9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
Key Takeaways
- Chilled water storage is sensible and requires roughly 90 gallons per ton-hour at a 16 F temperature difference, while ice storage is latent at 144 Btu/lb and requires only about 10 gallons of water per ton-hour, roughly one-sixth the tank volume.
- Full storage shifts the entire on-peak cooling load to off-peak hours, while partial storage sizes the chiller for the level 24-hour average load and lets storage cover the difference during the peak.
- A chiller making ice must produce roughly 22 F to 26 F glycol instead of 44 F chilled water, which derates its capacity by about 30% to 35% and raises its kW per ton.
- Thermal storage rarely saves energy; it saves cost by moving consumption to lower-priced hours and by cutting the billed peak demand, so its economics depend entirely on the rate structure.
- Storage capacity is expressed in ton-hours: one ton-hour is 12,000 Btu, so a stratified tank storing 1,580 ton-hours holds 18.96 million Btu of usable cooling.
9.7 Thermal Energy Storage: Full vs. Partial Storage, Chilled Water & Ice Systems
Thermal energy storage (TES) decouples when cooling is produced from when cooling is used. It is listed under NCEES sub-topic 3D alongside chillers and heat pumps because the storage decision changes the chiller selection - sometimes dramatically.
State the economics up front, because exam distractors depend on it: TES almost never reduces annual energy consumption. Making ice at a 22 F suction temperature is less efficient than making 44 F chilled water. What TES buys is a cost shift - cheaper off-peak energy and, usually more valuable, a lower billed peak demand.
1. Storage Media and the Volume Math
Sensible Storage - Chilled Water
Capacity comes from the temperature swing of the stored water:
Converting to the units engineers actually use, with 8.33 lb/gal and a specific heat of 1 Btu/lb-F, the gallons required per ton-hour are:
- At a 16 F swing: 12,000 / 133.3 = 90 gallons per ton-hour
- At a 20 F swing: 12,000 / 166.6 = 72 gallons per ton-hour
The temperature swing is limited by what the coils can use. Stratified tanks rely on the density difference between roughly 40 F and 60 F water, and a thermocline of 1 to 3 ft separates the two layers. Excessive inlet velocity destroys stratification, so diffusers are sized to keep the inlet Froude number low.
Latent Storage - Ice
Ice stores the heat of fusion of water, 144 Btu/lb, which is far more than any practical sensible swing:
- Ice required per ton-hour: 12,000 / 144 = 83.3 lb
- As water volume: 83.3 / 8.33 = 10.0 gallons per ton-hour
Ice therefore needs roughly one-sixth the water inventory of a 16 F chilled water system. In practice the installed tank volume is larger than 10 gal/ton-hr - typically 2.4 to 3.3 ft3 (about 18 to 25 gallons) per ton-hour once you account for the heat exchanger coils, the unfrozen water that must remain to carry flow, and the fact that not all water is converted to ice. Even so, ice remains three to five times more compact than chilled water storage.
Ice Storage Configurations
| Type | How It Works | Notes |
|---|---|---|
| Ice-on-coil, internal melt | Glycol circulates in submerged coils; ice builds on them and melts from the inside out | Most common; discharge temperature rises as ice recedes from the coil |
| Ice-on-coil, external melt | Warm return water flows over the ice; melts from the outside in | Holds a colder, flatter discharge temperature; used for low-temperature air systems |
| Encapsulated ice | Water sealed in plastic spheres or bricks in a glycol-filled tank | Modular, simple tank |
| Ice harvester | Ice is periodically released from an evaporator plate into a water tank | High discharge rate; more moving parts |
Eutectic salt phase-change materials freeze near 47 F rather than 32 F, which lets a conventional chiller charge them without derating, at the cost of a much lower storage density (about 6 Btu/lb).
2. Operating Strategies
Cooling load (tons)
| FULL STORAGE PARTIAL STORAGE
| +---------------+ +---------------+
| | storage | | storage |
| | discharge | | discharge |
| ---+---------------+--- ---+===============+--- <- level chiller output
| chiller off on-peak chiller runs 24 hours
+------------------------------ ------------------------
on-peak window on-peak window
| Strategy | Chiller Sizing | Storage Sizing | When It Wins |
|---|---|---|---|
| Full storage (load shifting) | Sized to make the entire daily requirement during off-peak hours | Largest; holds the whole on-peak load | Steep on-peak/off-peak rate differential; short on-peak window; high demand charges |
| Partial storage (load leveling) | Sized for the level 24-hour average load - the smallest chiller of the three | Moderate | Most common; lowest combined first cost |
| Partial storage (demand limiting) | Between the two; chiller runs on-peak but throttled to a demand cap | Moderate to large | Ratchet-based demand charges |
Worked Example - Partial Storage, Load Leveling
A building has a peak cooling load of 400 tons, a total daily cooling requirement of 3,400 ton-hours, and a 10-hour on-peak window during which 3,000 ton-hours of cooling is required.
Step 1 - Level chiller size. Running continuously, the chiller only has to produce the daily average:
- 3,400 ton-hr / 24 hr = 142 tons
Step 2 - Storage required. During the on-peak window the chiller supplies 142 x 10 = 1,420 ton-hours directly, and storage must cover the rest:
- 3,000 - 1,420 = 1,580 ton-hours of usable storage
Step 3 - Compare tank volumes.
- Chilled water at 16 F swing: 1,580 x 90 = 142,000 gallons
- Ice, installed basis at roughly 21 gal/ton-hr: 1,580 x 21 = 33,000 gallons
Step 4 - Correct the chiller selection for ice-making. The 142-ton figure is a load requirement. A chiller producing 24 F glycol instead of 44 F water loses roughly 30% to 35% of its nameplate capacity, so the machine must be selected at approximately 142 / 0.68 = 209 nominal tons. Skipping this derate is the single most common error in TES problems.
Even after the derate, the plant is 209 nominal tons instead of 400 tons - and the entire on-peak electrical demand associated with 1,580 ton-hours has been removed from the utility bill.
3. What Storage Does and Does Not Change
| Metric | Effect of Adding TES |
|---|---|
| Annual kWh | Typically flat to slightly worse; ice-making penalty offsets gains from cooler nighttime condensing |
| Peak kW demand | Substantially reduced - usually the dominant economic driver |
| Energy cost | Reduced when off-peak rates are materially lower |
| Chiller size | Reduced for partial storage; possibly not reduced for full storage |
| Distribution | Ice enables 38 F to 42 F supply water, allowing larger delta-T, smaller pipe, and low-temperature air distribution with smaller ducts and fans |
| Reliability | Storage provides a short-duration cooling reserve during a chiller outage |
That low-temperature air distribution point is the underrated one. Ice systems can supply 44 F air rather than 55 F air, which nearly doubles the temperature difference the air carries. Supply airflow, duct size, and fan power all drop accordingly - and those fan savings can offset the chiller's ice-making penalty entirely.
A stratified chilled water storage tank operates between 40 F and 58 F. How many gallons of storage volume are required per ton-hour of usable cooling capacity?
A partial-storage load-leveling design serves a building with a 4,800 ton-hour daily cooling requirement, of which 3,600 ton-hours occurs during a 12-hour on-peak window. What is the level chiller load, and how much usable storage is required?
A chiller in an ice storage plant must be selected to meet a 250-ton ice-making load while producing 24 F glycol. Its manufacturer rates it at 44 F leaving water. What nominal capacity should be specified, and why?
Which statement most accurately describes the energy and cost impact of adding ice thermal storage to an existing chilled water plant on a utility rate with high on-peak demand charges?