10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI)
Key Takeaways
Variable Air Volume (VAV) systems modulate zone supply airflow to match sensible cooling loads while maintaining constant supply temperature, relying on minimum airflow setpoints ( to ) to satisfy ASHRAE 62.1 ventilation.
Series Fan-Powered VAV terminal units run their internal fan continuously to deliver constant airflow to space diffusers, mixing cold primary air with warm plenum air to eliminate cold air dumping and maintain constant room air motion.
Parallel Fan-Powered VAV terminal units operate their fan intermittently only during heating/reheat mode, offering lower annual fan electrical consumption than series units but exhibiting backdraft damper leakage.
The Air Diffusion Performance Index (ADPI) defines the percentage of occupied zone points where Effective Draft Temperature is at air velocity , where .
Diffuser selection optimizes the Throw-to-Length ratio (), relying on the Coanda effect (ceiling surface attachment) to induce room air and prevent cold supply air from dumping into the occupied zone at low VAV part-load airflows.
10.5 Variable Air Volume (VAV) Systems, Terminal Boxes & Space Air Diffusion (ADPI)
Variable Air Volume (VAV) systems are the predominant air distribution design for modern commercial and institutional office buildings. Rather than varying supply air temperature at a constant flow rate, a VAV system delivers conditioned air at a constant supply temperature (typically / ) while modulating volumetric airflow rate () to match dynamic zone sensible thermal loads. On the PE Mechanical: HVAC and Refrigeration exam, VAV and air diffusion problems evaluate terminal box architectures (single-duct, series/parallel fan-powered), dual-maximum reheat sequences, Effective Draft Temperature (), Air Diffusion Performance Index (ADPI), diffuser throw selection, and duct static pressure reset algorithms.
1. VAV Terminal Box Architectures & Operational Sequences
VAV terminal boxes (often called VAV units) regulate primary cold air entering individual thermal zones from the central AHU supply trunk.
+---------------------------------------------------------------------------------------------------------+
| VAV TERMINAL UNIT ARCHITECTURES |
+---------------------------------------------------------------------------------------------------------+
| |
| 1. SINGLE-DUCT VAV WITH REHEAT: |
| Primary Air (55°F) ===> [ Airflow Sensor + Damper ] ===> [ Reheat Coil (HW/Elec) ] ===> Diffusers |
| |
| 2. SERIES FAN-POWERED VAV (Constant Volume to Space): |
| Primary Air (55°F) ===\ |
| [ Continuous Terminal Fan ] ===> [ Reheat Coil ] ===> Diffusers (Constant CFM)|
| Plenum Return (75°F) ==/ |
| |
| 3. PARALLEL FAN-POWERED VAV (Variable Volume to Space): |
| Primary Air (55°F) ====================================> [ Reheat Coil ] ===> Diffusers (Variable) |
| ^ |
| Plenum Return (75°F) ===> [ Backdraft Damper + Fan ] ========/ (Fan runs ONLY during Reheat) |
+---------------------------------------------------------------------------------------------------------+
Detailed Engineering Comparison: Terminal Unit Types
| Feature / Parameter | Single-Duct VAV | Series Fan-Powered VAV (FPU) | Parallel Fan-Powered VAV (FPU) |
|---|---|---|---|
| Terminal Fan Operation | No internal fan; relies 100% on central AHU fan. | Terminal fan runs continuously whenever space is occupied. | Terminal fan runs intermittently (only during heating/reheat mode). |
| Airflow Delivered to Room | Variable: Drops from 100% cooling max down to 20%-30% minimum airflow. | Constant: Delivers 100% constant design airflow to diffusers at all times. | Variable: Variable in cooling (primary only); constant total in heating (primary min + fan). |
| Plenum Air Induction | Zero plenum air induction. | Induces warm ceiling plenum air () as primary damper modulates closed. | Induces warm plenum air only when terminal fan cycles energized. |
| Diffuser Performance at Low Load | High risk of cold air dumping if diffuser throw decays at minimum CFM. | Zero dumping risk: Constant airflow preserves diffuser throw, induction, and room air mixing. | Moderate dumping risk during low-load deadband cooling before fan starts. |
| Acoustic Characteristics | Quietest operation; sound generated only by primary damper throttling. | Constant white noise floor; sound does not change between heating and cooling. | Intermittent noise stepping when terminal fan cycles on and off (can annoy occupants). |
| Annual Fan Energy | Lowest fan energy; central VFD fan handles all airflow. | Higher annual fan kWh (small fractional HP terminal motors run continuously). | Low fan energy; terminal fan runs only during heating hours. |
2. ASHRAE 90.1 Dual-Maximum Control Logic
Energy conservation standards (ASHRAE Standard 90.1) prohibit simultaneous heating and cooling (reheating primary cold air) unless airflow is throttled to a minimum ventilation baseline.
ASHRAE 90.1 DUAL-MAXIMUM VAV CONTROL SEQUENCE:
Airflow (CFM)
^
Max +=============== ==============+ Max Heating
Cool | \ / | Flow (~50%)
Flow | \ / (Zone calls |
| \ / for heat) |
Min | \ / |
Flow | +=====================================+ |
| | DEADBAND (No Heat / No Cool) | |
+-------------------+-------------------------------------+------------------+------> Zone Temp
68°F 72°F
[ Cooling Mode ] [ Reheat Valve CLOSED ] [ Heating Mode: Reheat Active ]
- Cooling Mode (): Reheat coil valve is closed. Primary damper modulates between ( to of maximum) and ().
- Deadband (): Primary damper stays at to satisfy ASHRAE 62.1 outdoor air ventilation. Reheat valve remains closed.
- Heating Mode (): As zone temperature drops, the reheat coil modulates open while maintaining . If maximum supply water temperature limit is reached ( to prevent ceiling thermal stratification), the damper is permitted to increase airflow up to (typically of cooling max).
3. Space Air Diffusion & Air Diffusion Performance Index (ADPI)
Space air diffusion is the aerodynamic process of distributing conditioned air into an occupied room to achieve uniform temperature, humidity, and velocity distribution without generating drafts or stagnant zones.
Occupied Zone Boundaries
ASHRAE Standard 55 defines the occupied zone as the room volume between:
- Floor level to () above the floor.
- () inward from perimeter walls or stationary air conditioning equipment.
CEILING AIR DIFFUSER DISCHARGE JET & COANDA ATTACHMENT:
[ Supply Diffuser ]
===================+===================================== Ceiling Surface
| ---> Supply Jet Clings to Ceiling (Coanda Effect)
| Entrains Room Air & Warms Up
|
| Drop (d)
\ /
\ /
v v
+--------------------------------------------------------+ <--- 6.0 ft Occupied Zone Ceiling
| |
| OCCUPIED ZONE (-3°F <= Effective Draft Temp <= +2°F) |
| Air Velocity: 30 FPM <= Vx <= 70 FPM (Ideal Comfort) |
| |
+--------------------------------------------------------+ <--- Floor Level
Effective Draft Temperature ()
Thermal comfort combines air temperature differences and local convective air velocity. The Effective Draft Temperature () is defined by ASHRAE Fundamentals as:
Where:
- = Effective Draft Temperature ()
- = Local airstream dry-bulb temperature at test point ()
- = Average room control dry-bulb temperature ()
- = Local air velocity at test point in feet per minute ()
ADPI Comfort Criteria
A test point within the occupied zone satisfies thermal comfort if:
- If : Occupants perceive an unacceptable cold draft.
- If : Occupants perceive stagnant, stuffy conditions.
- If : Excessive air movement causes draft discomfort regardless of temperature.
Air Diffusion Performance Index (ADPI) Definition
Design Target: A high-performance air distribution system achieves across both full-load and part-load VAV operating conditions.
4. Diffuser Throw, Induction & The Coanda Effect
Key Diffuser Aerodynamic Metrics
- Throw (): The linear distance from the diffuser face to the point where the discharge jet centerline velocity decays to , , or .
- Characteristic Room Length (): The distance from the diffuser centerline to the nearest wall or to the mid-point collision line between opposing diffusers.
- Throw-to-Length Ratio (): The primary engineering sizing ratio for diffuser selection to maximize ADPI.
- Coanda Effect (Surface Attachment): When cold air is discharged parallel to a ceiling, the constraint of the solid surface prevents ambient air from being entrained from above. This generates a localized low-pressure zone between the air jet and ceiling, causing the jet to cling to the ceiling surface for extended distances. This surface attachment allows cold primary air () to induce warm room air and temper to before dropping into the occupied space.
Optimal Sizing Matrix for Maximum ADPI
| Diffuser Type | Characteristic Length () | Optimal Ratio | Max ADPI Achievable |
|---|---|---|---|
| Louvered / Cone Ceiling Diffuser (4-Way) | Distance to wall or mid-point | to (Peak at ) | to |
| Perforated Face Diffuser | Distance to wall or mid-point | to (Peak at ) | to |
| Linear Slot Diffuser | Distance to wall perpendicular to slot | to (Peak at ) | to |
| High-Induction Swirl Diffuser | Distance to mid-point | to (Peak at ) | to |
5. Duct Static Pressure Reset (Trim and Respond)
ASHRAE Standard 90.1 mandates that multi-zone VAV systems with DDC controls implement dynamic static pressure reset.
- Traditional Control: Supply fan modulates VFD to maintain a fixed static pressure setpoint () measured at a static pressure sensor located down the main duct trunk.
- Trim and Respond Algorithm: The building automation system (BAS) continuously monitors all VAV box damper positions. If the most open damper is only open, the AHU fan speed is trimmed downward, dropping the duct static setpoint until at least one critical VAV box damper opens to to .
- Energy Impact: Reducing duct static pressure from down to during part-load hours slashes central fan electrical consumption by to while eliminating high-pressure duct hiss.
6. Worked Example: VAV Box Mixed Air & ADPI Point Evaluation
Problem: A Series Fan-Powered Terminal Unit (FPU) serves a corner conference room. The terminal fan delivers a constant airflow of to four ceiling diffusers. Primary cold air is supplied at (). Ceiling plenum return air is at (). The room thermostat setpoint is .
Part A: When the room sensible cooling load is , calculate:
- The required supply air temperature () delivered by the terminal unit.
- The required primary airflow rate () and induced plenum airflow rate ().
Part B: In the occupied zone, air velocity and temperature are measured at two locations:
- Point 1: ,
- Point 2: , Calculate the Effective Draft Temperature () for each point and determine whether each point satisfies the ADPI thermal comfort criteria.
Step-by-Step Solution:
Part A: Calculate supply temperature and primary airflow:
Now, perform a sensible energy balance across the series mixing plenum ():
Part B: Evaluate Effective Draft Temperatures (theta):
Point 1 (, ):
- (Fails comfort threshold ; slight cold draft).
- (Velocity acceptable).
- Conclusion for Point 1: FAILS ADPI criteria due to draft.
Point 2 (, ):
- (Severe cold draft failure).
- (Velocity exceeds maximum comfort limit).
- Conclusion for Point 2: FAILS ADPI criteria.
7. NCEES Reference Handbook Navigation & Exam Tips
- Effective Draft Temperature: Look in the Space Air Diffusion section of the Mechanical Reference Handbook for .
- ADPI Criteria: Remember that a test point passes if and only if AND .
- Coanda Throw Rule: For diffusers with surface attachment (Coanda), catalog throw values are approximately to longer than for non-attached (free jet) discharge.
In an occupied office space maintained at 75.0°F control temperature, an air velocity of 50 FPM and an air dry-bulb temperature of 73.0°F are measured at an occupant workstation. What is the Effective Draft Temperature (theta), and does this location satisfy ASHRAE comfort criteria?
theta = -2.00°F; Passes comfort criteria
theta = -0.60°F; Passes comfort criteria
theta = -3.40°F; Fails comfort criteria due to cold draft sensation
theta = -3.40°F; Passes comfort criteria because velocity is below 70 FPM
Which of the following describes the operational behavior of a Series Fan-Powered VAV Terminal Unit (FPU) compared to a Parallel Fan-Powered VAV Unit?
A Series FPU uses electric reheat exclusively while a Parallel FPU is restricted to hydronic hot water coils
A Series FPU has a variable airflow delivered to room diffusers at all times, while a Parallel FPU delivers constant volume
A Series FPU completely eliminates the need for primary air filtration at the central air handling unit
A Series FPU runs its terminal fan continuously in occupied mode delivering constant CFM to diffusers, whereas a Parallel FPU cycles its fan on only when heat or plenum air is required
What is the primary function of the Coanda effect in ceiling-mounted air diffuser design for VAV systems?
To cause the cold supply air jet to attach to and flow along the ceiling surface, promoting room air induction and thermal mixing before the air drops into the occupied zone at low part-load flows
To increase the static pressure drop across the terminal box primary damper
To convert sensible heat gain into latent moisture removal along the plenum return
To eliminate the requirement for sound attenuators on the supply air fan discharge
In a Variable Air Volume (VAV) system equipped with DDC controls, what is the engineering mechanism and benefit of a 'Trim-and-Respond' duct static pressure reset strategy under ASHRAE 90.1?
It fixes fan speed at 100% and modulates outdoor air dampers to maintain constant plenum static pressure
It continuously monitors all VAV terminal box damper positions and dynamically reduces supply fan VFD speed until at least one critical VAV damper is 90% to 95% open, slashing fan power and acoustic noise
It cycles terminal reheat coils on and off to maintain constant duct velocity pressure at the central riser
It increases duct static pressure to 5.0 in. wg during part-load hours to prevent terminal box hunting
Sections you finish are checked off in the contents.