9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings

Key Takeaways

  • Water chiller capacity is governed by the hydronic heat balance $\dot{q} = 500 \times \text{GPM}_{\text{CHW}} \times (T_{\text{CHWR}} - T_{\text{CHWS}})$; standard AHRI rating conditions specify $54^\circ\text{F}$ entering and $44^\circ\text{F}$ leaving chilled water ($2.4\text{ GPM/ton}$ for a $10^\circ\text{F}\text{ }\Delta T$).
  • Chiller efficiency metrics are interconverted via $\text{kW/ton} = \frac{3.51685}{\text{COP}} = \frac{12}{\text{EER}}$; total heat of rejection to the condenser is $\text{THR} = \text{Tons} \times 12,000 + \text{kW}_{\text{input}} \times 3,412.14$.
  • AHRI Standard 550/590 Integrated Part-Load Value (IPLV.IP) weights four distinct operating points: $1\%$ at $100\%$ load ($85^\circ\text{F}$ ECWT), $42\%$ at $75\%$ load ($75^\circ\text{F}$ ECWT), $45\%$ at $50\%$ load ($65^\circ\text{F}$ ECWT), and $12\%$ at $25\%$ load ($65^\circ\text{F}$ ECWT).
  • For $\text{kW/ton}$, IPLV.IP uses a weighted harmonic mean: $\text{IPLV (kW/ton)} = \frac{1}{\frac{0.01}{A} + \frac{0.42}{B} + \frac{0.45}{C} + \frac{0.12}{D}}$; for EER or COP, IPLV.IP uses an arithmetic mean: $\text{IPLV} = 0.01 A + 0.42 B + 0.45 C + 0.12 D$.
  • ASHRAE Standard 90.1 defines two compliance paths: Path A requires higher full-load efficiency (ideal for baseload chillers), while Path B permits lower full-load efficiency in exchange for aggressive part-load IPLV performance (ideal for VFD chillers with condenser water relief).
Last updated: August 2026

9.4 Water Chillers: Centrifugal, Screw & Scroll with ASHRAE 90.1 Path A/B IPLV Ratings

Water chillers are the cornerstone of commercial, institutional, and district central chilled water plants. A water chiller integrates the four primary refrigeration cycle components—compressor, condenser, expansion device, and evaporator—into a packaged machine engineered to produce cold water (typically $40^\circ\text{F}$ to $45^\circ\text{F}$) for building air conditioning or process cooling. On the PE Mechanical: HVAC and Refrigeration exam, chiller questions evaluate hydronic heat balances, energy efficiency unit conversions, part-load performance under AHRI Standard 550/590, and energy code compliance under ASHRAE Standard 90.1.


1. Chiller Capacity & Primary Hydronic Energy Balances

Chiller cooling capacity represents the rate of heat removed from the circulating chilled water loop:

Q˙evap (Btu/hr)=m˙CHWcp,water(TCHWRTCHWS)=500×GPMCHW×ΔTCHW\dot{Q}_{\text{evap}}\text{ (Btu/hr)} = \dot{m}_{\text{CHW}} \cdot c_{p,\text{water}} \cdot (T_{\text{CHWR}} - T_{\text{CHWS}}) = 500 \times \text{GPM}_{\text{CHW}} \times \Delta T_{\text{CHW}}

Cooling Capacity (Tons)=500×GPMCHW×(TCHWRTCHWS)12,000=GPMCHW×ΔTCHW24\text{Cooling Capacity (Tons)} = \frac{500 \times \text{GPM}_{\text{CHW}} \times (T_{\text{CHWR}} - T_{\text{CHWS}})}{12,000} = \frac{\text{GPM}_{\text{CHW}} \times \Delta T_{\text{CHW}}}{24}

+-----------------------------------------------------------------------------------------+
| STANDARD AHRI 550/590 WATER-COOLED CHILLER RATING BASELINE                              |
+-----------------------------------------------------------------------------------------+
| Evaporator Entering Water Temp (CHWR): 54.0°F (12.2°C)                                  |
| Evaporator Leaving Water Temp (CHWS):  44.0°F (6.67°C)   --> Delta_T = 10.0°F           |
| Chilled Water Flow Rate per Ton:       2.40 GPM/ton                                     |
| Condenser Entering Water Temp (ECWT):  85.0°F (29.4°C)                                  |
| Condenser Leaving Water Temp (LCWT):   95.0°F (35.0°C)   --> Delta_T = 10.0°F           |
| Condenser Water Flow Rate per Ton:     3.00 GPM/ton                                     |
| Evaporator Waterside Fouling Factor:   0.00010 hr·ft²·°F/Btu                            |
| Condenser Waterside Fouling Factor:    0.00025 hr·ft²·°F/Btu                            |
+-----------------------------------------------------------------------------------------+

Condenser Heat Rejection Balance

THR (Btu/hr)=Q˙evap+W˙comp=(Tons×12,000)+(kWinput×3,412.14)\text{THR (Btu/hr)} = \dot{Q}_{\text{evap}} + \dot{W}_{\text{comp}} = (\text{Tons} \times 12,000) + (\text{kW}_{\text{input}} \times 3,412.14)

THR (Btu/hr)=500×GPMCW×(TLCWTTECWT)\text{THR (Btu/hr)} = 500 \times \text{GPM}_{\text{CW}} \times (T_{\text{LCWT}} - T_{\text{ECWT}})

GPMCW=(Tons×12,000)+(kW×3,412.14)500×(TLCWTTECWT)\text{GPM}_{\text{CW}} = \frac{(\text{Tons} \times 12,000) + (\text{kW} \times 3,412.14)}{500 \times (T_{\text{LCWT}} - T_{\text{ECWT}})}


2. Chiller Efficiency Metrics & Interconversions

Chiller efficiency is expressed in multiple imperial and metric engineering metrics:

+-----------------------------------------------------------------------------------------+
| CHILLER EFFICIENCY METRIC CONVERSION FORMULAS                                           |
+-----------------------------------------------------------------------------------------+
|                                 3.51685           12.000                                |
|             kW/ton       =   ------------   =   ----------                              |
|                                  COP               EER                                  |
|                                                                                         |
|                                 3.51685           EER                                   |
|              COP         =   ------------   =   ----------                              |
|                                 kW/ton            3.41214                               |
|                                                                                         |
|                                 12.000                                                  |
|              EER         =   ------------   =   3.41214 * COP                           |
|                                 kW/ton                                                  |
+-----------------------------------------------------------------------------------------+

Practical Benchmarks by Compressor Architecture

Compressor TypeTypical Capacity RangeFull-Load Efficiency (kW/ton)Full-Load COPPart-Load IPLV (kW/ton)
Air-Cooled Scroll20 to 180 Tons$1.10 - 1.30\text{ kW/ton}$$2.70 - 3.20$$0.75 - 0.90\text{ kW/ton}$
Air-Cooled Screw100 to 500 Tons$1.00 - 1.20\text{ kW/ton}$$2.93 - 3.52$$0.65 - 0.80\text{ kW/ton}$
Water-Cooled Scroll30 to 200 Tons$0.70 - 0.85\text{ kW/ton}$$4.14 - 5.02$$0.50 - 0.65\text{ kW/ton}$
Water-Cooled Screw100 to 600 Tons$0.58 - 0.70\text{ kW/ton}$$5.02 - 6.06$$0.40 - 0.55\text{ kW/ton}$
Water-Cooled Centrifugal (Fixed Speed)200 to 3,000+ Tons$0.52 - 0.62\text{ kW/ton}$$5.67 - 6.76$$0.45 - 0.55\text{ kW/ton}$
Water-Cooled Centrifugal (VFD Mag-Bearing)200 to 1,500 Tons$0.50 - 0.58\text{ kW/ton}$$6.06 - 7.03$$0.28 - 0.38\text{ kW/ton}$

3. AHRI Standard 550/590 Integrated Part-Load Value (IPLV)

Commercial chillers operate at 100% design capacity for less than 1% to 2% of their total annual operating hours. The vast majority of runtime occurs between 40% and 75% load when outdoor wet-bulb temperatures are lower than design conditions. To reflect real-world annual energy consumption, AHRI Standard 550/590 established the Integrated Part-Load Value (IPLV.IP) rating.

AHRI Standard Part-Load Test Points

+-----------------------------------------------------------------------------------------+
| AHRI 550/590 IPLV.IP TEST CONDITIONS & TIMING WEIGHTS                                   |
+-------+-----------+----------------------+--------------------+-------------------------+
| Point | Capacity  | Water-Cooled ECWT    | Air-Cooled Ambient | Time Weighting Fraction |
+-------+-----------+----------------------+--------------------+-------------------------+
| **A** | **100%**  | **85.0°F (29.4°C)**  | **95.0°F (35.0°C)**| **0.01 (1%)**           |
| **B** | **75%**   | **75.0°F (23.9°C)**  | **80.0°F (26.7°C)**| **0.42 (42%)**          |
| **C** | **50%**   | **65.0°F (18.3°C)**  | **65.0°F (18.3°C)**| **0.45 (45%)**          |
| **D** | **25%**   | **65.0°F (18.3°C)**  | **55.0°F (12.8°C)**| **0.12 (12%)**          |
+-------+-----------+----------------------+--------------------+-------------------------+

Condenser Water Relief: Notice that as chiller cooling load decreases from 100% down to 50%, entering condenser water temperature (ECWT) is allowed to drop from $85^\circ\text{F}$ down to $65^\circ\text{F}$ ($1.0^\circ\text{F}$ reduction in ECWT for every $2.5%$ drop in load). Below 50% load, ECWT is capped at a minimum of $65.0^\circ\text{F}$ to prevent oil separation and refrigerant migration issues.

Mathematical Formulation of IPLV

1. When Efficiency is Expressed in EER or COP (Higher is Better):

IPLV.IP=0.01A+0.42B+0.45C+0.12D\text{IPLV.IP} = 0.01 A + 0.42 B + 0.45 C + 0.12 D Where $A, B, C, D$ are the measured EER or COP at $100%, 75%, 50%, 25%$ load.

2. When Efficiency is Expressed in kW/ton (Lower is Better):

Because $\text{kW/ton} = 12 / \text{EER}$, the weighted averaging must be performed on the reciprocal (weighted harmonic mean):

IPLV.IP (kW/ton)=10.01A+0.42B+0.45C+0.12D\text{IPLV.IP (kW/ton)} = \frac{1}{\frac{0.01}{A} + \frac{0.42}{B} + \frac{0.45}{C} + \frac{0.12}{D}}

Where $A, B, C, D$ are the measured $\text{kW/ton}$ values at $100%, 75%, 50%, 25%$ load.

Exam Calculation Trap: Never calculate IPLV in $\text{kW/ton}$ using the direct linear formula $0.01 A + 0.42 B + 0.45 C + 0.12 D$. Linear weighting on $\text{kW/ton}$ produces mathematical errors of $8%$ to $15%$. You must use the harmonic reciprocal equation above!

Non-Standard Part-Load Value (NPLV.IP)

When a chiller is selected to operate at design conditions differing from AHRI standard conditions (e.g., producing $42.0^\circ\text{F}$ leaving chilled water instead of $44.0^\circ\text{F}$, or with $82.0^\circ\text{F}$ entering condenser water), the identical formula is applied to calculate NPLV.IP using the non-standard entering water temperature schedule:

ECWT=ECWTdesign(ECWTdesign65F10050)×(100%%Load)\text{ECWT} = \text{ECWT}_{\text{design}} - \left(\frac{\text{ECWT}_{\text{design}} - 65^\circ\text{F}}{100 - 50}\right) \times (100\% - \%\text{Load})


4. ASHRAE Standard 90.1 Chiller Compliance: Path A vs. Path B

ASHRAE Standard 90.1 (Energy Standard for Buildings Except Low-Rise Residential) mandates minimum full-load and part-load efficiency thresholds for water chillers. To accommodate different plant operating profiles, 90.1 provides two alternative compliance paths:

+-----------------------------------------------------------------------------------------+
| ASHRAE STANDARD 90.1 COMPLIANCE PHILOSOPHY: PATH A vs. PATH B                           |
+-----------------------------------+-----------------------------------------------------+
| PATH A (Full-Load Optimized)      | PATH B (Part-Load / VFD Optimized)                  |
+-----------------------------------+-----------------------------------------------------+
| • Strict Full-Load Efficiency     | • Relaxed Full-Load Efficiency                      |
| • Modest Part-Load (IPLV) Target  | • Highly Aggressive Part-Load (IPLV) Target         |
| • Best for: Constant-speed base-  | • Best for: Variable-speed (VFD) chillers operating |
|   load chillers in data centers   |   in variable cooling load applications with       |
|   or industrial process cooling.  |   condenser water temperature relief.               |
+-----------------------------------+-----------------------------------------------------+

ASHRAE Standard 90.1 Minimum Efficiency Table (Representative Values)

Equipment Type & Size RangePath A: Min Full-LoadPath A: Min IPLVPath B: Min Full-LoadPath B: Min IPLV
Air-Cooled Chillers ($< 150\text{ Tons}$)$\ge 10.10\text{ EER}$$\ge 13.70\text{ EER}$$\ge 9.70\text{ EER}$$\ge 15.80\text{ EER}$
Air-Cooled Chillers ($\ge 150\text{ Tons}$)$\ge 10.10\text{ EER}$$\ge 14.00\text{ EER}$$\ge 9.70\text{ EER}$$\ge 16.10\text{ EER}$
Water-Cooled Positive Disp (Screw/Scroll) ($150-300\text{ Tons}$)$\le 0.660\text{ kW/ton}$$\le 0.540\text{ kW/ton}$$\le 0.740\text{ kW/ton}$$\le 0.400\text{ kW/ton}$
Water-Cooled Centrifugal ($300-600\text{ Tons}$)$\le 0.560\text{ kW/ton}$$\le 0.500\text{ kW/ton}$$\le 0.590\text{ kW/ton}$$\le 0.360\text{ kW/ton}$
Water-Cooled Centrifugal ($> 600\text{ Tons}$)$\le 0.540\text{ kW/ton}$$\le 0.480\text{ kW/ton}$$\le 0.560\text{ kW/ton}$$\le 0.330\text{ kW/ton}$

Key Code Rule: A chiller must comply with BOTH the full-load and part-load IPLV requirements of either Path A or Path B. Mixing Path A full-load with Path B IPLV is strictly prohibited.


5. Chiller Lift Reduction & VFD Energy Savings

The fundamental thermodynamic driver of part-load chiller efficiency is compressor lift reduction:

Lift=Pcondenser, satPevaporator, satTcondenser, satTevaporator, sat\text{Lift} = P_{\text{condenser, sat}} - P_{\text{evaporator, sat}} \propto T_{\text{condenser, sat}} - T_{\text{evaporator, sat}}

When ambient wet-bulb temperature drops, the cooling tower produces colder condenser water ($85^\circ\text{F} \to 75^\circ\text{F} \to 65^\circ\text{F}$). In a constant-speed centrifugal chiller, lowering the ECWT saves energy, but the compressor must throttle using inlet guide vanes, creating aerodynamic drag. In a Variable Frequency Drive (VFD) chiller, reducing compressor speed directly matches the reduced pressure lift requirement according to the affinity laws ($H \propto N^2$, $\text{Power} \propto N^3$). At 50% load and $65^\circ\text{F}$ ECWT, a VFD centrifugal chiller can operate at $0.25$ to $0.32\text{ kW/ton}$ (a COP exceeding $11.0$!).


6. Worked Example: Comprehensive Chiller Analysis & IPLV Calculation

Problem: A 600-ton water-cooled centrifugal chiller is evaluated for a commercial central plant. The measured performance data at AHRI Standard 550/590 test points are:

  • Point A (100% Load, 600 Tons, 85°F ECWT): Power = $330.0\text{ kW}$
  • Point B (75% Load, 450 Tons, 75°F ECWT): Power = $189.0\text{ kW}$
  • Point C (50% Load, 300 Tons, 65°F ECWT): Power = $96.0\text{ kW}$
  • Point D (25% Load, 150 Tons, 65°F ECWT): Power = $54.0\text{ kW}$

Find:

  1. The specific power consumption ($\text{kW/ton}$) and COP at each test point ($A, B, C, D$).
  2. The Integrated Part-Load Value in $\text{kW/ton}$ ($\text{IPLV.IP}_{\text{kW/ton}}$).
  3. The Integrated Part-Load Value in COP ($\text{IPLV.IP}_{\text{COP}}$).
  4. Determine whether the chiller meets ASHRAE Standard 90.1 Path B requirements for a 600-ton centrifugal chiller (Full-Load $\le 0.590\text{ kW/ton}$, IPLV $\le 0.360\text{ kW/ton}$).

Step-by-Step Solution:

Step 1: Compute specific power (kW/ton) and COP at each operating point.

  • Point A (100%): kW/tonA=330.0 kW600 tons=0.5500 kW/ton\text{kW/ton}_A = \frac{330.0\text{ kW}}{600\text{ tons}} = 0.5500\text{ kW/ton} COPA=3.516850.5500=6.394\text{COP}_A = \frac{3.51685}{0.5500} = 6.394

  • Point B (75%): kW/tonB=189.0 kW450 tons=0.4200 kW/ton\text{kW/ton}_B = \frac{189.0\text{ kW}}{450\text{ tons}} = 0.4200\text{ kW/ton} COPB=3.516850.4200=8.373\text{COP}_B = \frac{3.51685}{0.4200} = 8.373

  • Point C (50%): kW/tonC=96.0 kW300 tons=0.3200 kW/ton\text{kW/ton}_C = \frac{96.0\text{ kW}}{300\text{ tons}} = 0.3200\text{ kW/ton} COPC=3.516850.3200=10.990\text{COP}_C = \frac{3.51685}{0.3200} = 10.990

  • Point D (25%): kW/tonD=54.0 kW150 tons=0.3600 kW/ton\text{kW/ton}_D = \frac{54.0\text{ kW}}{150\text{ tons}} = 0.3600\text{ kW/ton} COPD=3.516850.3600=9.769\text{COP}_D = \frac{3.51685}{0.3600} = 9.769

Step 2: Calculate IPLV.IP in kW/ton using the harmonic weighting formula. Denominator=0.01A+0.42B+0.45C+0.12D\text{Denominator} = \frac{0.01}{A} + \frac{0.42}{B} + \frac{0.45}{C} + \frac{0.12}{D} Denominator=0.010.5500+0.420.4200+0.450.3200+0.120.3600\text{Denominator} = \frac{0.01}{0.5500} + \frac{0.42}{0.4200} + \frac{0.45}{0.3200} + \frac{0.12}{0.3600} Denominator=0.018182+1.000000+1.406250+0.333333=2.757765\text{Denominator} = 0.018182 + 1.000000 + 1.406250 + 0.333333 = 2.757765

IPLV.IP (kW/ton)=12.757765=0.3626 kW/ton\text{IPLV.IP (kW/ton)} = \frac{1}{2.757765} = 0.3626\text{ kW/ton}

(Note: If calculated incorrectly using linear weighting: $0.01(0.55) + 0.42(0.42) + 0.45(0.32) + 0.12(0.36) = 0.0055 + 0.1764 + 0.1440 + 0.0432 = 0.3691\text{ kW/ton}$, which is mathematically invalid).

Step 3: Calculate IPLV.IP in COP using linear weighting. IPLV.IPCOP=0.01(COPA)+0.42(COPB)+0.45(COPC)+0.12(COPD)\text{IPLV.IP}_{\text{COP}} = 0.01(\text{COP}_A) + 0.42(\text{COP}_B) + 0.45(\text{COP}_C) + 0.12(\text{COP}_D) IPLV.IPCOP=0.01(6.394)+0.42(8.373)+0.45(10.990)+0.12(9.769)\text{IPLV.IP}_{\text{COP}} = 0.01(6.394) + 0.42(8.373) + 0.45(10.990) + 0.12(9.769) IPLV.IPCOP=0.06394+3.51666+4.94550+1.17228=9.69849.70\text{IPLV.IP}_{\text{COP}} = 0.06394 + 3.51666 + 4.94550 + 1.17228 = 9.6984 \approx 9.70

Check consistency: $\text{IPLV (kW/ton)} = \frac{3.51685}{9.6984} = 0.3626\text{ kW/ton}$ (Exact match!).

Step 4: Check ASHRAE 90.1 Path B compliance.

  • Full-Load Requirement: $0.550\text{ kW/ton} \le 0.590\text{ kW/ton}$ $\implies$ Complies (PASS)
  • Part-Load IPLV Requirement: $0.3626\text{ kW/ton} > 0.360\text{ kW/ton}$ $\implies$ Marginally Fails (FAIL)
  • To achieve compliance under Path B, the manufacturer must slightly retrim impeller staging or optimize VFD tuning at 50% load to lower IPLV below $0.360\text{ kW/ton}$, or evaluate under Path A ($0.550\text{ kW/ton} \le 0.560\text{ kW/ton}$ and $0.363\text{ kW/ton} \le 0.500\text{ kW/ton}$ $\implies$ Fully Complies under Path A!).

7. NCEES Reference Handbook Navigation & Exam Tips

  • HVAC Section: Chillers & AHRI Ratings: Find standard IPLV weighting equation coefficients ($0.01, 0.42, 0.45, 0.12$).
  • Harmonic vs. Linear IPLV Rule: Always check whether the question asks for IPLV in $\text{kW/ton}$ (harmonic mean) or $\text{EER} / \text{COP}$ (linear weighted sum).
  • Path A vs Path B Code Identification: Path A is Full-Load optimized; Path B is Part-Load (VFD) optimized.
Loading diagram...
AHRI 550/590 IPLV Part-Load Test Operating Points
Test Your Knowledge

A 400-ton water-cooled screw chiller operates with the following measured specific power consumptions at AHRI 550/590 test points: Point A (100% load) = 0.620 kW/ton; Point B (75% load) = 0.480 kW/ton; Point C (50% load) = 0.380 kW/ton; Point D (25% load) = 0.440 kW/ton. What is the Integrated Part-Load Value (IPLV.IP) of this chiller in kW/ton?

A
B
C
D
Test Your Knowledge

A chilled water plant circulates 1,200 GPM of water through an evaporator. Water enters the chiller at 56.0°F and leaves at 42.0°F. If the compressor motor consumes 466.7 kW of electrical power, what is the chiller operating COP and efficiency in kW/ton?

A
B
C
D
Test Your Knowledge

Under ASHRAE Standard 90.1, which of the following statements correctly distinguishes Path A from Path B for water-cooled chiller compliance?

A
B
C
D
Test Your Knowledge

Why does a water-cooled centrifugal chiller equipped with a Variable Frequency Drive (VFD) achieve dramatic efficiency improvements at 50% part load compared to a constant-speed chiller?

A
B
C
D