the exact same dry-bulb temperature of 80°F and the exact same dew-point temperature of 60°F (partial vapor pressure p_v = 0.2563 psia). How does the humidity ratio at 5,000 ft (W_alt) compare to that at sea level (W_sl)?

A

W_alt is approximately 20.6% lower than W_sl

B

W_alt is equal to W_sl because the dew-point temperature is identical

C

W_alt is approximately 20.6% higher than W_sl

D

W_alt is 50% higher than W_sl

Test Your Knowledge

A supply fan designed to satisfy a space cooling load delivers 6,000 CFM of standard sea-level air (rho = 0.075 lb/ft^3). If the same system is installed in Denver (rho = 0.0624 lb/ft^3) and must deliver the exact same mass flow rate of dry air (lb_m/hr), what volumetric airflow (in ACFM) must the fan deliver?

A

4,992 ACFM

B

6,000 ACFM

C

8,333 ACFM

D

7,212 ACFM

Test Your Knowledge

Which of the following describes the visual transformation of the ASHRAE psychrometric chart when constructed for high altitude (e.g., 5,000 ft, barometric pressure 12.23 psia) compared to the standard sea-level chart?

A

The saturation curve shifts upward and to the left; for a given dry-bulb and relative humidity, the humidity ratio W is higher

B

The saturation curve shifts down and to the right; humidity ratio lines shift downward for any given wet-bulb temperature

C

The enthalpy lines become perfectly horizontal and align with dry-bulb temperature lines

D

The specific volume lines become vertical and align with dry-bulb temperature lines

Sections you finish are checked off in the contents.