6.2 Water Supply Fixture Units and Estimating Demand

Key Takeaways

  • IPC Table E103.3(2) assigns a private bathroom group 3.6 water supply fixture units with a flush tank and 8.0 with a flushometer valve.
  • IPC Table E103.3(2) assigns a public water closet 5.0 wsfu with a flush tank and 10.0 wsfu with a flushometer valve.
  • Table E103.3(2) footnote a states that separate hot and cold water loads are each three-fourths of the total load for the fixture.
  • IPC Table E103.3(3) converts 10 wsfu to 14.6 gpm in a flush tank system but 27.0 gpm in a flushometer valve system.
  • IPC E104.1 requires supply load to be determined in water supply fixture units from Table E103.3(2), with unlisted fixtures assigned the value of a fixture with similar flow characteristics.
Last updated: September 2026

Why fixture units exist

No building ever runs every fixture at once. If you sized a 30-unit apartment building's water service for the simultaneous full flow of every fixture, you would install a main three times larger than anything the building will ever use.

The water supply fixture unit (wsfu) is a weighted probability index. Each fixture gets a load value reflecting how much water it uses, how fast, and how often. Add the load values, then convert the total to gallons per minute through a demand curve that flattens sharply as the count rises — the Hunter curve, tabulated in Table E103.3(3).

Do not confuse wsfu with drainage fixture units (dfu) from IPC Table 709.1. They are different systems with different numbers for the same fixture. A private lavatory is 0.7 wsfu on the supply side and 1 dfu on the drainage side.

Table E103.3(2) — load values assigned to fixtures

FixtureOccupancySupply controlColdHotTotal
Bathroom groupPrivateFlush tank2.71.53.6
Bathroom groupPrivateFlushometer valve6.03.08.0
Water closetPrivateFlush tank2.22.2
Water closetPrivateFlushometer valve6.06.0
Water closetPublicFlush tank5.05.0
Water closetPublicFlushometer valve10.010.0
Water closetPublic or privateFlushometer tank2.02.0
UrinalPublic1-inch flushometer valve10.010.0
UrinalPublic3/4-inch flushometer valve5.05.0
UrinalPublicFlush tank3.03.0
LavatoryPrivateFaucet0.50.50.7
LavatoryPublicFaucet1.51.52.0
BathtubPrivateFaucet1.01.01.4
BathtubPublicFaucet3.03.04.0
Shower headPrivateMixing valve1.01.01.4
Shower headPublicMixing valve3.03.04.0
Kitchen sinkPrivateFaucet1.01.01.4
Kitchen sinkHotel, restaurantFaucet3.03.04.0
Service sinkOffices, etc.Faucet2.252.253.0
Laundry trays (1 to 3)PrivateFaucet1.01.01.4
Dishwashing machinePrivateAutomatic1.41.4
Washing machine (8 lb)PrivateAutomatic1.01.01.4
Washing machine (8 lb)PublicAutomatic2.252.253.0
Washing machine (15 lb)PublicAutomatic3.03.04.0
BidetPrivateFaucet1.51.52.0
Combination fixturePrivateFaucet2.252.253.0
Drinking fountainOffices, etc.3/8-inch valve0.250.25

Footnote a carries two rules worth memorizing:

  1. For fixtures not listed, assume loads by comparing to a listed fixture using water in similar quantities at similar rates.
  2. The separate hot and cold water loads are each three-fourths of the total load for the fixture. Check it: a private lavatory is 0.7 total and 0.5 each side; 0.75 x 0.7 = 0.525, rounded to 0.5. A private bathtub is 1.4 total and 1.0 each side; 0.75 x 1.4 = 1.05.

The hot-plus-cold sum therefore exceeds the total (0.5 + 0.5 = 1.0 versus a total of 0.7), because hot and cold are rarely drawn at full rate simultaneously.

The bathroom group shortcut

A "bathroom group" bundles a water closet, a lavatory and a bathtub or shower into a single value. A private bathroom group with a flush tank water closet is 3.6 wsfu. Adding the same three fixtures individually would give 2.2 + 0.7 + 1.4 = 4.3 wsfu. The grouped value is lower because the code recognizes that one person uses one bathroom at a time.

Note the enormous jump for flushometer valves: the same private bathroom group goes from 3.6 to 8.0 wsfu. A public water closet goes from 5.0 to 10.0. That reflects the instantaneous 25 gpm draw of a flushometer valve.

Table E103.3(3) — converting load to demand

The table has two separate sets of columns: systems predominantly for flush tanks and systems predominantly for flushometer valves.

Load (wsfu)Demand, flush tank (gpm)Demand, flushometer valve (gpm)
59.415.0
1014.627.0
1517.531.0
2019.635.0
3023.342.0
5029.150.0
10043.567.5
20065.090.0
500124.0143.0
1,000208.0208.0

Three lessons from these numbers:

  1. Demand is strongly nonlinear. Going from 10 to 100 wsfu — a tenfold increase in fixtures — raises flush-tank demand only from 14.6 to 43.5 gpm, a threefold increase.
  2. Flushometer systems demand much more at low counts. At 10 wsfu, flushometer demand is nearly double flush-tank demand.
  3. The two curves converge. At 1,000 wsfu both read 208 gpm, because with enough fixtures the statistics dominate the device type. The flushometer column does not even begin until 5 wsfu.

Worked example: a 12-unit apartment building

Each unit has one private bathroom group (flush tank), one kitchen sink and one clothes washer. The building also has a shared laundry with two 15-pound public washing machines and one service sink.

Total (combined) load:

ItemEachCountSubtotal
Private bathroom group, flush tank3.61243.2
Kitchen sink, private1.41216.8
Washing machine (8 lb), private1.41216.8
Washing machine (15 lb), public4.028.0
Service sink3.013.0
Total87.8 wsfu

Demand: this is a flush-tank building, so read the flush tank column. 80 wsfu gives 38.0 gpm and 90 wsfu gives 41.0 gpm. Interpolating at 87.8 wsfu gives roughly 40.3 gpm; sizing conservatively at the next tabulated value, use 41 gpm.

Hot water side: use the hot column of Table E103.3(2) for the hot branch. Bathroom group hot is 1.5 each, kitchen sink hot 1.0, private washer hot 1.0, public washer hot 3.0, service sink hot 2.25:

(12 x 1.5) + (12 x 1.0) + (12 x 1.0) + (2 x 3.0) + 2.25 = 18 + 12 + 12 + 6 + 2.25 = 50.25 wsfu hot, which reads about 29 gpm from the flush tank column.

The five-step E104.1 procedure

  1. Supply load in wsfu from Table E103.3(2), using the combined column for the service and main distribution pipe.
  2. Minimum daily static service pressure from the local water authority, adjusted for:
    • 0.5 psi deducted per foot the highest outlet is above the source (added per foot below);
    • where a PRV is installed, the available pressure is 80 percent of the minimum daily static pressure at the source, or the PRV set pressure, whichever is smaller;
    • deduct all pressure losses from special equipment (backflow preventer, filter, softener) per the manufacturer;
    • deduct pressure in excess of 8 psi required by special fixtures such as a temperature-controlled shower or a flushometer tank water closet.
  3. Maximum developed length = actual pipe length from the source to the most remote fixture, including hot (through the water heater) or cold branches, multiplied by 1.2 to account for fittings.
  4. Read the service, meter and main distribution size from Table E104.1 at the intersection of the pressure range, developed length column and total demand.
  5. Size each distribution pipe by working back from the most remote outlet on each branch, accumulating the related hot or cold column values. No branch or main needs to be larger than the main distribution pipe established in step 4.
Loading diagram...
Fixture units to demand to pipe size
Test Your Knowledge

What is the water supply fixture unit value of a private bathroom group served by a flushometer valve water closet?

A
B
C
D
Test Your Knowledge

A load of 10 water supply fixture units occurs in a system predominantly served by flushometer valves. What is the estimated demand?

A
B
C
D
Test Your Knowledge

Under footnote a of Table E103.3(2), how are the separate hot and cold loads for a fixture related to its total load?

A
B
C
D
Test Your Knowledge

Under the Appendix E104.1 procedure, how much pressure is deducted for elevation where the highest outlet is 28 feet above the source of supply?

A
B
C
D