6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
Key Takeaways
- ASHRAE Standard 62.1-2022 Ventilation Rate Procedure defines breathing zone outdoor airflow as V_bz = R_p * P_z + R_a * A_z, corrected by zone air distribution effectiveness E_z to find zone outdoor airflow V_oz.
- Outdoor ventilation air introduced at the central air handling unit does NOT impose a load on the occupied space; it acts as a primary load on the central cooling and heating coils.
- The Room Sensible Heat Ratio (RSHR = q_s,space / q_total,space) establishes the slope of the space conditioning process line on the psychrometric chart, governing required supply air temperature and apparatus dew point (ADP).
- Required supply airflow is determined strictly by the room sensible heat load and temperature differential: CFM_supply = q_s,space / (1.08 * (T_room - T_supply)).
- Mixed air properties represent mass-weighted averages of outdoor air and return air: T_mix = (CFM_oa * T_oa + CFM_ra * T_ra) / CFM_supply, with total cooling coil tonnage calculated via q_total = 4.5 * CFM_supply * (h_mix - h_leaving).
6.5 Ventilation Loads & Sensible / Latent / Total Cooling Load Synthesis
The final phase of load calculations synthesizes all individual load components—envelope transmission, fenestration conduction, solar radiation, lighting, occupants, plug loads, and outdoor ventilation air—into a unified psychrometric system analysis. Correctly synthesizing these loads allows the mechanical engineer to determine required supply airflow ($\text{CFM}{\text{supply}}$), establish the supply air temperature ($T{\text{supply}}$) and apparatus dew point (ADP), evaluate mixed air properties ($T_{\text{mix}}, W_{\text{mix}}, h_{\text{mix}}$), and size central cooling and heating coils in Tons of Refrigeration (TR) or MBH.
1. ASHRAE Standard 62.1 Ventilation Rate Procedure (VRP)
Outdoor air must be continuously introduced to occupied spaces to dilute bioeffluents, volatile organic compounds (VOCs), and off-gassing from building materials.
+-----------------------------------------------------------------------------------------+
| ASHRAE 62.1 VENTILATION RATE PROCEDURE (VRP) FLOWCHART |
+-----------------------------------------------------------------------------------------+
| 1. Breathing Zone Outdoor Airflow: V_bz = (R_p * P_z) + (R_a * A_z) |
| | |
| 2. Zone Outdoor Airflow: V_oz = V_bz / E_z |
| | |
| 3. Multi-Zone System Efficiency: E_v = 1 + X_s - Z_p (or tabular lookup) |
| | |
| 4. Total System Outdoor Air Intake: V_ot = V_ou / E_v |
+-----------------------------------------------------------------------------------------+
1. Breathing Zone Outdoor Airflow ($V_{bz}$)
Where:
- $R_p = \text{Outdoor airflow rate per person } (\text{CFM/person, typically } 5\text{ to }10\text{ CFM/person})$
- $P_z = \text{Design zone population (occupants)}$
- $R_a = \text{Outdoor airflow rate per unit area } (\text{CFM/ft}^2\text{, typically } 0.06\text{ to }0.12\text{ CFM/ft}^2)$
- $A_z = \text{Zone floor area } (\text{ft}^2)$
2. Zone Outdoor Airflow ($V_{oz}$)
Where $E_z$ is the Zone Air Distribution Effectiveness:
- $E_z = 1.0$: Ceiling supply of cool air; or floor supply of warm air ($T_{\text{supply}} < T_{\text{room}} + 15^\circ\text{F}$).
- $E_z = 0.8$: Ceiling supply of warm air with ceiling return ($T_{\text{supply}} > T_{\text{room}}$), due to thermal stratification and short-circuiting.
2. Ventilation Load Allocation: Coil Load vs. Space Load
A critical distinction on the PE Mechanical exam is the physical location where outdoor air enters the building:
- Outdoor Air Introduced at Central AHU (Ventilation): Outdoor air mixes with return air in the mixing plenum before passing across the central cooling/heating coil. This air is conditioned before entering the room. Therefore, ventilation outdoor air is a central coil load, NOT a direct space load.
- Uncontrolled Infiltration Across Envelope: Outdoor air leaks directly into the room through cracks and doors without conditioning. Therefore, infiltration is a direct space sensible and latent load.
+-----------------------------------------------------------------------------------------+
| SPACE LOAD VS. CENTRAL COIL LOAD MATRIX |
+-----------------------------------------------------------------------------------------+
| LOAD COMPONENT | IMPOSES LOAD ON SPACE? | IMPOSES LOAD ON COIL? |
| -------------------------------------- | ---------------------- | --------------------- |
| Envelope Conduction (Walls/Roofs) | YES (Sensible) | YES (Sensible) |
| Window Solar Radiation (SHGC) | YES (Sensible) | YES (Sensible) |
| Lighting (Room Fraction) | YES (Sensible) | YES (Sensible) |
| Lighting (Plenum Fraction) | NO | YES (Sensible) |
| People (Occupants) | YES (Sensible+Latent) | YES (Sensible+Latent) |
| Equipment & Plug Loads | YES (Sensible) | YES (Sensible) |
| Envelope Infiltration | YES (Sensible+Latent) | YES (Sensible+Latent) |
| Central Ventilation Outdoor Air | NO | YES (Sensible+Latent) |
| Supply Fan Motor Heat | NO | YES (Sensible) |
| Return Air Duct Heat Gain | NO | YES (Sensible) |
+-----------------------------------------------------------------------------------------+
3. Sensible Heat Ratios & Supply Airflow Sizing
Psychrometric load synthesis establishes the operating state points connecting room conditions, mixed air conditions, and coil leaving conditions.
+-----------------------------------------------------------------------------------------+
| PSYCHROMETRIC LOAD PROCESS LINES (RSHR VS. GSHR) |
+-----------------------------------------------------------------------------------------+
| Humidity Ratio (W) |
| ^ |
| | (O) Outdoor Air State |
| | . |
| | . |
| | (M) Mixed Air State |
| | / . |
| | / . |
| | / . |
| | / (R) Room Air State (75°F, 50% RH) |
| | / . |
| | / . <--- Room Sensible Heat Ratio (RSHR) Slope |
| | / . |
| | (S) Supply Air State (55°F DB) |
| | . |
| | (ADP) Apparatus Dew Point |
| +--------------------------------------------------------------------> Dry Bulb (T) |
+-----------------------------------------------------------------------------------------+
1. Room Sensible Heat Ratio (RSHR)
The slope of the state line between supply air ($S$) and room air ($R$) is governed by the space loads:
2. Grand Sensible Heat Ratio (GSHR)
The slope of the state line across the cooling coil between mixed air ($M$) and leaving supply air ($S$) includes both room loads and ventilation outdoor air loads:
3. Supply Airflow ($\text{CFM}_{\text{supply}}$) Determination
Supply airflow is determined strictly by the room sensible heat load ($q_{ss}$) and design supply-to-room temperature difference (typically $\Delta T = 75^\circ\text{F} - 55^\circ\text{F} = 20^\circ\text{F}$):
4. Mixed Air Psychrometric State Evaluation
When outdoor air and return air mix in the AHU plenum, the mixed air state ($M$) represents a mass-weighted average:
+-----------------------------------------------------------------------------------------+
| MIXED AIR PSYCHROMETRIC EQUATIONS |
+-----------------------------------------------------------------------------------------+
| Mixed Dry-Bulb: T_mix = (CFM_oa * T_oa + CFM_ra * T_ra) / CFM_supply |
| Mixed Humidity: W_mix = (CFM_oa * W_oa + CFM_ra * W_ra) / CFM_supply |
| Mixed Enthalpy: h_mix = (CFM_oa * h_oa + CFM_ra * h_ra) / CFM_supply |
+-----------------------------------------------------------------------------------------+
Letting the outdoor air fraction be $X_{oa} = \frac{\text{CFM}{oa}}{\text{CFM}{\text{supply}}}$:
5. Total Cooling Coil Capacity & Tonnage Calculations
Once mixed air and leaving coil states are established, central coil capacity is calculated using the three standard moist air equations:
1. Coil Sensible Capacity ($q_{\text{coil, sensible}}$)
2. Coil Latent Capacity ($q_{\text{coil, latent}}$)
3. Total Coil Capacity ($q_{\text{coil, total}}$)
Fan Heat Gain & Duct Parasitic Corrections
- Supply Fan Temperature Rise (Draw-Through Fan): The fan is located downstream of the cooling coil. Motor and impeller mechanical dissipation heat the supply air before it reaches the zone: Typically, $\Delta T_{\text{fan}} = 1.0^\circ\text{F}\text{ to }2.5^\circ\text{F}$. To deliver $55^\circ\text{F}$ air to the room, the coil must leave at $T_{\text{coil, leaving}} = 55 - \Delta T_{\text{fan}} = 53^\circ\text{F}$.
- Duct Heat Gain: Conditioned supply air traveling through unconditioned ceiling plenums absorbs $1.0^\circ\text{F}\text{ to }2.0^\circ\text{F}$ of sensible heat.
6. NCEES Reference Handbook Navigation Tactics
- ASHRAE 62.1 Equations: Search
"Ventilation Rate Procedure"or"Breathing Zone"in Section 7 (HVAC & Refrigeration Applications) to find $V_{bz} = R_p P_z + R_a A_z$ and $E_z$ tables. - Psychrometric Equations: Search
"Sensible Heat Ratio"or"RSHR"in Section 6 (Psychrometrics) to find formulas for RSHR, GSHR, mixed air equations, and shortcut constants ($1.08, 4840, 4.5$). - Fan Temperature Rise: Search
"Fan Heat Gain"to find the exact mechanical energy temperature rise equation.
7. Master Worked Computational Example
Comprehensive Building Cooling Load & Psychrometric Synthesis
A single-zone commercial office building ($12,000\text{ ft}^2$, $14\text{ ft}$ floor-to-floor) in Charlotte, NC has the following design parameters:
- Indoor Design Conditions: $75^\circ\text{F}$ DB, $50%\text{ RH}$ ($W_r = 0.00925\text{ lb}w/\text{lb}{da}$, $h_r = 28.14\text{ Btu/lb}$).
- Outdoor Design Conditions (0.4%): $95^\circ\text{F}$ DB, $75^\circ\text{F}$ MCWB ($W_o = 0.01410\text{ lb}w/\text{lb}{da}$, $h_o = 38.60\text{ Btu/lb}$).
- Occupancy: 100 people ($q_s = 250\text{ Btu/hr}$, $q_l = 200\text{ Btu/hr}$ per person).
- ASHRAE 62.1 Ventilation Rates: $R_p = 5\text{ CFM/person}$, $R_a = 0.06\text{ CFM/ft}^2$, $E_z = 1.0$.
- Lighting & Plug Loads: Lighting = $1.0\text{ W/ft}^2$ (all entering room space); Plug Loads = $0.75\text{ W/ft}^2$.
- Building Envelope & Glazing Transmission: Net space envelope conduction + solar heat gain = $78,000\text{ Btu/hr}$ (100% sensible).
- Infiltration: $0.15\text{ ACH}$ (unconditioned direct space infiltration).
- Supply Air Conditions: Air leaves cooling coil at $53.0^\circ\text{F}$ DB saturated ($W_{\text{coil}} = 0.00850\text{ lb}w/\text{lb}{da}$, $h_{\text{coil}} = 22.00\text{ Btu/lb}$). Supply fan adds $2.0^\circ\text{F}$ of draw-through heat, delivering air to the space at $T_{\text{supply}} = 55.0^\circ\text{F}$ DB.
Calculate: (1) Required ventilation airflow, (2) Space sensible and latent loads, (3) Required supply airflow, (4) Mixed air psychrometric properties, (5) Total cooling coil capacity and chiller tonnage.
Solution Step-by-Step:
Step 1: Calculate Outdoor Ventilation Airflow (ASHRAE 62.1)
Step 2: Calculate Infiltration Load Entering Space
Step 3: Calculate Internal Heat Gains Entering Space
- Occupants: $q_{s,\text{occ}} = 100 \times 250 = 25,000\text{ Btu/hr}$; $q_{l,\text{occ}} = 100 \times 200 = 20,000\text{ Btu/hr}$
- Lighting: $q_{\text{light}} = 12,000\text{ ft}^2 \times 1.0\text{ W/ft}^2 \times 3.412 = 40,944\text{ Btu/hr}$
- Plug Loads: $q_{\text{plug}} = 12,000\text{ ft}^2 \times 0.75\text{ W/ft}^2 \times 3.412 = 30,708\text{ Btu/hr}$
Step 4: Sum Total Space Loads & Determine Supply Airflow ($\text{CFM}_{\text{supply}}$)
Step 5: Evaluate Mixed Air State at AHU Intake
Step 6: Sizing Central Cooling Coil Capacity & Tonnage
(Notice that the central coil capacity of 24.37 Tons exceeds the net space load of 17.80 Tons by 6.57 Tons due to the ventilation outdoor air load and fan heat gain!)
An air handling unit supplies 10,000 CFM of total airflow to a conditioned building. The system introduces 2,500 CFM of outdoor ventilation air at 92°F DB and 76°F WB (enthalpy = 39.5 Btu/lb). The return air from the space is at 76°F DB and 50% RH (enthalpy = 28.5 Btu/lb). What is the mixed air dry-bulb temperature and enthalpy entering the cooling coil?
A conditioned commercial zone has a calculated sensible cooling load of 162,000 Btu/hr and a latent cooling load of 38,000 Btu/hr. If the indoor space is maintained at 75°F DB and conditioned air is supplied to the space at 55°F DB, what is the required supply airflow to satisfy the space sensible load?
A cooling coil receives 12,000 CFM of mixed air at an entering enthalpy of 33.20 Btu/lb and discharges saturated air at a leaving enthalpy of 21.80 Btu/lb. What is the total cooling capacity of the coil in Tons of Refrigeration?
Which of the following correctly defines the Room Sensible Heat Ratio (RSHR) and its primary geometric significance on the psychrometric chart?