10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units
Key Takeaways
- Air Handling Units (AHUs) condition and circulate mixed air using modular component trains; Draw-Through configurations provide uniform air velocity across cooling coils to prevent moisture carryover, whereas Blow-Through configurations place fan heat upstream of cooling coils.
- Supply and return fan motor heat adds sensible temperature rise to the airstream via $\Delta T_{\text{fan}} = 0.3707 \times \frac{\Delta P_{\text{total}}}{\eta_{\text{total}}}$, which must be added to cooling loads or credited to heating loads.
- Dedicated Outdoor Air Systems (DOAS) decouple ventilation from space sensible cooling, conditioning 100% outdoor air to handle the entire building latent ventilation and internal space moisture loads while delivering dry neutral or cold air.
- Total energy recovery wheels in DOAS exchange both sensible and latent energy between exhaust and outdoor airstreams, reducing peak ventilation cooling loads by 60% to 75% and complying with ASHRAE 90.1 energy recovery mandates.
- Four-pipe fan-coil units (FCUs) provide simultaneous heating and cooling flexibility with separate supply and return hydronic coils, eliminating seasonal changeover lag and thermal mixing losses characteristic of two-pipe systems.
10.1 Air Handling Units (AHUs), Dedicated Outdoor Air Systems (DOAS) & Fan-Coil Units
Air-side distribution systems are the primary thermal and ventilation delivery mechanisms in commercial, institutional, and industrial HVAC applications. The primary function of an Air Handling Unit (AHU) or Dedicated Outdoor Air System (DOAS) is to process, filter, condition (heat, cool, humidify, dehumidify), and circulate moist air throughout building zones to satisfy indoor environmental quality, ventilation, and thermal comfort criteria. On the PE Mechanical: HVAC and Refrigeration exam, air-handling equipment questions test psychrometric coil processes, fan heat temperature rise, freeze protection, sensible-latent decoupling, energy recovery effectiveness, and hydronic terminal selection.
1. Central Air Handling Unit (AHU) Architecture & Component Sequence
A custom or packaged commercial AHU consists of an insulated sheet metal casing enclosing a sequential train of aerodynamic, thermal, and filtration components. The physical arrangement of these components determines thermal performance, acoustic generation, filtration efficiency, and maintenance longevity.
+---------------------------------------------------------------------------------------------------------+
| STANDARD DRAW-THROUGH AHU COMPONENT TRAIN |
+---------------------------------------------------------------------------------------------------------+
| |
| Outdoor Air (OA) ---\ |
| [Mixing Box / Dampers] ==> [Prefilter (MERV 8)] ==> [Final Filter (MERV 13-14)] |
| Return Air (RA) ----/ |
| |
| ==> [Preheat / Glycol Coil] ==> [Cooling / Dehum Coil] ==> [Supply Fan] ==> [Sound Attenuator] |
| (with Drain Pan) (Draw-Thru) ===> Supply Air (SA) |
+---------------------------------------------------------------------------------------------------------+
Standard Component Sequence (Airflow Direction)
- Air Mixing Plenum (Economizer Section): Interlinked motorized outdoor air (OA), return air (RA), and relief/exhaust air (EA) dampers modulate to control the mixed air ratio and execute airside economizer free cooling.
- Filtration Bank:
- Pre-filters: Typically 2-inch or 4-inch pleated filters rated MERV 8 (ASHRAE 52.2) to capture large particulate matter and protect downstream coils.
- Final Filters: High-efficiency bag, cartridge, or mini-pleat filters rated MERV 13 to 14 (standard LEED/ASHRAE 55 baseline) or MERV 16/HEPA (healthcare/cleanroom applications).
- Preheat Coil: Located upstream of the chilled water cooling coil in cold climates to temper incoming mixed air above $40^\circ\text{F}$ ($4.4^\circ\text{C}$), preventing coil freeze-up. Utilizes hot water with a dedicated circulating pump, ethylene/propylene glycol, steam distributing tubes (non-freeze type), or face-and-bypass dampers.
- Cooling and Dehumidification Coil: Finned-tube heat exchanger circulating chilled water ($42^\circ\text{F}$ to $45^\circ\text{F}$) or direct expansion (DX) evaporating refrigerant. Operates with face velocities restricted to $400$ to $500\text{ FPM}$ ($2.0$ to $2.5\text{ m/s}$). Face velocities exceeding $500-550\text{ FPM}$ cause condensed moisture droplet blow-off from fins into the downstream casing.
- Sloped Condensate Drain Pan: Stainless steel dual-sloped drain pan conforming to ASHRAE Standard 62.1 to prevent standing water, biological slime, and mold amplification. P-traps must be engineered with sufficient water seal depth to overcome negative casing static pressure.
- Reheat / Heating Coil: Hot water, electric resistance, or indirect gas-fired heat exchanger positioned downstream of the cooling coil for zone temperature control or humidity trim.
- Supply Air Fan: Centrifugal airfoil, plenum/plug fan, or fan array (FANWALL) driven by electronically commutated (EC) motors or premium-efficiency motors with variable frequency drives (VFDs).
- Sound Attenuator (Silencer): Factory-engineered dissipative silencer baffles to attenuate blade pass frequencies and broadband fan noise before discharge into the duct system.
2. Draw-Through vs. Blow-Through Configurations
The relative placement of the supply fan with respect to the cooling coil creates two distinct thermodynamic and aerodynamic architectures:
DRAW-THROUGH CONFIGURATION: BLOW-THROUGH CONFIGURATION:
Coil Under Negative Static Pressure Coil Under Positive Static Pressure
Fan Heat Added AFTER Cooling Coil Fan Heat Added BEFORE Cooling Coil
Negative (-) Positive (+) Positive (+) Positive (+)
[Coil] ===> [Fan] ===> Supply Duct [Fan] ===> [Coil] ===> Supply Duct
| |
Fan Heat Fan Heat
Added Here Added Here
Comparative Engineering Matrix
| Engineering Parameter | Draw-Through Configuration | Blow-Through Configuration |
|---|---|---|
| Coil Velocity Profile | Highly uniform velocity distribution across the entire coil face due to fan suction plenum drawing air evenly. | Non-uniform velocity profile; high-velocity air jet from fan discharge strikes center of coil unless diffuser baffles are installed. |
| Moisture Carryover Risk | Low risk; uniform face velocity prevents localized high-velocity hot spots that strip water droplets. | Higher risk of condensate blow-off directly opposite the fan discharge cone. |
| Casing Static Pressure | Casing upstream of fan (filters, coils, mixing box) operates under negative static pressure ($P_s < P_{\text{atm}}$). | Casing downstream of fan (coils, discharge plenum) operates under positive static pressure ($P_s > P_{\text{atm}}$). |
| Drain Pan Trap Design | Requires a deep P-trap with negative trap seal ($H = P_{\text{static, suction}} + 1\text{ to }2\text{ in.}$) to prevent air being sucked into the pan, which halts drainage and overflows the pan. | Requires standard positive pressure trap; air blows out through drain line if untrapped. |
| Fan Heat Addition | Fan work heat is added after the cooling coil; increases supply air temperature delivered to ductwork ($T_{\text{SA}} = T_{\text{leaving coil}} + \Delta T_{\text{fan}}$). | Fan work heat is added before the cooling coil; cooling coil must absorb both space cooling load and fan heat load ($T_{\text{entering coil}} = T_{\text{mix}} + \Delta T_{\text{fan}}$). |
| Primary Application | Commercial VAV systems, DOAS units, single-zone constant volume AHUs (dominant $>90%$ of designs). | Multi-zone dual-duct AHUs with separate hot/cold decks, or applications requiring ultra-low discharge temperatures. |
3. Supply Fan Heat Temperature Rise Equations
All mechanical energy losses and thermodynamic work imparted by the fan impeller into the airstream convert into thermal internal energy (heat). For a fan with total pressure rise $\Delta P_t$ (in inches of water gauge, $\text{in. wg}$) and total efficiency $\eta_t$:
Substituting $\dot{Q} = 1.08 \times \text{CFM} \times \Delta T_{\text{fan}}$ (for standard air density $\rho = 0.075\text{ lbm/ft}^3$ and specific heat $c_p = 0.240\text{ Btu/(lbm}\cdot^\circ\text{F)}$):
Where:
- $\Delta P_t$ = Total pressure rise across fan ($ ext{in. wg}$)
- $\eta_t$ = Fan total efficiency (decimal, typically $0.60$ to $0.80$)
- If the motor is located inside the airstream (common in packaged units and plug fans), motor electrical inefficiency heat ($1 - \eta_m$) is also transferred to the air:
Exam Rule of Thumb: For a typical commercial AHU with $\Delta P_t = 3.5\text{ in. wg}$ and total fan-motor efficiency $\eta = 0.65$, fan heat produces a temperature rise of $\Delta T = 0.3707 \times \frac{3.5}{0.65} \approx 2.0^\circ\text{F}$. If the leaving cooling coil temperature is $53.0^\circ\text{F}$, the air leaves the draw-through AHU at $55.0^\circ\text{F}$.
4. Dedicated Outdoor Air Systems (DOAS)
A Dedicated Outdoor Air System (DOAS) is an HVAC architecture that completely decouples building ventilation and latent humidity control from space sensible cooling and heating.
+-----------------------------------------------------------------------------------------+
| DECOUPLED DOAS + PARALLEL TERMINAL ARCHITECTURE |
+-----------------------------------------------------------------------------------------+
| |
| 100% Outdoor Air ===> [ DOAS AHU ] ======> Dry Neutral Air (70°F DB, 48°F DP) |
| (Ventilation & (Cool to 50°F DP, - Handles 100% Latent Load |
| Latent Control) Reheat to 70°F) - Handles 100% Ventilation Air |
| | |
| v |
| +-------------------+ |
| | Occupied Zone | |
| +-------------------+ |
| ^ |
| | |
| Recirculating Zone Air =================> [ Parallel Sensible ] |
| [ Terminal Device ] |
| • Fan-Coil Units (FCUs) |
| • Active Chilled Beams |
| • Radiant Cooling Panels |
| • VRF Indoor Units |
+-----------------------------------------------------------------------------------------+
Core Engineering Principles of DOAS
- Latent Load Decoupling: Traditional variable air volume (VAV) systems dehumidify by overcooling mixed air down to $55^\circ\text{F}$ at the central AHU. In spaces with high latent loads (auditoriums, classrooms, gyms), central VAV requires wasteful terminal reheat. DOAS processes 100% outdoor air down to a low dew point ($45^\circ\text{F}$ to $50^\circ\text{F}$), removing all outdoor air moisture plus internal occupant latent generation.
- Delivery Strategies:
- Cold Air Delivery ($55^\circ\text{F}$ DB / $48^\circ\text{F}$ DP): DOAS air provides sensible cooling capacity directly to the zone, reducing the sizing of parallel sensible cooling terminals.
- Neutral Air Delivery ($70^\circ\text{F}$ DB / $48^\circ\text{F}$ DP): DOAS air enters at room temperature, handling zero space sensible load. Parallel terminal systems handle 100% of space sensible loads.
- ASHRAE Standard 62.1 Multiple Spaces Compliance: In a multi-zone recirculating VAV system, system ventilation efficiency ($E_v$) is governed by the critical zone requiring the highest outdoor air fraction, forcing significant over-ventilation of uncritical zones. Because DOAS delivers dedicated, measured outdoor air directly to each zone, $E_v = 1.0$, reducing total building outdoor air intake by $20%$ to $40%$.
Total Energy Recovery in DOAS (Enthalpy Wheels)
Modern DOAS units incorporate an air-to-air energy recovery device between the exhaust/relief airstream and incoming outdoor airstream:
- Total Enthalpy Wheel: A rotating honeycomb matrix impregnated with a desiccant (silica gel or molecular sieve) rotating at $10$ to $30\text{ RPM}$. It transfers both sensible heat (via matrix thermal mass) and latent moisture (via desiccant adsorption/desorption).
- Effectiveness Equation (Sensible, Latent, or Total):
Where $X$ represents dry-bulb temperature ($T$), humidity ratio ($W$), or enthalpy ($h$), and $\dot{m}{\min} = \min(\dot{m}{oa}, \dot{m}_{ea})$.
5. Fan-Coil Units (FCUs) & Parallel Hydronic Terminals
Fan-Coil Units (FCUs) are decentralized zone conditioning units consisting of a small centrifugal fan, filter, and one or two water coils.
2-PIPE FCU (Seasonal Changeover): 4-PIPE FCU (Simultaneous Heating/Cooling):
+----------------------+ +----------------------+
| Single Coil for | | Heating | Cooling |
| Heating OR Cooling | | Coil | Coil |
+----------------------+ +----------------------+
| | | | | |
Supply Return HW-S HW-R CW-S CW-R
(Seasonally switched at plant) (Independent simultaneous loops)
2-Pipe vs. 4-Pipe System Comparison
| Feature | 2-Pipe System | 4-Pipe System |
|---|---|---|
| Piping Distribution | 1 supply pipe, 1 return pipe; single shared coil. | 2 supply pipes, 2 return pipes; dedicated heating and cooling coils. |
| Operational Flexibility | The entire building loop must be in either 100% cooling mode or 100% heating mode. | Any zone can heat while an adjacent zone cools simultaneously. |
| Seasonal Changeover Lag | High; changing modes requires circulating loop water through a bypass until water temperature normalizes before switching chiller/boiler. | Zero changeover lag; instant response to variable solar/internal loads. |
| Installed Capital Cost | Lower initial cost (50% less piping, 1 valve per unit). | Higher initial cost (4 pipes, 2 control valves per unit). |
| Energy Waste & Complaints | High occupant dissatisfaction during shoulder seasons (spring/fall); zones with perimeter solar heat gain overheat while shaded zones freeze. | Outstanding thermal comfort; minimal energy waste. |
Chilled Beams (Active vs. Passive)
- Passive Chilled Beams: Natural convection coils mounted at ceiling level. Room air warms, rises, passes through the chilled coil, cools, and sinks back into the occupied zone. Zero fan power, quiet. Handles sensible cooling only.
- Active Chilled Beams: Pressurized primary air from a DOAS unit discharges through aerodynamic nozzles at high velocity, inducing room air through an integrated chilled water coil at an induction ratio of $3:1$ to $5:1$.
- Condensation Prevention Rule: Chilled water supply temperature entering chilled beams must be maintained $2^\circ\text{F}$ to $3^\circ\text{F}$ above the zone dew point temperature (typically $T_{\text{CHWS}} \ge 58^\circ\text{F}$ to $60^\circ\text{F}$). If the zone dew point rises near $T_{\text{CHWS}}$, condensation sensors automatically close the hydronic control valve.
6. Worked Example: DOAS Enthalpy Wheel & Coil Load Analysis
Problem: A commercial DOAS unit supplies $8,000\text{ CFM}$ of outdoor air to an office building at sea level ($P = 14.696\text{ psia}$, $\rho = 0.075\text{ lbm/ft}^3$). Summer outdoor design conditions are $95.0^\circ\text{F}$ Dry-Bulb (DB) and $78.0^\circ\text{F}$ Wet-Bulb (WB) ($h_{oa} = 41.38\text{ Btu/lbm}$, $W_{oa} = 0.0168\text{ lbm}w/\text{lbm}{da}$). Building exhaust air enters the energy recovery wheel at $75.0^\circ\text{F}$ DB and $62.0^\circ\text{F}$ WB ($h_{ea} = 27.80\text{ Btu/lbm}$, $W_{ea} = 0.0092\text{ lbm}w/\text{lbm}{da}$) with an exhaust flow rate of $8,000\text{ CFM}$.
The DOAS unit features a total enthalpy wheel with a total effectiveness of $\varepsilon_t = 0.72$ and sensible effectiveness of $\varepsilon_s = 0.75$. Downstream of the wheel, a chilled water cooling coil dehumidifies the air to a leaving coil condition of $52.0^\circ\text{F}$ DB and $51.0^\circ\text{F}$ WB ($h_{cc} = 20.80\text{ Btu/lbm}$, $W_{cc} = 0.0078\text{ lbm}w/\text{lbm}{da}$). The draw-through supply fan has a total pressure rise of $\Delta P_t = 2.80\text{ in. wg}$ and total efficiency of $\eta_t = 0.68$.
Find:
- The condition of the air leaving the enthalpy wheel (enthalpy $h$, dry-bulb temperature $T$, and humidity ratio $W$).
- The cooling capacity reduction provided by the energy recovery wheel in Tons of Refrigeration.
- The net cooling coil load in $\text{Btu/hr}$ and Tons.
- The final supply air dry-bulb temperature ($T_{\text{SA}}$) delivered to the ductwork after fan heat addition.
Step-by-Step Solution:
Step 1: Calculate air properties leaving the enthalpy wheel.
Step 2: Calculate thermal energy recovered by the wheel.
Step 3: Calculate cooling coil thermal load.
(Note: Without the energy recovery wheel, the cooling coil would require $4.5 \times 8,000 \times (41.38 - 20.80) = 740,880\text{ Btu/hr} = 61.74\text{ Tons}$. The wheel reduces cooling coil size by $47.5%$).
Step 4: Calculate fan heat temperature rise and final supply air temperature.
7. NCEES Reference Handbook Navigation & Exam Tips
- Psychrometric Energy Equations: Look in the HVAC section for $\dot{Q}_s = 1.08 \cdot \text{CFM} \cdot \Delta T$, $\dot{Q}_l = 4840 \cdot \text{CFM} \cdot \Delta W$, and $\dot{Q}_t = 4.5 \cdot \text{CFM} \cdot \Delta h$.
- Fan Power & Heat Relations: Verify whether fan motor is inside or outside the airstream. If the motor is inside, divide total pressure by $\eta_{\text{fan}} \times \eta_{\text{motor}}$.
- Enthalpy Wheel Conservation: When outdoor airflow ($\text{CFM}{oa}$) equals exhaust airflow ($\text{CFM}{ea}$), the effectiveness formula simplifies directly to linear interpolation of enthalpy, temperature, and humidity ratio.
A draw-through air handling unit operates with a total fan pressure rise of 3.60 in. wg and a fan total efficiency of 66.0%. If the air leaves the chilled water cooling coil saturated at 52.5°F, what is the temperature of the supply air discharged into the supply ductwork (assuming standard air and the fan motor is mounted outside the airstream)?
A dedicated outdoor air system (DOAS) conditions 12,000 CFM of outdoor air from 94.0°F dry-bulb and 77.0°F wet-bulb (enthalpy h = 40.50 Btu/lbm) to a leaving coil condition of 50.0°F dry-bulb and 49.0°F wet-bulb (enthalpy h = 19.80 Btu/lbm). A total enthalpy recovery wheel with an effectiveness of 70.0% is installed, utilizing 12,000 CFM of building exhaust air at 75.0°F dry-bulb and 62.0°F wet-bulb (enthalpy h = 27.80 Btu/lbm). What is the net cooling coil load required downstream of the wheel?
Which of the following describes the fundamental operational difference between 2-pipe and 4-pipe fan-coil unit (FCU) distribution systems?
Why is an active chilled beam system strictly paired with a Dedicated Outdoor Air System (DOAS) supplying dehumidified ventilation air?